HomeMy WebLinkAboutLA183426 17961 Eventide Way Permit PackRESIDENTIAL BUILDING PERMIT APPLICATION
PAGE 2
OFFICE USE ONLY
BUILDING PERMIT TYPE REQUIRED INSPECTIONS
SINGLE FAMILY DWELLING BUILDING
DUPLEX AS BUILT
TOWNHOUSE UNITS BUILDING FINAL
DETACHED TOWN HOUSE UNIT DECK FOOTING
CONDO FIREPLACE
ACESSORY BUILDING FOOTING
REROOF FOUNDATION
RESIDE FRAMING
PORCH FRAMING
GARAGES
INSULATION
RES ADDN/REPAIR/RMDL
DECK
PORCH
GARAGES LATH
LOWER LEVEL FINISH LOWER LEVEL FINAL
ADDITION OTHER
FOUNDATION ONLY PORCH FOOTING
MISCELLANEOUS POURED WALL
DEMO SEPTIC TANK REMOVAL
MOVED SITE
MECHANICAL
CITY BUILDING VALUATION: $AIR TEST
FINAL
BUILDING PERMIT FEES ROUGH-IN
$PERMIT FEE PLUMBING
$PLAN CHECK FINAL
$SURCHARGE ROUGH-IN
$METRO SAC METER SIZE
$CITY WATER HOOKUP UNIT PRESSURE REDUCING VALVE
$CITY SEWER HOOKUP UNIT SEWER/WATER
$LANDSCAPE ESCROW SEWER/WATER
$TREE ESCROW FINAL
$MISC ESCROW STREET DRAINTILE
$PLUMBING BUILDING INFORMATION
$MECHANICAL TYPE OF CONSTRUCTION
$SEWER WATER ZONING
$OTHER CODE EDITION
$TOTAL FIRE SUPPRESSION SYSTEM
OCCUPANCY GROUP
APPROVED BY:
BUILDING INSPECTOR: Date:
PLUMBING/MECHANICAL
INSPECTOR: Date:
COMMENTS:
20195 Holyoke Avenue, Lakeville, MN 55044
952-985-4400 952-985-4499 fax
www.lakevillemn.gov
Sewer & Water Tie Card
Address:________________________________________
Contractor:______________________________________
Permit Number:__________________________________
Final Date:________________
Street Drain-Tile:______
Size of Water Service: 1”
Comments: AIRTEST SANITARY OVER 20’/2 FITTINGS
THIS CARD MUST BE COMPLETED AND ON-SITE AT TIME
OF SEWER & WATER INSPECTION
08/10/2020XKP
Secure door closed until deck isconstructed with a separate permit.Concept Approval ONLYSubject to Field InspectionInspectorDate2015MN BldgCode08/25/2020shutchins
See Detail 1/PF-1Minimum (2) 1-3/4" x 11-7/8" Header per detailFOR THIS WALL LINE, INSTALL INTERIOR GYPSUM WALLBOARD WITH BLOCKING AT ALL HORIZONTAL JOINTS AND WITH 4” OC FASTENING AT ALL ENDS AND EDGES. SEE FASTENING SCHEDULE ON PLAN PAGE GSN. 3WSPWSPWSPWSP33UFER Ground-Provide 20' Rebar in footing and stubup near electrical service panel.
22x30 ATTIC ACCESSBWP aboveContinuous bearingrequired for girderabove to foundation. Top plates must beremoved.3WSPWSPWSPWSPWSPFOR THIS WALL LINE, INSTALL INTERIOR GYPSUM WALLBOARD WITH BLOCKING AT ALL HORIZONTAL JOINTS AND WITH 4” OC FASTENING AT ALL ENDS AND EDGES. SEE FASTENING SCHEDULE ON PLAN PAGE GSN. 14WSPFOR INDICATED PORTION OF BWL USE DETAIL /SC-1 FOR THE TOPPLATE SPLICES. IF NO TOP PLATESARE TO BE USED, INSTALL SIMPSONCS20 STRAP AT ALL BEAM OR PLATEJOINTS WITH MINIMUM 9" OVERLAP ATEACH END OF STRAP.1 4.5WSP6GBGB676WSPWSP6WSPSee Detail 2/PF-1Minimum (2) 2x12 Header per detailPFHPFHMinimum 3" x 11-1/4" Header per detailSee Detail 3/PF-1Minimum 3" x 11-1/4" Header per detailSee Detail 4/PF-1PFHVerify loads with girdertruss specs, may requireremoval of top plates atbearing due to crushing.-Min. 15" clearance to anyobstruction from center ofW.C., 24" in front(typ).
