Site Information:Page 1:
Customer: Automated Building Components, Inc.Job Number: T201946-REP
Job Description: Dsgnr:Shane Anders
Address:
Job Engineering Criteria:
Design Code: IRC 2018 IntelliVIEW Version: 19.02.02B through 20.01.00
JRef #: 1WVd90730015
Wind Standard: ASCE 7-16 Wind Speed (mph): 115 Roof Load (psf): 35.00-10.00- 0.00-10.00
Building Type: Closed Floor Load (psf): None
This package contains general notes pages, 6 truss drawing(s) and 2 detail(s).
Item Drawing Number Truss Item Drawing Number Truss
1 140.20.0736.19683 D1 2 140.20.0736.32457 D2
3 140.20.0736.39280 D4 4 139.20.1607.23863 D1REP
5 140.20.0759.45007 D2REP 6 140.20.0916.03350 D4REP
7 BRCLBSUB0119 8 160TL
Printed 5/19/2020 9:26:03 AM
05/19/2020
General Notes
Truss Design Engineer Scope of Work, Design Assumptions and Design Responsibilities:
The design responsibilities assumed in the preparation of these design drawings are those specified in ANSI/TPI 1,
Chapter 2; and the National Design Standard for Metal Plate Connected Wood Truss Construction, by the Truss Plate
Institute. The truss component designs conform to the applicable provisions of ANSI/TPI 1 and NDS, the National Design
Specification for Wood Construction by AWC. The truss component designs are based on the specified loading and
dimension information furnished by others to the Truss Design Engineer. The Truss Design Engineer has no duty to
independently verify the accuracy or completeness of the information provided by others and may rely on that information
without liability. The responsibility for verification of that information remains with others neither employed nor controlled
by the Truss Design Engineer. The Truss Design Engineer’s seal and signature on the attached drawings, or cover page
listing these drawings, indicates acceptance of professional engineering responsibility solely for the truss component
designs and not for the technical information furnished by others which technical information and consequences thereof
remain their sole responsibility.
The suitability and use of these drawings for any particular structure is the responsibility of the Building Designer in
accordance with ANSI/TPI 1 Chapter 2. The Building Designer is responsible for determining that the dimensions and
loads for each truss component match those required by the plans and by the actual use of the individual component, and
for ascertaining that the loads shown on the drawings meet or exceed applicable building code requirements and any
additional factors required in the particular application. Truss components using metal connector plates with integral teeth
shall not be placed in environments that will cause the moisture content of the wood in which plates are embedded to
exceed 19% and/or cause corrosion of connector plates and other metal fasteners.
The Truss Design Engineer shall not be responsible for items beyond the specific scope of the agreed contracted work set
forth herein, including but not limited to: verifying the dimensions of the truss component, calculation of any of the truss
component design loads, inspection of the truss components before or after installation, the design of temporary or
permanent bracing and their attachment required in the roof and/or floor systems, the design of diaphragms or shear
walls, the design of load transfer connections to and from diaphragms and shear walls, the design of load transfer to the
foundation, the design of connections for truss components to their bearing supports, the design of the bearing supports,
installation of the truss components, observation of the truss component installation process, review of truss assembly
procedures, sequencing of the truss component installation, construction means and methods, site and/or worker safety in
the installation of the truss components and/or its connections.
This document may be a high quality facsimile of the original engineering document which is a digitally signed electronic
file with third party authentication. A wet or embossed seal copy of this engineering document is available upon request.
Temporary Lateral Restraint and Bracing:
Temporary lateral restraint and diagonal bracing shall be installed according to the provisions of BCSI chapters B1, B2,
B7 and/or B10 (Building Component Safety Information, by TPI and SBCA), or as specified by the Building Designer or
other Registered Design Professional. The required locations for lateral restraint and/or bracing depicted on these
drawings are only for the permanent lateral support of the truss members to reduce buckling lengths, and do not apply to
and may not be relied upon for the temporary stability of the truss components during their installation.
Permanent Lateral Restraint and Bracing:
The required locations for lateral restraint or bracing depicted on these drawings are for the permanent lateral support of
the truss members to reduce buckling lengths. Permanent lateral support shall be installed according to the provisions of
BCSI chapters B3, B7 and/or B10, or as specified by the Building Designer or other Registered Design Professional.
These drawings do not depict or specify installation/erection bracing, wind bracing, portal bracing or similar building
stability bracing which are parts of the overall building design to be specified, designed and detailed by the Building
Designer.
Connector Plate Information:
Alpine connector plates are made of ASTM A653 or ASTM A1063 galvanized steel with the following designations,
gauges and grades: W=Wave, 20ga, grade 40; H=High Strength, 20ga, grade 60; S=Super Strength, 18ga, grade 60.
Information on model code compliance is contained in the ICC Evaluation Service report ESR-1118, available on-line at
www.icc-es.org.
Fire Retardant Treated Lumber:
Fire retardant treated lumber must be properly re-dried and maintained below 19% or less moisture level through all
stages of construction and usage. Fire retardant treated lumber may be more brittle than untreated lumber. Special
handling care must be taken to prevent breakage during all handling activities.
Page 1 of 3
General Notes (continued)
Key to Terms:
Information provided on drawings reflects a summary of the pertinent information required for the truss design. Detailed
information on load cases, reactions, member lengths, forces and members requiring permanent lateral support may be
found in calculation sheets available upon written request.
BCDL = Bottom Chord standard design Dead Load in pounds per square foot.
BCLL = Bottom Chord standard design Live Load in pounds per square foot.
CL = Certified lumber.
Des Ld = total of TCLL, TCDL, BCLL and BCDL Design Load in pounds per square foot.
FRT = Fire Retardant Treated lumber.
FRT-DB = D-Blaze Fire Retardant Treated lumber.
FRT-DC = Dricon Fire Retardant Treated lumber.
FRT-FP = FirePRO Fire Retardant Treated lumber.
FRT-FL = FlamePRO Fire Retardant Treated lumber.
