PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-01
COVER SHEET
VICINITY VIEW
PROJECT
LOCATION
DESIGN CRITERIA
WIND SPEED: 115 MPH
EXPOSURE CATEGORY: B
SNOW LOAD: 5 PSF
OCCUPANCY: II
N.T.S.
INDEX/INDICATORS
PV-01 COVER SHEET
PV-02 SITE PLAN
PV-03 ROOF PLAN
PV-04 SINGLE LINE DIAGRAM
PV-05 MOUNTING DETAIL
PV-06 LABELS AND PLACARD
PV-07 INTERCONNECTIONPHOTOS
PV-08 DATASHEET
FL-01 BOM
FL-02 STRING PLAN
FL-03 ASBUILT
FL-04 OPTIMIZER MAP
FL-05 JOB CHECK SHEET
ABBREVIATIONS
(E)EXISTING
(N)NEWGNDGROUNDPNLPANEL BOARD OR PANEL
J-BOX JUNCTION BOXMONMONITORING
MSP MAIN SERVICE PANELMONMONITORING
PVC POLYVINYL CHLORIDEEMT ELECTRIC METAL TUBING
FMC FLEXIBLE METAL CONDUIT
USE UNDERGROUND SERVICE ENTRANCENEMANATIONAL ELECTRIC MANUFACTURES
ASSOCIATIONWWATTS
KW 1,000 WATTSMMETER
GENERAL NOTES:
1.1.1 PROJECT NOTES:1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE
LISTING AND INSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES
APPLICABLE CODES.1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED
AND PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION.1.1.4 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE IS
INTEGRATED WITH THE MICROINVERTER IN ACCORDANCE WITH NEC690.5(A).1.1.5 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE
INVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIEDAND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC
690.4 & NEC 690.60:PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C
FIRE.INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519.
COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY.
1.1.6 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDEDTEMP COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE
CALCULATED ACCORDING TO NEC 690.7.1.1.7 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS,
AND SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN APHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR
THE APPLICATION PER 690.4 (D). SHALL BE INSTALLED ACCORDING TOANY INSTRUCTIONS FROM LISTING OR LABELING [NEC 110.3].
1.1.8 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING
CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALLPLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE NEC
AND AHJ.
1.2.1 SCOPE OF WORK:1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND
SPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT.PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTINGONSITE REQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THEEXTERIOR ROOF-MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMSDETAILED IN THIS DOCUMENT.
AERIAL VIEW
SYSTEM INFORMATION
SYSTEM SIZE (kW):8.03
NO. OF MODULES:22
SITE INFORMATION
PROJECT NAME:MIKE JORDAN
PROJECT ADDRESS:20998 JUNCO TRAIL,LAKEVILLE, MN 55044
INVERTERS:1 (N)SOLAREDGE SE7600H-US (240V)
(N)SOLARIA POWERXT-365R-PD
CODES
2017 NATIONAL ELECTRIC CODE (NEC).2018 INTERNATIONAL BUILDING CODE (IBC) 2003 EDITION.2018 INTERNATIONAL RESIDENTIAL CODE (IRC) 2000 EDITION.2018 INTERNATIONAL MECHANICAL CODE (IMC).
2018 INTERNATIONAL PLUMBING CODE (IPC).2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC).
PARCEL MAP
DRIVEWAYYYYY
121'-1"
133'-6"
183'-6"
33'-4"
123'-3"123'-3"
53'-8"
31'-1"56'-2"48'-7"77'-4"
73'-2"----JANCO TRAIL----70'-8"
----210TH ST W----
10'10'10'10'10'10'5'5'
ARRAY AZIMUTH224 & 134DEGREES
W
NN
MAIN SERVICE PANEL (E / INSIDE)
CONDUIT RUN (ON ROOF)
JUNCTION BOX (ON ROOF)
UTILITY METER (E)
PV MODULE(N)
PHOTOVOLTAIC SYSTEM UTILITY
DISCONNECT SWITCH (N)
FIRE SETBACKS (3' MIN.)