The vapor barrier must be sealed atthe top & bottom plates & where theadjacent wall is insulated. All seamsshall be overlapped at least 6 inchesand sealed with compatible sealingtape or equivalent. (TYP)-Min. 15" clearance to anyobstruction from center ofW.C., 24" in front(typ).Temper glass if lessthan 36" off floorVerify loads with girdertruss specs, may requireremoval of top plates atbearing due to crushing.33333322222222Braced WallPanels WSP
BWL 1BWL 210'10'3'3'FOR THIS WALL LINE, INSTALL INTERIOR GYPSUM WALLBOARD WITH BLOCKING AT ALL HORIZONTAL JOINTS AND WITH 4” OC FASTENING AT ALL ENDS AND EDGES. SEE FASTENING SCHEDULE ON PLAN PAGE GSN. 3'3'SEE DETAIL 1/PF-1
BWL 4BWL 5BWL 3BWL 6BWL 710'56'2'-3"2'-3"2'-3"3'3'SEE DETAIL 2/PF-1FOR THIS WALL LINE, INSTALL INTERIOR GYPSUM WALLBOARD WITH BLOCKING AT ALL HORIZONTAL JOINTS AND WITH 4” OC FASTENING AT ALL ENDS AND EDGES. SEE FASTENING SCHEDULE ON PLAN PAGE GSN. 17'17'BWL 4.58'6'6'6'14'SEE DETAIL 3/PF-1SEE DETAIL 4/PF-16'6'7'FOR INDICATED PORTION OF BWL USE DETAIL /SC-1 FOR THE TOPPLATE SPLICES. IF NO TOP PLATESARE TO BE USED, INSTALL SIMPSONCS20 STRAP AT ALL BEAM OR PLATEJOINTS WITH MINIMUM 9" OVERLAP ATEACH END OF STRAP.1 4.5
42'28'BWL 8BWL 9BWL 10BWL 112'2'2'2'2'2'2'2'3'3'3'3'3'3'
Voigt & Associates, Inc.C-1Structural Engineering Services 4635 Nicols Road, Suite 204Eagan, MN 55122MethodCS-WSPWind speed 90Exposure C GB BWL 1 2 3 4 4.5 5 6 7 8 9 10 11Spacing - ft 10 10 10 17 17 17 56 56 28 28 42 42Level 3 3 2 2 2 2 2 2 1 1 1 1Length req'd- ft 5 5 3.5 5.6 11.2 5.6 16 16 4.7 4.7 6.3 6.3per Table R602.10.3(1)Adjustments:Exposure 1.4 1.4 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2Eave to ridge Height 1 1 1 1 1 1 1 1 1 1 1 1Wall Height 0.9 0.9 0.95 0.95 0.95 0.95 0.95 0.95 0.9 0.9 0.90.9# of BWL 1.3 1.3 1.3 1.3 1.3 1.3 1 1 1 1 1 14" Gyp WB w.block joints0.7 1 0.7 1 1 1 1 1 1 1 1 1Adjusted Length 5.7 8.2 3.9 9.0 18.0 9.0 19.8 19.8 5.1 5.1 6.86.8Community Cares17961 Eventide Way, Lakeville, MN Sheet
Passive (No Fan)
Active (With fan and monitoring
device )
Location (or future location) of Fan:
Other Please Describe Here
Not applicable, all ducts located in conditioned space
Not required per mech. code
Passive
Powered
Interlocked with exhaust device.
Describe:
Input in
BTUS:
Capacity in
Gallons:
Other, describe:
AFUE or
HSPF%
Cfm's
" round duct OR
" metal duct
Not required per mech. code
Passive
Low: Other, describe:
Low:
Location of fan(s), describe: Cfm's
" round duct OR
" metal duct
Per R401.3 Certificate. A building certificate shall be posted on or in the electrical distribution
panel.