FRT-FT = FlameTech Fire Retardant Treated lumber.
FRT-PG = PYRO-GUARD Fire Retardant Treated lumber.
g = green lumber.
HORZ(LL) = maximum Horizontal panel point deflection due to Live Load, in inches.
HORZ(TL) = maximum Horizontal panel point long term deflection in inches, due to Total Load, including creep
adjustment.
HPL = additional Horizontal Load added to a truss Piece in pounds per linear foot or pounds.
Ic = Incised lumber.
FJ = Finger Jointed lumber.
L/# = user specified divisor for limiting span/deflection ratio for evaluation of actual L/defl value.
L/defl = ratio of Length between bearings, in inches, divided by the vertical Deflection due to creep, in inches, at the
referenced panel point. Reported as 999 if greater than or equal to 999.
Loc = Location, starting location of left end of bearing or panel point (joint) location of deflection.
Max BC CSI = Maximum bending and axial Combined Stress Index for Bottom Chords for of all load cases.
Max TC CSI = Maximum bending and axial Combined Stress Index for Top Chords for of all load cases.
Max Web CSI= Maximum bending and axial Combined Stress Index for Webs for of all load cases.
NCBCLL = Non-Concurrent Bottom Chord design Live Load in pounds per square foot.
PL = additional Load applied at a user specified angle on a truss Piece in pounds per linear foot or pounds.
PLB = additional vertical load added to a Bottom chord Piece of a truss in pounds per linear foot or pounds
PLT = additional vertical load added to a Top chord Piece of a truss in pounds per linear foot or pounds.
PP = Panel Point.
R = maximum downward design Reaction, in pounds, from all specified gravity load cases, at the indicated location (Loc).
-R = maximum upward design Reaction, in pounds, from all specified gravity load cases, at the identified location (Loc).
Rh = maximum horizontal design Reaction in either direction, in pounds, from all specified gravity load cases, at the
indicated location (Loc).
RL = maximum horizontal design Reaction in either direction, in pounds, from all specified non-gravity (wind or seismic)
load cases, at the indicated location (Loc).
Rw = maximum downward design Reaction, in pounds, from all specified non-gravity (wind or seismic) load cases, at the
identified location (Loc).
TCDL = Top Chord standard design Dead Load in pounds per square foot.
TCLL = Top Chord standard design Live Load in pounds per square foot.
U = maximum Upward design reaction, in pounds, from all specified non-gravity (wind or seismic) load cases, at the
indicated location (Loc).
VERT(CL) = maximum Vertical panel point deflection in inches due to Live Load and Creep Component of Dead Load in
inches.
VERT(CTL) = maximum Vertical panel point deflection ratios due to Live Load and Creep Component of Dead Load, and
maximum long term Vertical panel point deflection in inches due to Total load, including creep adjustment.
VERT(LL) = maximum Vertical panel point deflection in inches due to Live Load.
VERT(TL) = maximum Vertical panel point long term deflection in inches due to Total load, including creep adjustment.
W = Width of non-hanger bearing, in inches.
Refer to ASCE-7 for Wind and Seismic abbreviations.
Uppercase Acronyms not explained above are as defined in TPI 1.
Page 2 of 3
References:
1. AWC: American Wood Council; 222 Catoctin Circle SE, Suite 201; Leesburg, VA 20175; www.awc.org.
2. ICC: International Code Council; www.iccsafe.org.
3. Alpine, a division of ITW Building Components Group Inc.: 13723 Riverport Drive, Suite 200, Maryland Heights, MO
63043; www.alpineitw.com.
4. TPI: Truss Plate Institute, 2670 Crain Highway, Suite 203, Waldorf, MD 20601; www.tpinst.org.
5. SBCA: Wood Truss Council of America, 6300 Enterprise Lane, Madison, WI 53719; www.sbcindustry.com.
Page 3 of 3
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;Bot chord: 2x4 SPF 1650f-1.5E;
Webs: 2x4 SPF #1/#2; w2,w3,w10 2x3 SPF #3; w4,w5,w9 2x3 SPF #1/#2;
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Purlins
In lieu of structural panels use purlins to brace all flat
TC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Wind loading based on both gable and hip roof types.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
P 1123 /-/-/499 /-/301
L 2775 /-/-/1103 /-/-
J 1004 /-/-/485 /-/-
Wind reactions based on MWFRS
P Brg Width = 5.5 Min Req =1.8
L Brg Width = 5.5 Min Req =4.0
J Brg Width = 5.5 Min Req =1.6
Bearings P, L, & J Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - C 89 -1123
C - D 184 -579
D - E 407 0
Chords Tens.Comp.
E - F 406 0
F - G 189 -722
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
O - N 747 -154
Chords Tens.Comp.
K - J 638 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - P 95 -1065
B - O 660 0
C - N 137 -668
D - N 583 -16
D - L 59 -1122
E - L 265 -724
Webs Tens.Comp.
L - F 54 -1014
F - K 742 -59
K - G 207 -569
G - J 0 -759
H - J 131 -408
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.89 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.032 O 999 240
VERT(CL):0.055 O 999 180
HORZ(LL):0.014 C - -
HORZ(TL):0.023 C - -
Creep Factor: 2.0
Max TC CSI:0.902
Max BC CSI:0.592
Max Web CSI:0.907
VIEW Ver: 19.02.02B.0122.16
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D1
Ply: 1
Qty:7
SEQN:165524 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T10
DrwNo:140.20.0736.19683
DW /BM 05/18/2020
w2
w3
w4
w5
w9 w10
20'6"4 18'4"12
6'10"12
6'10"12
13'5"8
6'6"12
20'5"13
7'0"5
25'5"8
4'11"11
32'8"11
7'3"3
38'11"
6'2"5
6'8"4
6'8"4
13'5"8
6'9"4
19'5"8
6'
20'5"13
1'0"5
29'7"4
9'1"7
38'11"
9'3"121'3"1'3"
1'2"11'9"1412'0"3(a)
(a)(a)(a)
(a)
A
B
C
D E F
G
H
I
JKLMNOP
9.5
12
3X6
3X4 3X4
3X4
5X6
3X4 3X8
1.5X4
4X8
5X6
4X4
3X4
1.5X4
3X4
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;Bot chord: 2x4 SPF 1650f-1.5E;
Webs: 2x4 SPF #1/#2; w2,w3,w10 2x3 SPF #3; w4,w5,w9 2x3 SPF #1/#2;
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Loading
Bottom chord checked for 10.00 psf non-concurrentlive load.