INVERTER (N/ OUTSIDE)
RESIDENCE
OPTIMIZER(N)
ROOF ACCESS POINT
PV PRODUCTION METER
1
2
3
4
5
6
7
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-02
SITE PLAN
1"=30'
0
Scale:(For 11x17 Print)1" = 30
15 30'60'
MODULE ALLOCATION
ROOF PLANE A B C D E
AZIMUTH 224 134
TILT 30 30
# OF MODULES 16 6
8
9
PROPERTY LINE
5'
FIELD VERIFY ALL MEASUREMENTS.3FT MINIMUM FIREMAN ACCESS.
24/7 UNESCORTED KEYLESS ACCESS
IS TO BE PROVIDED FOR ALL UTILITY
EQUIPMENT
NOTE:
SYSTEM AC OUTPUT:7.6 kW
SYSTEM DC INPUT:8.03 kW
10
7
510
9
3
1
11
12
ARRAY AZIMUTH
224 & 134 DEGREES
W
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-03
ROOF PLAN
1"= 10'
0
Scale:
(For 11x17 Print)
1" = 10'
5'10'15'
LOCATION OF
ATTACHMENT POINTS
FIRE SETBACKS
(3' MIN)2X4 TRUSSES
@24" O.C.
ARRAY-1
ARRAY-2
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-04
SINGLE LINE DIAGRAM
N.T.S.
CALCULATIONS
MAXIMUM DC CURRENT (A)OPTIMIZER X 1.25
18.75
OPERATING DC CURRENT (A)MODULE IMP
9.16
AC OUTPUT (A)(INVERTER)
INVERTER IAC X 1.25
40.0
TOTAL AC OUTPUT (A)40.0
MAXIMUM DC VOLTAGE (V)TEMP. COEFF.
561.2
DC OPERATING VOLTAGE (V)(MOD./STRING)X MOD. VMP
438.9
MAIN SERVICE PANEL INFO
VOLTAGE 240 V
PHASES 1
BOX/BUS RATING 200 A
MAIN BREAKER RATING 150 A
SYSTEM INFORMATION
# OF MODULES 22
# OF STRINGS 2
# OF MODULES PER STRING 11 11
TOTAL POWER (kW)8.03
INTERCONNECTION 120% RULE (NEC705.12(D)(2))
SOLAR BREAKER +MAIN BREAKER 190
MSP RATING X 120%240
PV MODULE SPECIFICATIONS
MAKE (N)SOLARIAPOWERXT-365R-PD
NOMINAL OUTPUT POWER (W)365
EQUIPMENT
KEY TYPE DESCRIPTION
1 PV MODULE (N)SOLARIA POWERXT-365R-PD
2 INVERTER (N)SOLAREDGE SE7600H-US (240V)
3 DC DISCONNECT INVERTER INTEGRATED
4 UTILITY DISCONNECT PV SYSTEM UTILITY DISCONNECT SW(VISIBLE OPEN, NO FUSES) SQUARE D 60A, 2P,240VAC NEMA 3R
5 MAIN SERVICE PANEL (E)MAIN SERVICE PANEL 200A RATED WITH 150AMAIN BREAKER
6 OPTIMIZERS SOLAREDGE POWER OPTIMIZERS P400
7 PV PRODUCTIONMETER(N)PV METER 1-PHASE, 3-WIRED
DESCRIPTION CONDUCTORSIZE
APPROXIMATE AREAOF CONDUCTOR (NECCHAPTER-9 TABLE-5)
# OF
CONDUCTORSPER CONDUIT
CONDUITSIZE
NOMINAL INTERNAL AREAOF CONDUIT IN SQ.INCH(NEC CHAPTER-9 TABLE-4)
CONDUIT/WIREFILL PERCENT
FILL FACTOR(NEC 2014 TABLE310.15(B)(3)(a))
AMBIENT TEMP.