New Construction Energy Code Compliance Certificate
Name of Residential Contractor MN License Number
City Mailing Address of the Dwelling or Dwelling Unit
Rigid, Extruded PolystyreneHeat Recover Ventilator (HRV) Capacity in cfms:
Energy Recover Ventilator (ERV) Capacity in cfms:
Combustion Air Select a Type
Location of duct or system:
Rim Joist (2nd Floor+)
Building envelope air tightness:
Below Entire Slab
Fuel Type
Solar Heat Gain Coefficient (SHGC):
Windows & Doors
Ceiling, vaulted
Bay Windows or cantilevered areas
Floors over unconditioned area
THERMAL ENVELOPE
Foam Open Cell Wall Rigid, Isocynurate Perimeter of Slab on Grade
RADON CONTROL SYSTEM
Total R-Value of all Types of InsulationType: Check All That Apply
Mineral FiberboardInsulation Location Foam, Closed Cell Describe other insulated areas
Ceiling, flat Non or Not ApplicableFiberglass, BlownFiberglass, Batts Foundation Wall
Output
in Tons:
Appliances Cooling System
Location of duct or system:
Heating or Cooling Ducts Outside Conditioned Spaces
Make-up Air Select a Type
Domestic Water
Heater
Model
Heating System
Rim Joist (1st Floor)
Average U-Factor (excludes skylights and one door ) U:
Duct system air tightness:
Rating or Size
Efficiency
Heating Gain Cooling Load
Select Type
Describe any additional or combined heating or cooling systems if installed: (e.g. two furnaces or air
source heat pump with gas back-up furnace):
Residential Load
Calculation
SEER
/EER
Capacity continuous ventilation rate in cfms:
Heating Loss
Manufacturer
Total ventilation (intermittent + continuous) rate in cfms:
Balanced Ventilation capacity in cfms:
High:
High:
MECHANICAL VENTILATION SYSTEM
Date Cert. Posted
R-value
MECHANICAL SYSTEMS
Builders Associaton of Minnesota version 101014
17961 Eventide Way, Lakeville
HVAC Load Calculations
for
Heartland Homes
Prepared By:
Jake Ryan
Silver Tree Plumbing & Heating
1335 Mendota Heights Rd
Mendota Heights, Mn 55120
651-900-7053
Thursday, July 30, 2020
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Silver Tree Plumbing & Heating 17961 Eventide Way, Lakeville
Eagan, MN 55121 Page 2
Project Report
General Project Information
Project Title:17961 Eventide Way, Lakeville
Designed By:Jake Ryan
Project Date:7/30/2020
Project Comment:Community Cares MN
Client Name:Heartland Homes
Company Name:Silver Tree Plumbing & Heating
Company Representative:Jake Ryan
Company Address:1335 Mendota Heights Rd
Company City:Mendota Heights, Mn 55120
Company Phone:651-900-7053
Company E-Mail Address:jaker@silvertreepandh.com
Design Data
Reference City:Minneapolis, Minnesota
Building Orientation:Front door faces East
Daily Temperature Range:Medium
Latitude:44 Degrees
Elevation:834 ft.