Purlins
In lieu of structural panels use purlins to brace all flat
TC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Wind loading based on both gable and hip roof types.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
P 1123 /-/-/499 /-/301
L 2775 /-/-/1103 /-/-
J 1004 /-/-/485 /-/-
Wind reactions based on MWFRS
P Brg Width = 5.5 Min Req =1.8
L Brg Width = 5.5 Min Req =4.0
J Brg Width = 5.5 Min Req =1.6
Bearings P, L, & J Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - C 89 -1123
C - D 184 -579
D - E 407 0
Chords Tens.Comp.
E - F 406 0
F - G 189 -722
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
O - N 747 -154
Chords Tens.Comp.
K - J 638 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - P 95 -1065
B - O 660 0
C - N 137 -668
D - N 583 -16
D - L 59 -1122
E - L 265 -724
Webs Tens.Comp.
L - F 54 -1014
F - K 742 -59
K - G 207 -569
G - J 0 -759
H - J 131 -408
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.89 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.032 O 999 240
VERT(CL):0.055 O 999 180
HORZ(LL):0.014 C - -
HORZ(TL):0.023 C - -
Creep Factor: 2.0
Max TC CSI:0.902
Max BC CSI:0.592
Max Web CSI:0.907
VIEW Ver: 19.02.02B.0122.16
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D1
Ply: 1
Qty:7
SEQN:165524 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T10
DrwNo:140.20.0736.19683
DW /BM 05/18/2020
w2
w3
w4
w5
w9 w10
20'6"4 18'4"12
6'10"12
6'10"12
13'5"8
6'6"12
20'5"13
7'0"5
25'5"8
4'11"11
32'8"11
7'3"3
38'11"
6'2"5
6'8"4
6'8"4
13'5"8
6'9"4
19'5"8
6'
20'5"13
1'0"5
29'7"4
9'1"7
38'11"
9'3"121'3"1'3"
1'2"11'9"1412'0"3(a)
(a)(a)(a)
(a)
A
B
C
D E F
G
H
I
JKLMNOP
9.5
12
3X6
3X4 3X4
3X4
5X6
3X4 3X8
1.5X4
4X8
5X6
4X4
3X4
1.5X4
3X4
05/19/2020
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;TC2 2x4 SPF #1/#2;
Bot chord: 2x4 SPF 1650f-1.5E;Webs: 2x4 SPF #1/#2; w2,w3,w10 2x3 SPF #3;w5 2x4 SPF 1650f-1.5E; w9 2x3 SPF #1/#2;
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Purlins
In lieu of structural panels use purlins to brace all flatTC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
O 637 /-/-/256 /-/301
M 2417 /-/-/1056 /-/-
J 1720 /-/-/788 /-/-
Wind reactions based on MWFRS
O Brg Width = 5.5 Min Req =1.5
M Brg Width = 5.5 Min Req =3.4
J Brg Width = 5.5 Min Req =2.7
Bearings O, M, & J Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - C 60 -459
C - D 393 -48
D - E 278 -854
Chords Tens.Comp.
E - F 278 -854
F - G 304 -1709
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
L - K 981 0
Chords Tens.Comp.
K - J 1373 -37
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - O 72 -581
C - M 158 -672
M - D 166 -1788
D - L 1252 -150
E - L 242 -659
Webs Tens.Comp.
F - K 633 -35
K - G 182 -436
G - J 59 -1670
H - J 155 -507
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.89 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.066 K 999 240
VERT(CL):0.108 K 999 180
HORZ(LL):0.035 H - -
HORZ(TL):0.057 H - -
Creep Factor: 2.0
Max TC CSI:0.789
Max BC CSI:0.708
Max Web CSI:0.775
VIEW Ver: 19.02.02B.0122.16
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D2
Ply: 1
Qty:8
SEQN:165527 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T2
DrwNo:140.20.0736.32457
DW /BM 05/18/2020
TC2
w2
w3
w5
w9 w10
10'8"12 28'2"4
6'4"15
6'4"15
13'5"8
7'0"9
19'5"8
6'
25'5"8
6'
32'2"10
6'9"2
38'11"
6'8"6
6'2"7
6'2"7
10'8"12
4'6"5
19'5"8
8'8"12
29'2"4
9'8"12
38'11"
9'8"121'3"1'3"
1'2"11'9"1412'0"3(a)(a)(a)(a)
(a)
A
B
C
D E F
G
H
I
JKLMNO
9.5
12
4X4
2X4 3X4
3X4
4X4
5X6 1.5X4
6X8
5X6
4X4
4X6
2X4
4X6
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;TC2 2x4 SPF #1/#2;
Bot chord: 2x4 SPF 1650f-1.5E;Webs: 2x4 SPF #1/#2; w2,w3,w10 2x3 SPF #3;w5 2x4 SPF 1650f-1.5E; w9 2x3 SPF #1/#2;
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Purlins
In lieu of structural panels use purlins to brace all flatTC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
O 637 /-/-/256 /-/301
M 2417 /-/-/1056 /-/-
J 1720 /-/-/788 /-/-
Wind reactions based on MWFRS
O Brg Width = 5.5 Min Req =1.5
M Brg Width = 5.5 Min Req =3.4
J Brg Width = 5.5 Min Req =2.7
Bearings O, M, & J Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - C 60 -459
C - D 393 -48
D - E 278 -854
Chords Tens.Comp.
E - F 278 -854
F - G 304 -1709
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
L - K 981 0
Chords Tens.Comp.