IN DEGREECELCIUS
TEMP.ADDER(NEC 2014 Table310.15(B)(3)(c))
TOTALTEMP INDEGREECELCIUS
TEMP CORR. FACTOR(NEC-2014TABLE-310.15(B)(2)(a))
CONDUCTORRATING IN AMPERE(NEC-2014TABLE-310.15(B)(16))
DERATEDCURRENTRATING INAMPERE
OCPD(NEC-2014ARTICLE-690.8 )
JUNCTION BOX TO INVERTER 10 AWG 0.0211 4 3/4"EMT 0.533 15.83%0.8 32 22 54 0.76 40 24.32 20A
INVERTER TO POINT OF
INTERCONNECTION
8 AWG 0.0366 3 3/4"EMT 0.533 20.60%1 32 0 32 0.96 55 52.80 40A
INVERTER SPECIFICATION
MAKE SOLAREDGE SE7600H-US (HD-WAVE)
AC CAPACITY 7.6
OUTPUT POWER 7.6
PHASE 1
VOLTS 240 V
OUTPUT CURRENT 32 A
INTERCONNECTION TYPE PRIMARY INTERCONNECTION
GGGG GGGG GGGG
GGGG GGGG GGGG
IRONRIDGE FLASHFOOT 2
(E) COMPOSITE SHINGLE
(E) RAFTERS
SOLAR MODULE
IRONRIDGE XR-100 RAIL
SIDE VIEW
FLASHING
3 1/2" x 5/16 WITH 2.5 MINLAG SCREW EMBEDMENT
TOP VIEW FRONT VIEW
PV MODULE FRAME
IRONRIDGE RAIL
IRONRIDGE CAMO
END CLAMP
PV MODULE FRAME
IRONRIDGE RAILIRONRIDGE CAMO
END CLAMP
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-05
MOUNTING DETAILS
&BOM
N.T.S.
ATTACHMENT TYPE: IRONRIDGE FLASHFOOT 2 WITH IRONRIDGE XR-100 RAILS
MODULE WEIGHT: 48 LBS
MODULE DIMENSIONS: 5.31' X 3.66'
MODULE WEIGHT/ SQ. FOOT: 2.36 LBS
TOTAL NO. OF MODULES: 22
TOTAL MODULE WEIGHT: 1056 LBS
ATTACHMENT DETAILS(N.T.S.)1
1
4
(E) 200A MAIN PANEL (N) INVERTER
(N) PHOTOVOLTAIC SYSTEM
UTILITY DISCONNECT SWITCH
TOARRAY
6
DUAL POWER SUPPLY
PHOTOVOLTAIC AC DISCONNECT
OPERATING CURRENT 32 AMPSOPERATING VOLTAGE 240 VOLTS
LABEL-1:
LABEL-2:
WARNING-ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDE
MAY BE ENERGIZED IN THE OPEN POSITION
LABEL-5:
LABELS TO BE BAKE LITE RED WITH WHITE LETTER ANDFASTENED BY BEING BOLTED OR RIVETED IN PLACE
WARNING: PHOTOVOLTAICPOWER SOURCE
LABEL-6:
LABEL 6 IS REFLECTIVE WEATHER RESISTENT STICKER TO BE PLACED ON
ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES,
AND CABLE ASSEMBLIES EVERY 10', WITHIN 1' OF TURNS OR BENDS, AND1' ABOVE AND BELOW ALL PENETRATIONS ON DC CONDUIT.
REQUIRED SIGNAGE:
2017 NEC CODES, ARTICLE 690
PHOTOVOLTAIC DC DISCONNECT
LABEL-3: INVERTER-1
OPERATING CURRENT
OPERATING VOLTAGEMAX SYSTEM VOLTAGE
SHORT CIRCUIT CURRENT
PHOTOVOLTAIC SYSTEM
AC DISCONNECT
20 AMPS
400 VOLTS480 VOLTS
20 AMPS
WARNING: INVERTER OUTPUT CONNECTION;DO NOT RELOCATE THIS OVERCURRENT DEVICE
LABEL-7:
LABEL-8:
PHOTOVOLTAIC SYSTEM
DEDICATED KWH METER
LABEL-9:
PHOTOVOLTAIC POWER SOURCE BREAKER
ARE BACKFEEDING DO NOT RELOCATE
LABEL- 10:
SOLAR PV SYSTEM
EQUIPPED WITHRAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"POSITION TO SHUT DOWN PV
SYSTEM AND REDUCE SHOCKHAZARD IN THE ARRAY
4
2
1
7
9
LABEL-4:
WARNING-ELECTRIC SHOCK HAZARD
IF A GROUND FAULT IS INDICATED
THEN THE NORMALLY GROUNDED CONDUCTORS
MAY BE ENERGIZED AND UNGROUNDED
3 5 10
DETAIL 1:
LOCATION OF MAIN SERVICE PANEL MOUNTED ON INTERIOR SOUTH EAST WALL OF THE
HOUSE AND UTILITY METER, UTILITY DISCONNECT, PV PRODUCTION METER AND INVERTER
ON EXTERIOR SOUTH EAST WALL OF THE HOUSE.