Altitude Factor:0.970
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter:-15 -15.33 n/a 30%72 33.90
Summer:88 73 50%50%72 42
Check Figures
Total Building Supply CFM:1,431 CFM Per Square ft.:0.423
Square ft. of Room Area:3,386 Square ft. Per Ton:1,063
Volume (ft³):28,183
Building Loads
Total Heating Required Including Ventilation Air:52,122 Btuh 52.122 MBH
Total Sensible Gain:31,437 Btuh 82 %
Total Latent Gain:6,766 Btuh 18 %
Total Cooling Required Including Ventilation Air:38,203 Btuh 3.18 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
F:\ ...\17961 Eventide Way, Lakeville - Heat Calc.rh9 Thursday, July 30, 2020, 12:11 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Silver Tree Plumbing & Heating 17961 Eventide Way, Lakeville
Eagan, MN 55121 Page 3
Load Preview Report
Scope
Has
AED
Net
Ton
ft.²
/Ton Area
Sen
Gain
Lat
Gain
Net
Gain
Sen
Loss
Min
Htg
CFM
Min
Clg
CFM
Sys
Htg
CFM
Sys
Clg
CFM
Sys
Act
CFM
Duct
Size
Building 3.18 1,063 3,386 31,437 6,766 38,203 52,122 625 1,431 625 1,431 1,431
System 1 Main Floor No 3.18 1,063 3,386 31,437 6,766 38,203 52,122 625 1,431 625 1,431 1,431 13x18
Ventilation 890 4,342 5,232 5,428
Supply Duct Latent 79 79
Return Duct 5 15 20 29
Humidification 6,158
Zone 1 3,386 30,541 2,331 32,872 40,506 625 1,431 625 1,431 1,431 13x18
1-Basement 1,098 5,188 0 5,188 11,569 178 243 178 243 243 2--7
2-Main Level 1,098 15,163 2,331 17,494 15,087 233 710 233 710 710 6--6
3-Upper Level 1,190 10,190 0 10,190 13,850 214 477 214 477 477 4--6
F:\ ...\17961 Eventide Way, Lakeville - Heat Calc.rh9 Thursday, July 30, 2020, 12:11 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Silver Tree Plumbing & Heating 17961 Eventide Way, Lakeville
Eagan, MN 55121 Page 4
Duct Size Preview
Room or
Duct Name Source Minimum
Velocity
Maximum
Velocity
Rough.
Factor
Design
L/100
SP
Loss
Duct
Velocity
Duct
Length Htg
Flow
Clg
Flow
Act.
Flow
Duct
Size
System 1
Supply Runouts
Zone 1
1-Basement Built-In 450 750 0.01 0.1 454.7 178 243 243 2--7
2-Main Level Built-In 450 750 0.01 0.1 603 233 710 710 6--6
3-Upper Level Built-In 450 750 0.01 0.1 607.9 214 477 477 4--6
Other Ducts in System 1
Supply Main Trunk Built-In 650 900 0.003 0.1 880.5 625 1,431 1,431 13x18
SummarySummarySummarySummarySummarySummarySummarySummary
System 1
Heating Flow:625
Cooling Flow:1431
F:\ ...\17961 Eventide Way, Lakeville - Heat Calc.rh9 Thursday, July 30, 2020, 12:11 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Silver Tree Plumbing & Heating 17961 Eventide Way, Lakeville
Eagan, MN 55121 Page 5
Total Building Summary Loads
Component
Description
Area
Quan
Sen
Loss
Lat
Gain
Sen
Gain
Total
Gain
LOWEE BUILDER GRADE: Glazing-LOWEE BUILDER
GRADE, ground reflectance = 0.23, indoor insect
screen with 100% coverage, U-value 0.32, SHGC
0.32
475.1 13,237 0 14,368 14,368
11J: Door-Metal - Fiberglass Core, U-value 0.6 37.8 1,972 0 612 612
12F-0sw: Wall-Frame, R-21 insulation in 2 x 6 stud
cavity, no board insulation, siding finish, wood studs,
U-value 0.065
2681.1 15,162 0 2,841 2,841
15B0-10sf-4: Wall-Basement, , R-10 board insulation to
floor, no interior finish, 4' floor depth, U-value 0.054
80 376 0 0 0
15B0-10sf-8: Wall-Basement, , R-10 board insulation to
floor, no interior finish, 8' floor depth, U-value 0.05
640 2,784 0 0 0
RJ R-20 RIM JOIST: Wall-Frame, Custom, RJ R-20 RIM
JOIST R-20 SPRAY FOAM, U-value 0.05
215.9 940 0 220 220
RJ R-20: Wall-Frame, Custom, RJ R-20 RIM JOIST R20
SPRAY FOAM, U-value 0.05
193.3 842 0 198 198