K - J 1373 -37
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - O 72 -581
C - M 158 -672
M - D 166 -1788
D - L 1252 -150
E - L 242 -659
Webs Tens.Comp.
F - K 633 -35
K - G 182 -436
G - J 59 -1670
H - J 155 -507
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.89 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.066 K 999 240
VERT(CL):0.108 K 999 180
HORZ(LL):0.035 H - -
HORZ(TL):0.057 H - -
Creep Factor: 2.0
Max TC CSI:0.789
Max BC CSI:0.708
Max Web CSI:0.775
VIEW Ver: 19.02.02B.0122.16
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D2
Ply: 1
Qty:8
SEQN:165527 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T2
DrwNo:140.20.0736.32457
DW /BM 05/18/2020
TC2
w2
w3
w5
w9 w10
10'8"12 28'2"4
6'4"15
6'4"15
13'5"8
7'0"9
19'5"8
6'
25'5"8
6'
32'2"10
6'9"2
38'11"
6'8"6
6'2"7
6'2"7
10'8"12
4'6"5
19'5"8
8'8"12
29'2"4
9'8"12
38'11"
9'8"121'3"1'3"
1'2"11'9"1412'0"3(a)(a)(a)(a)
(a)
A
B
C
D E F
G
H
I
JKLMNO
9.5
12
4X4
2X4 3X4
3X4
4X4
5X6 1.5X4
6X8
5X6
4X4
4X6
2X4
4X6
05/19/2020
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;TC2 2x4 SPF #1/#2;
Bot chord: 2x4 SPF 1650f-1.5E;Webs: 2x4 SPF #1/#2; w3,w9 2x3 SPF #3;w4 2x3 SPF #1/#2; w8 2x4 SPF 1650f-1.5E;
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Purlins
In lieu of structural panels use purlins to brace all flatTC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right cantilever is exposed to wind
Wind loading based on both gable and hip roof types.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
N 1772 /-/-/802 /-/301
K 2695 /-/-/1005 /192 /-
O 389 /-/-/291 /-/-
Wind reactions based on MWFRS
N Brg Width = 5.5 Min Req =2.8
K Brg Width = 5.5 Min Req =3.9
O Brg Width = 3.5 Min Req =1.5
Bearings N, K, & O Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
C - D 325 -1784
D - E 258 -942
Chords Tens.Comp.
E - F 258 -942
F - G 692 -154
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
N - M 1429 -108M - L 1041 -51
Chords Tens.Comp.
L - K 394 -106K - J 481 -266
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - N 197 -509
N - C 26 -1744
C - M 243 -441
M - D 637 -91
E - L 238 -660
Webs Tens.Comp.
L - F 1298 -218
F - K 356 -2031
K - G 287 -638
H - J 197 -435
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.89 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.066 M 999 240
VERT(CL):0.111 M 999 180
HORZ(LL):0.036 C - -
HORZ(TL):0.058 C - -
Creep Factor: 2.0
Max TC CSI:0.963
Max BC CSI:0.719
Max Web CSI:0.933
VIEW Ver: 19.02.02B.0122.16
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D4
Ply: 1
Qty:6
SEQN:165530 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T12
DrwNo:140.20.0736.39280
DW /BM 05/18/2020
TC2
w3
w4
w8 w9
28'8"4 9'7"4 7"8
6'8"6
6'8"6
13'5"8
6'9"2
19'5"8
6'
25'5"8
6'
32'0"4
6'6"12
38'11"
6'10"12
9'8"12
9'8"12
19'5"8
9'8"12
28'10"1
9'4"9
38'11"
10'0"151'3"1'3"
1'2"11'9"1412'0"3(a)
(a)(a)(a)(a)
(a)
A
B
C
D E F
G
H
I
JKLMNO
9.5
12
2X4
4X6
4X6
4X4
5X6 1.5X4
6X8
5X6
4X4
3X4
1.5X4
3X4
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;TC2 2x4 SPF #1/#2;
Bot chord: 2x4 SPF 1650f-1.5E;Webs: 2x4 SPF #1/#2; w3,w9 2x3 SPF #3;w4 2x3 SPF #1/#2; w8 2x4 SPF 1650f-1.5E;
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Purlins
In lieu of structural panels use purlins to brace all flatTC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right cantilever is exposed to wind
Wind loading based on both gable and hip roof types.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
N 1772 /-/-/802 /-/301
K 2695 /-/-/1005 /192 /-
O 389 /-/-/291 /-/-
Wind reactions based on MWFRS
N Brg Width = 5.5 Min Req =2.8
K Brg Width = 5.5 Min Req =3.9
O Brg Width = 3.5 Min Req =1.5
Bearings N, K, & O Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
C - D 325 -1784
D - E 258 -942
Chords Tens.Comp.
E - F 258 -942
F - G 692 -154
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
N - M 1429 -108M - L 1041 -51
Chords Tens.Comp.
L - K 394 -106K - J 481 -266
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - N 197 -509
N - C 26 -1744
C - M 243 -441
M - D 637 -91
E - L 238 -660
Webs Tens.Comp.
L - F 1298 -218
F - K 356 -2031
K - G 287 -638
H - J 197 -435
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.89 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.066 M 999 240
VERT(CL):0.111 M 999 180
HORZ(LL):0.036 C - -
HORZ(TL):0.058 C - -
Creep Factor: 2.0
Max TC CSI:0.963
Max BC CSI:0.719
Max Web CSI:0.933
VIEW Ver: 19.02.02B.0122.16
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D4
Ply: 1
Qty:6
SEQN:165530 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T12
DrwNo:140.20.0736.39280
DW /BM 05/18/2020
TC2
w3
w4
w8 w9
28'8"4 9'7"4 7"8
6'8"6
6'8"6
13'5"8
6'9"2
19'5"8
6'
25'5"8
6'
32'0"4
6'6"12
38'11"
6'10"12
9'8"12
9'8"12
19'5"8
9'8"12
28'10"1
9'4"9
38'11"
10'0"151'3"1'3"
1'2"11'9"1412'0"3(a)
(a)(a)(a)(a)
(a)
A
B
C
D E F
G
H
I
JKLMNO
9.5
12
2X4
4X6
4X6
4X4
5X6 1.5X4
6X8
5X6
4X4
3X4
1.5X4
3X4
05/19/2020
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;Bot chord: 2x4 SPF 1650f-1.5E;
Webs: 2x4 SPF #1/#2; w2,w3,w13 2x3 SPF #3;w4,w5,w12 2x3 SPF #1/#2;
Bracing
(a) Continuous lateral restraint equally
spaced on member.