(E) UTILITY METER
(N) PV PRODUCTION METER
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYDRWCHK
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-6.1
LABELS
N.T.S.
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYDRWCHK
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-6.2
PLACARD
N.T.S.
PV ARRAY ON ROOF
N
ES
W
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
20998 JUNCO TRL., LAKEVILLE , MN 55044
UTILITY METER(EXTERIOR)MAIN SERVICE PANEL(INTERIOR)UTILITY METER(EXTERIOR)UTILITY METER(EXTERIOR)AC DISCONNECT BOX(EXTERIOR)
INVERTER(EXTERIOR)PV PROUCTION METER(EXTERIOR)INVERTER(EXTERIOR)
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYDRWCHK
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-6.3
PLACARD
N.T.S.
PV ARRAY ON ROOF
N
ES
W
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
20998 JUNCO TRL., LAKEVILLE , MN 55044
UTILITY METER(EXTERIOR)MAIN SERVICE PANEL(INTERIOR)UTILITY METER(EXTERIOR)UTILITY METER(EXTERIOR)AC DISCONNECT BOX(EXTERIOR)
INVERTER(EXTERIOR)PV PROUCTION METER(EXTERIOR)INVERTER(EXTERIOR)
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-07
INTERCONNECTIONPHOTO
N.T.S.
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
FL-01
BOM
N.T.S.
BILL OF MATERIAL
EQUIPMENT MAKE QUANTITY
MODULE (N)SOLARIA POWERXT-365R-PD 22
INVERTER (N)SOLAREDGE SE7600H-US (240V)1
PV BREAKERS (N)40A/2P 1
END CLAMPS MODULE END CLAMP STANDARD 12
MID CLAMPS MODULE MIDDLE CLAMP SET STANDARD(INTEGRATED GROUNDING)38
MOUNTING POINTS IRONRIDGE FLASH FOOT 2 44
MOUNTING RAILS IRONRIDGE XR100 16
UTILITY DISCONNECT PV SYSTEM UTILITY DISCONNECT SW(VISIBLE OPEN, NO FUSES) SQUARE D 60A, 2P,240VAC NEMA 3R 1
OPTIMIZERS SOLAREDGE POWER OPTIMIZERS P400 22
PV PRODUCTION
METER(N)PV METER 1-PHASE, 3-WIRED 1
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
FL-02
STRING PLAN
N.T.S.
STRING-1
STRING-2
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
FL-03
ASBUILT
N.T.S.
DRAW IN FINAL LOCATION OF EQUIPMENT
1.PANELS2.BRANCHS3.INVERTER(S)4.MAIN PANEL5.SUBPANEL (IF PRESENT)6.DISCONNECT(S) (IF PRESENT)7.ROOF ELECTRICAL PENETRATION8.CONDUIT ROUTES
9.COMMUNICATION WIRE RUNS
10.MONITORING EQUIPMENT
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
FL-04
OPTIMIZERMAP
N.T.S.
Inverter ZigBee Sticker
Model
Serial #
#of Modules
per Branch
MAPPING INSTRUCTIONS:
1.REMOVE THE 'SQUARE' OPTIMIZER OR ENPHASE STICKER ANDPLACE NEATLY ON THE APPROPRIATE NUMBERED SPACE.2.WRITE THE CORRESPONDING NUMBER ON THE APPROPRIATEPANEL WITHIN THE ARRAY.