R49 Attic: Roof/Ceiling-Under Attic with Insulation on
Attic Floor (also use for Knee Walls and Partition
Ceilings), Custom, R49 Attic, U-value 0.02
1329.9 2,314 0 1,833 1,833
21A-32: Floor-Basement, Concrete slab, any thickness, 2
or more feet below grade, no insulation below floor,
any floor cover, shortest side of floor slab is 32' wide,
U-value 0.02
1097.9 1,910 0 0 0
20P-30: Floor-Over open crawl space or garage, Passive,
R-30 blanket insulation, any cover, U-value 0.035
224 682 0 86 86
Subtotals for structure:40,219 0 20,158 20,158
People:6 1,200 1,380 2,580
Equipment:1,131 4,262 5,393
Lighting:650 2,217 2,217
Ductwork:317 94 74 167
Infiltration: Winter CFM: 0, Summer CFM: 0 0 0 0 0
Ventilation: Winter CFM: 158, Summer CFM: 158 5,428 4,342 890 5,232
Humidification (Winter) 16.79 gal/day :6,158 0 0 0
AED Excursion:0 0 2,456 2,456
Total Building Load Totals:52,122 6,766 31,437 38,203
Check Figures
Total Building Supply CFM:1,431 CFM Per Square ft.:0.423
Square ft. of Room Area:3,386 Square ft. Per Ton:1,063
Volume (ft³):28,183
Building Loads
Total Heating Required Including Ventilation Air:52,122 Btuh 52.122 MBH
Total Sensible Gain:31,437 Btuh 82 %
Total Latent Gain:6,766 Btuh 18 %
Total Cooling Required Including Ventilation Air:38,203 Btuh 3.18 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
F:\ ...\17961 Eventide Way, Lakeville - Heat Calc.rh9 Thursday, July 30, 2020, 12:11 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Silver Tree Plumbing & Heating 17961 Eventide Way, Lakeville
Eagan, MN 55121 Page 6
Building Rotation Report
All rotation degree values in this report are clockwise with respect to the project's original orientation.
Building orientation as entered (zero degrees rotation): Front door faces East
Individual Rooms
Rm.
No.
Room
Name
0°
Rot.
CFM
45°
Rot.
CFM
90°
Rot.
CFM
135°
Rot.
CFM
180°
Rot.
CFM
225°
Rot.
CFM
270°
Rot.
CFM
315°
Rot.
CFM
High
Duct
Size
System 1:
Zone 1:
1 Basement *243 183 113 179 223 207 161 223 2--7
2 Main Level *710 649 566 644 667 662 605 703 6--6
3 Upper Level *477 409 319 395 430 405 342 442 4--6
* Indicates highest CFM of all rotations.
Whole Building
Rotation
Degrees
Front door
Faces
Supply
CFM
Sensible
Gain
Latent
Gain
Net
Tons
0°East *1,431 *31,437 *6,766 *3.18
45°Southeast 1,241 27,385 6,766 2.85
90°South 999 22,217 6,766 2.42
135°Southwest 1,218 26,884 6,766 2.80
180°West 1,321 29,087 6,766 2.99
225°Northwest 1,274 28,092 6,766 2.90
270°North 1,108 24,552 6,766 2.61
315°Northeast 1,367 30,078 6,766 3.07
* Indicates highest value of all rotations.
2.2
2.4
2.6
2.8
3.0
East Southeast South Southwest West Northwest North NortheastCooling TonsDirection Front door Faces
Building Rotation Tonnage
Building Net Tonnage
F:\ ...\17961 Eventide Way, Lakeville - Heat Calc.rh9 Thursday, July 30, 2020, 12:11 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Silver Tree Plumbing & Heating 17961 Eventide Way, Lakeville
Eagan, MN 55121 Page 7
Building Rotation Report (cont'd)
26,000
27,000
28,000
29,000
30,000
31,000
32,000
33,000
34,000
35,000
36,000
37,000
38,000
39,000
40,000
41,000
42,000
43,000
8 am 9 am 10 am 11 am 12 pm 1 pm 2 pm 3 pm 4 pm 5 pm 6 pm 7 pmBuilding Net Gain, BtuhTime of Day
Building Rotation Hourly Net Gain
Front door faces East
Front door faces Southeast
Front door faces South
Front door faces Southwest
Front door faces West
Front door faces Northwest
Front door faces North
Front door faces Northeast
F:\ ...\17961 Eventide Way, Lakeville - Heat Calc.rh9 Thursday, July 30, 2020, 12:11 PM