Loading
Bottom chord checked for 10.00 psf non-concurrent live load.
Purlins
In lieu of structural panels use purlins to brace all flat
TC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Wind loading based on both gable and hip roof types.
Condition:This Truss Label: D1 needs the interior bearing shifted left to 18-4-12as shown. All plates and joints shall be fully intact and undisturbed.Solution:
Restore any original camber to the truss and support as necessary.Carefully cut and remove a portion of the truss not to disrupt theremaining plates in the remaining members as shown.Cut to fit and insert 2x4 SPF#1/#2-CAN webs as shown.Cut and apply 7/16" OSB APA Span Rated 24/16 Exposure 1gussets to each face of the truss using 0.113" x2.5" 8d boxnails at 2.0 inches on center staggered throughout all members.Size of gussets are indicated by height in inches x length in inches.Gussets are centered over the joint unless otherwise noted. If shownthe circled number indicates the minimum number of nails required
on each face of each member. Apply nails per NDS requirements.Provide web bracing as shown.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
R 1030 /-/-/457 /-/301
O 2619 /-/-/1062 /-/-
K 1203 /-/-/583 /-/-
Wind reactions based on MWFRS
R Brg Width = 5.5 Min Req =1.6
O Brg Width = 5.5 Min Req =3.7
K Brg Width = 5.5 Min Req =1.9
Bearings R, O, & K Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - C 80 -996
C - D 175 -439
Chords Tens.Comp.
G - H 215 -991
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
Q - P 647 -149M - L 375 -6
Chords Tens.Comp.
L - K 838 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - R 88 -974
B - Q 562 0
C - P 137 -680
D - P 572 -20
D - O 37 -1021
O - S 232 -1618
E - S 151 -415
S - F 61 -917
Webs Tens.Comp.
S - M 401 -26
F - M 624 0
M - G 85 -915
G - L 672 -39
L - H 186 -486
H - K 0 -1012
I - K 140 -435
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.89 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.040 L 999 240
VERT(CL):0.066 L 999 180
HORZ(LL):0.018 I - -
HORZ(TL):0.029 I - -
Creep Factor: 2.0
Max TC CSI:0.716
Max BC CSI:0.626
Max Web CSI:0.983
VIEW Ver: 20.01.00.0324.19
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D1REP
Ply: 1
Qty:7
SEQN:20866 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T21
DrwNo:139.20.1607.23863
DW /BM 05/18/2020
w2
w3
w4
w5
w12 w13
18'4"12 20'6"4
6'10"12
6'10"12
13'5"8
6'6"12
18'4"12
4'11"4
20'4"1
1'11"5
25'5"8
5'1"7
32'8"11
7'3"3
38'11"
6'2"5
6'8"4
6'8"4
13'5"8
6'9"4
18'3"
4'9"8
19'5"8
1'2"8
20'5"13
1'0"5
29'7"4
9'1"7
38'11"
9'3"121'3"1'3"
1'2"11'9"1412'0"3(a)
(a)(a)
(a)
(a)
(a)
A
B
C
D E F G
H
I
J
KLMNOPQR
S
9.5
12
3X6
3X4 3X4
3X4
5X6
3X4
1.5X4
3X8
4X8
5X6
4X4
3X4
1.5X4
3X4
1212
12
8 8
14
814
22
8 8
12
14
2024"x30" Gusset 24"x30" Gusset
24"x42" Gusset
24"x16" Gusset
16"x24" Gusset
24"x16" Gusset
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;Bot chord: 2x4 SPF 1650f-1.5E;
Webs: 2x4 SPF #1/#2; w2,w3,w13 2x3 SPF #3;w4,w5,w12 2x3 SPF #1/#2;
Bracing
(a) Continuous lateral restraint equally
spaced on member.
Loading
Bottom chord checked for 10.00 psf non-concurrent live load.
Purlins
In lieu of structural panels use purlins to brace all flat
TC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&Cmember design.
Wind loading based on both gable and hip roof types.
Condition:This Truss Label: D1 needs the interior bearing shifted left to 18-4-12as shown. All plates and joints shall be fully intact and undisturbed.Solution:
Restore any original camber to the truss and support as necessary.Carefully cut and remove a portion of the truss not to disrupt theremaining plates in the remaining members as shown.Cut to fit and insert 2x4 SPF#1/#2-CAN webs as shown.Cut and apply 7/16" OSB APA Span Rated 24/16 Exposure 1gussets to each face of the truss using 0.113" x2.5" 8d boxnails at 2.0 inches on center staggered throughout all members.Size of gussets are indicated by height in inches x length in inches.Gussets are centered over the joint unless otherwise noted. If shownthe circled number indicates the minimum number of nails required
on each face of each member. Apply nails per NDS requirements.Provide web bracing as shown.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
R 1030 /-/-/457 /-/301
O 2619 /-/-/1062 /-/-
K 1203 /-/-/583 /-/-
Wind reactions based on MWFRS
R Brg Width = 5.5 Min Req =1.6
O Brg Width = 5.5 Min Req =3.7
K Brg Width = 5.5 Min Req =1.9
Bearings R, O, & K Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - C 80 -996
C - D 175 -439
Chords Tens.Comp.
G - H 215 -991
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
Q - P 647 -149M - L 375 -6
Chords Tens.Comp.
L - K 838 0
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - R 88 -974
B - Q 562 0
C - P 137 -680
D - P 572 -20
D - O 37 -1021
O - S 232 -1618
E - S 151 -415
S - F 61 -917
Webs Tens.Comp.