3.ATTACH THE SQUARE INVERTER STICKER (AND ZIGBEE
STICKER IF REQ'D) IN SPACE PROVIDED.
Branch Information
String 1 Panel 1 - 11
String 2 Panel 12 - 22
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18 19 20 21 22
MODULE ALLOCATION
ROOF PLANE A B C D E
AZIMUTH 224 134
TILT 30 30
# OF MODULES 16 6
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
FL-05
JOB CHECKSHEET
N.T.S.
CREW LEAD: __________________________________
DATE: ________________________________________
Y N PHOTO CHECKLIST DONE (SEE RIGHT)?
Y N PERMIT LEFT FOR INSPECTION?WHERE? _______________
Y N JOBSITE CLEANED UP?
Y N CONDUIT PAINTED?
Y N STICKERS & PLACARDS INSTALLED?
Y N DAMAGE REPAIRS NEEDED?
Y N JOB PHOTOS TAKEN
Y N OPTIMIZER/MICROINVERTER MAP FILLED OUT?
Y N CLIENT WALK THROUGH COMPLETED?
Y N YARD SIGN INSTALLED?
Y N WAS SYSTEM LEFT ON?
INVERTER INFORMATION
STRING VOLTAGE
1
2
3
4
BRAND:
MODEL:
LOCATION:
SERIAL:
1
2
3
4
5
6
BRAND:
MODEL:
LOCATION:
SERIAL:
1
2
3
4
5
6
BRAND:
MODEL:
LOCATION:
SERIAL:
1
2
3
4
5
6
BRAND:
MODEL:
LOCATION:
SERIAL:
1
2
3
4
5
6
PHOTO CHECKLIST
INVERTER
WIRING
SERIAL NUMBERS
STRING DIAGRAM
MOUNTING
CONDUIT CONNECTIONS
LABELING
MAIN PANEL
BREAKER TIE IN LOCATION
WIRING
CONDUIT CONNECTION
LABELING
GEC
DISCONNECT
WIRING
MOUNTING (CLEARANCES)
CONDUIT CONNECTION
LABELING
CONDUIT (SHOW FULL RUN)
ATTIC CONDUIT
EXTERIOR CONDUIT
JUNCTION BOXES
WIRING
WEEP HOLE
CONDUIT CONNECTION
LABELING
FLASHING
UP CLOSE
STEPPED BACK
CONDUIT PENETRATION
BEFORE SEALANT
AFTER SEALANT
COMBINER BOXES
WIRING
WEEP HOLE
CONDUIT CONNECTION
LABELING
ROOFING MATERIAL
UNDER ARRAY BEFORE
MODULES
AROUND ARRAY
AFTER MODULES
RAIL MOUNTING
HARDWARE
STEP BACK VIEW
ARRAY WIRING
HOME RUNS
JUMPERS
ATTIC PENETRATIONS
GROUNDING WIRE
OPTIMIZERS
FINISHED ARRAY
INVERTER
OTHER ITEMS NEEDED?
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-08.1
MODULEDATASHEET
N.T.S.
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-08.2
N.T.S.
INVERTERDATASHEET
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-08.3
N.T.S.
INVERTERDATASHEET
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-08.4
RACKINGDATASHEET
N.T.S.
PAGE SIZEJOB NUMBER B
SITE NUMBER
DRAWING NUMBER
SCALE
DATEDESCRIPTIONREVREVISION HISTORYREVDRWDRWCHKDRW
PROJECT ADDRESS
20998 JUNCO TRAIL,LAKEVILLE, MN 55044
0 DRAFT REVIEW
DRAWING TITLE
PROJECT OWNER
CONTRACTOR:
12/21/20SK
TEL. NO. 1-800-467-4562
AHJ
APN.
MIKE JORDAN - 15485
UTILITY COMPANY
226481104080
EMPIRE SOLARGROUP
WWW.EMPIRESOLARGROUP.COM
1 COMMENTS INCORPORATED 01/04/20DG
LAKEVILLE
2 COMMENTS INCORPORATED 01/06/21AP
PV-08.5
ATTACHMENTDATASHEET
N.T.S.