S - M 401 -26
F - M 624 0
M - G 85 -915
G - L 672 -39
L - H 186 -486
H - K 0 -1012
I - K 140 -435
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.89 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.040 L 999 240
VERT(CL):0.066 L 999 180
HORZ(LL):0.018 I - -
HORZ(TL):0.029 I - -
Creep Factor: 2.0
Max TC CSI:0.716
Max BC CSI:0.626
Max Web CSI:0.983
VIEW Ver: 20.01.00.0324.19
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D1REP
Ply: 1
Qty:7
SEQN:20866 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T21
DrwNo:139.20.1607.23863
DW /BM 05/18/2020
w2
w3
w4
w5
w12 w13
18'4"12 20'6"4
6'10"12
6'10"12
13'5"8
6'6"12
18'4"12
4'11"4
20'4"1
1'11"5
25'5"8
5'1"7
32'8"11
7'3"3
38'11"
6'2"5
6'8"4
6'8"4
13'5"8
6'9"4
18'3"
4'9"8
19'5"8
1'2"8
20'5"13
1'0"5
29'7"4
9'1"7
38'11"
9'3"121'3"1'3"
1'2"11'9"1412'0"3(a)
(a)(a)
(a)
(a)
(a)
A
B
C
D E F G
H
I
J
KLMNOPQR
S
9.5
12
3X6
3X4 3X4
3X4
5X6
3X4
1.5X4
3X8
4X8
5X6
4X4
3X4
1.5X4
3X4
1212
12
8 8
14
814
22
8 8
12
14
2024"x30" Gusset 24"x30" Gusset
24"x42" Gusset
24"x16" Gusset
16"x24" Gusset
24"x16" Gusset
05/19/2020
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;TC2 2x4 SPF #1/#2;
Bot chord: 2x4 SPF 1650f-1.5E;Webs: 2x4 SPF #1/#2; w2,w3,w11 2x3 SPF #3;w5 2x4 SPF 1650f-1.5E; w9 2x3 SPF #1/#2;
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Purlins
In lieu of structural panels use purlins to brace all flatTC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
Condition:This Truss Label: D2 needs the interior bearing shifted right to 28-2-4as shown. All plates and joints shall be fully intact and undisturbed.Solution:
Restore any original camber to the truss and support as necessary.Carefully cut and remove a portion of the truss not to disrupt theremaining plates in the remaining members as shown.Cut to fit and insert 2x4 SPF#1/#2-CAN web as shown.Cut and apply 7/16" OSB APA Span Rated 24/16 Exposure 1
gussets to each face of the truss using 0.113" x2.5" 8d boxnails at 2.0 inches on center staggered throughout all members.Size of gussets are indicated by height in inches x length in inches.Gussets are centered over the joint unless otherwise noted. If shownthe circled number indicates the minimum number of nails required
on each face of each member. Apply nails per NDS requirements.Provide web bracing as shown.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
P 1754 /-/-/782 /-/301
L 2224 /-/-/866 /-/-
J 769 /-/-/411 /-/-
Wind reactions based on MWFRS
P Brg Width = 5.5 Min Req =2.8
L Brg Width = 5.5 Min Req =3.1
J Brg Width = 5.5 Min Req =1.5
Bearings P, L, & J Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - C 192 -1991
C - D 307 -1681
Chords Tens.Comp.
D - E 290 -908
E - F 290 -908
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
O - N 1439 -75
Chords Tens.Comp.
N - M 1022 -24
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - P 171 -1693B - O 1357 -28
C - N 129 -483
N - D 544 -25
M - F 1184 -145
Webs Tens.Comp.
E - M 240 -653F - L 178 -2074
F - K 598 -45
K - G 207 -596
H - J 148 -484
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.89 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.068 N 999 240
VERT(CL):0.108 N 999 180
HORZ(LL):0.023 C - -
HORZ(TL):0.038 C - -
Creep Factor: 2.0
Max TC CSI:0.736
Max BC CSI:0.531
Max Web CSI:0.951
VIEW Ver: 20.01.00.0324.19
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D2REP
Ply: 1
Qty:8
SEQN:20870 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T22
DrwNo:140.20.0759.45007
DW /BM 05/18/2020
TC2
w2
w3
w5
w9 w11
28'2"4 10'8"12
6'4"15
6'4"15
13'5"8
7'0"9
19'5"8
6'
25'5"8
6'
32'2"10
6'9"2
38'11"
6'8"6
6'2"7
6'2"7
10'8"12
4'6"5
19'5"8
8'8"12
28'2"4
8'8"12
29'2"4
1'
38'11"
9'8"121'3"1'3"
1'2"11'9"1412'0"3(a)(a)(a)
(a)
(a)
(a)
A
B
C
D E F
G
H
I
JKLMNOP
9.5
12
4X4
2X4 3X4
3X4
4X4
5X6 1.5X4
6X8
5X6
4X4
4X6
2X4
4X6
9 9
106
4
12
12
11
11
18
18
18
12
12
12
12 12
10 10
24"x18" Gusset 12"x18" Gusset 28"x24" Gusset
18"x30" Gusset 36"x32" Gusset
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;TC2 2x4 SPF #1/#2;
Bot chord: 2x4 SPF 1650f-1.5E;Webs: 2x4 SPF #1/#2; w2,w3,w11 2x3 SPF #3;w5 2x4 SPF 1650f-1.5E; w9 2x3 SPF #1/#2;
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Purlins
In lieu of structural panels use purlins to brace all flatTC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
Condition:This Truss Label: D2 needs the interior bearing shifted right to 28-2-4as shown. All plates and joints shall be fully intact and undisturbed.Solution:
Restore any original camber to the truss and support as necessary.Carefully cut and remove a portion of the truss not to disrupt theremaining plates in the remaining members as shown.Cut to fit and insert 2x4 SPF#1/#2-CAN web as shown.Cut and apply 7/16" OSB APA Span Rated 24/16 Exposure 1
gussets to each face of the truss using 0.113" x2.5" 8d boxnails at 2.0 inches on center staggered throughout all members.Size of gussets are indicated by height in inches x length in inches.Gussets are centered over the joint unless otherwise noted. If shownthe circled number indicates the minimum number of nails required
on each face of each member. Apply nails per NDS requirements.Provide web bracing as shown.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
P 1754 /-/-/782 /-/301
L 2224 /-/-/866 /-/-
J 769 /-/-/411 /-/-
Wind reactions based on MWFRS
P Brg Width = 5.5 Min Req =2.8
L Brg Width = 5.5 Min Req =3.1
J Brg Width = 5.5 Min Req =1.5
Bearings P, L, & J Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
B - C 192 -1991
C - D 307 -1681
Chords Tens.Comp.
D - E 290 -908
E - F 290 -908
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
O - N 1439 -75
Chords Tens.Comp.
N - M 1022 -24
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - P 171 -1693B - O 1357 -28
C - N 129 -483
N - D 544 -25
M - F 1184 -145
Webs Tens.Comp.
E - M 240 -653F - L 178 -2074
F - K 598 -45
K - G 207 -596
H - J 148 -484
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.89 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.068 N 999 240
VERT(CL):0.108 N 999 180
HORZ(LL):0.023 C - -
HORZ(TL):0.038 C - -
Creep Factor: 2.0
Max TC CSI:0.736
Max BC CSI:0.531
Max Web CSI:0.951
VIEW Ver: 20.01.00.0324.19
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D2REP
Ply: 1
Qty:8
SEQN:20870 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T22
DrwNo:140.20.0759.45007
DW /BM 05/18/2020
TC2
w2
w3
w5
w9 w11
28'2"4 10'8"12
6'4"15
6'4"15
13'5"8
7'0"9
19'5"8
6'
25'5"8
6'
32'2"10
6'9"2
38'11"
6'8"6
6'2"7
6'2"7
10'8"12
4'6"5
19'5"8
8'8"12
28'2"4
8'8"12
29'2"4
1'
38'11"
9'8"121'3"1'3"
1'2"11'9"1412'0"3(a)(a)(a)
(a)
(a)
(a)
A
B
C
D E F
G
H
I
JKLMNOP
9.5
12
4X4
2X4 3X4
3X4
4X4
5X6 1.5X4
6X8
5X6
4X4
4X6
2X4
4X6
9 9
106
4
12
12
11
11
18
18
18
12
12
12
12 12
10 10
24"x18" Gusset 12"x18" Gusset 28"x24" Gusset
18"x30" Gusset 36"x32" Gusset
05/19/2020
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;TC2 2x4 SPF #1/#2;
Bot chord: 2x4 SPF 1650f-1.5E;Webs: 2x4 SPF #1/#2; w4 2x3 SPF Stud;w10 2x4 SPF 1650f-1.5E; w11 2x3 SPF #3;
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Purlins
In lieu of structural panels use purlins to brace all flatTC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right cantilever is exposed to wind
Wind loading based on both gable and hip roof types.
Condition:This Truss Label: D4 needs the interior bearing shifted left to 9-7-4as shown. All plates and joints shall be fully intact and undisturbed.Solution:Restore any original camber to the truss and support as necessary.
Carefully cut and remove a portion of two webs not to disrupt theremaining plates in the remaining members as shown.Cut to fit and insert 2x4 SPF#1/#2-CAN webs as shown.Cut and apply 7/16" OSB APA Span Rated 24/16 Exposure 1gussets to each face of the truss using 0.113" x2.5" 8d box
nails at 2.0 inches on center staggered throughout all members.Size of gussets are indicated by height in inches x length in inches.Gussets are centered over the joint unless otherwise noted. If shownthe circled number indicates the minimum number of nails requiredon each face of each member. Apply nails per NDS requirements.Provide web bracing as shown.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
P 615 /-/-/240 /-/301
O 2295 /-/-/1021 /72 /-
L 1854 /-/-/861 /26 /-
Wind reactions based on MWFRS
P Brg Width = 5.5 Min Req =1.5
O Brg Width = 5.5 Min Req =3.2
L Brg Width = 3.5 Min Req =2.5
Bearings P, O, & L Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
E - F 329 -947
F - G 329 -946
Chords Tens.Comp.
G - H 375 -1650
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
O - N 440 -60N - M 999 0
Chords Tens.Comp.
M - L 1277 -54
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - P 207 -500
C - O 209 -478
O - E 124 -1484
E - N 1101 -153
Webs Tens.Comp.
F - N 240 -665
G - M 476 -74
H - L 423 -2030
I - K 207 -430
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.89 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.057 M 999 240
VERT(CL):0.093 M 999 180
HORZ(LL):0.024 L - -
HORZ(TL):0.041 L - -
Creep Factor: 2.0
Max TC CSI:0.683
Max BC CSI:0.652
Max Web CSI:1.000
VIEW Ver: 20.01.00.0324.19
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D4REP
Ply: 1
Qty:6
SEQN:20886 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T23
DrwNo:140.20.0916.03350
DW /BM 05/18/2020
E
5X6
O
w4
C4X6
5
5
TC2
w3
w4 w10 w11
9'7"4 28'8"4 7"8
6'8"6
6'8"6
9'7"
2'10"10
13'5"8
3'10"8
19'5"8
6'
25'5"8
6'
32'0"4
6'6"12
38'11"
6'10"12
9'7"
9'7"
19'5"8
9'10"8
28'10"1
9'4"9
38'0"14
9'2"13
38'11"
10"2
1'3"
1'3"
1'2"11'9"1412'0"3(a)
(a)
(a)(a)(a)(a)
(a)
(a)
A
B
C
D
E F G
H
I
J
KLMNOP
9.5
12
2X4
4X6
4X6
1.5X4
6X8
5X6
4X4
3X4
1.5X4
3X4
5X6
2X3 Web
2X4 WebTrim Plate
12"x12" Gusset
24"x24" Gusset
24"x36" Gusset
24"x30" Gusset
16"x30" Gusset16"x16" Gusset
5
5
5
10
14
14
11
14
14
20
5
5
5
5
10
18
18
18
20
**WARNING**READ AND FOLLOW ALL NOTES ON THIS DRAWING!**IMPORTANT**FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERSTrusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (BuildingComponent Safety Information, by TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporarybracing per BCSI. Unless noted otherwise,top chord shall have properly attached structural sheathing and bottom chord shall have a properlyattached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7, or B10,as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer todrawings 160A-Z for standard plate positions.
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing,any failure to build thetruss in conformance with ANSI/TPI 1, or for handling, shipping, installation and bracing of trusses.A seal on this drawing or cover pagelisting this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitabilityand use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job's general notes page and these web sites: ALPINE: www.alpineitw.com; TPI: www.tpinst.org; SBCA: www.sbcindustry.com; ICC: www.iccsafe.org
2820 N. Great Southwest ParkwayGrand Prairie, TX 75050
Lumber
Top chord: 2x4 SPF 1650f-1.5E;TC2 2x4 SPF #1/#2;
Bot chord: 2x4 SPF 1650f-1.5E;Webs: 2x4 SPF #1/#2; w4 2x3 SPF Stud;w10 2x4 SPF 1650f-1.5E; w11 2x3 SPF #3;
Bracing
(a) Continuous lateral restraint equally spaced onmember.
Loading
Bottom chord checked for 10.00 psf non-concurrent
live load.
Purlins
In lieu of structural panels use purlins to brace all flatTC @ 24" oc.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right cantilever is exposed to wind
Wind loading based on both gable and hip roof types.
Condition:This Truss Label: D4 needs the interior bearing shifted left to 9-7-4as shown. All plates and joints shall be fully intact and undisturbed.Solution:Restore any original camber to the truss and support as necessary.
Carefully cut and remove a portion of two webs not to disrupt theremaining plates in the remaining members as shown.Cut to fit and insert 2x4 SPF#1/#2-CAN webs as shown.Cut and apply 7/16" OSB APA Span Rated 24/16 Exposure 1gussets to each face of the truss using 0.113" x2.5" 8d box
nails at 2.0 inches on center staggered throughout all members.Size of gussets are indicated by height in inches x length in inches.Gussets are centered over the joint unless otherwise noted. If shownthe circled number indicates the minimum number of nails requiredon each face of each member. Apply nails per NDS requirements.Provide web bracing as shown.
Maximum Reactions (lbs)
Gravity Non-Gravity
Loc R+/ R-/ Rh / Rw / U / RL
P 615 /-/-/240 /-/301
O 2295 /-/-/1021 /72 /-
L 1854 /-/-/861 /26 /-
Wind reactions based on MWFRS
P Brg Width = 5.5 Min Req =1.5
O Brg Width = 5.5 Min Req =3.2
L Brg Width = 3.5 Min Req =2.5
Bearings P, O, & L Fcperp = 425psi.
Members not listed have forces less than 375#
Maximum Top Chord Forces Per Ply (lbs)
Chords Tens.Comp.
E - F 329 -947
F - G 329 -946
Chords Tens.Comp.
G - H 375 -1650
Maximum Bot Chord Forces Per Ply(lbs)
Chords Tens.Comp.
O - N 440 -60N - M 999 0
Chords Tens.Comp.
M - L 1277 -54
Maximum Web Forces Per Ply(lbs)
Webs Tens.Comp.
B - P 207 -500
C - O 209 -478
O - E 124 -1484
E - N 1101 -153
Webs Tens.Comp.
F - N 240 -665
G - M 476 -74
H - L 423 -2030
I - K 207 -430
Loading Criteria (psf)
TCLL:35.00
TCDL:10.00
BCLL:0.00
BCDL:10.00
Des Ld:55.00
NCBCLL:10.00
Soffit:0.00
Load Duration: 1.15
Spacing: 24.0 "
Wind Criteria
Wind Std:ASCE 7-16
Speed:115 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.78 ft
TCDL: 6.0 psf
BCDL: 6.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.89 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.60
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Code / Misc Criteria
Bldg Code:IRC 2018
TPI Std:2014
Rep Fac: Yes
FT/RT:16(0)/10(0)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL):0.057 M 999 240
VERT(CL):0.093 M 999 180
HORZ(LL):0.024 L - -
HORZ(TL):0.041 L - -
Creep Factor: 2.0
Max TC CSI:0.683
Max BC CSI:0.652
Max Web CSI:1.000
VIEW Ver: 20.01.00.0324.19
Job Number:T201946-REP
Dsgnr:Shane Anders
Truss Label:D4REP
Ply: 1
Qty:6
SEQN:20886 COMN
FROM:
Cust: R9073 JRef:1WVd90730015 T23
DrwNo:140.20.0916.03350
DW /BM 05/18/2020
E
5X6
O
w4
C4X6
5
5
TC2
w3
w4 w10 w11
9'7"4 28'8"4 7"8
6'8"6
6'8"6
9'7"
2'10"10
13'5"8
3'10"8
19'5"8
6'
25'5"8
6'
32'0"4
6'6"12
38'11"
6'10"12
9'7"
9'7"
19'5"8
9'10"8
28'10"1
9'4"9
38'0"14
9'2"13
38'11"
10"2
1'3"
1'3"
1'2"11'9"1412'0"3(a)
(a)
(a)(a)(a)(a)
(a)
(a)
A
B
C
D
E F G
H
I
J
KLMNOP
9.5
12
2X4
4X6
4X6
1.5X4
6X8
5X6
4X4
3X4
1.5X4
3X4
5X6
2X3 Web
2X4 WebTrim Plate
12"x12" Gusset
24"x24" Gusset
24"x36" Gusset
24"x30" Gusset
16"x30" Gusset16"x16" Gusset
5
5
5
10
14
14
11
14
14
20
5
5
5
5
10
18
18
18
20