HomeMy WebLinkAboutLA185059 -18886 Iden Ave 2 Wyssling Consulting 76 North Meadowbrook Drive Alpine, UT 84004 Scott E. Wyssling, PE, PP, CME office (201) 874-3483 swyssling@wysslingconsulting.com October 13, 2020 Illumine Industries 39111 Paseo Padre Parkway Suite 313 Fremont, CA 94538 Re: Engineering Services Adair Residence 18886 Iden Avenue, Lakeville MN 13.135 kW System To Whom it May Concern: Pursuant to your request, we have reviewed the following information regarding solar panel installation on the roof of the above referenced home: 1. Site Visit/Verification Form prepared by Illumine Industries Solar Engineers representative identifying specific site information including size and spacing of rafters for the existing roof structure. 2. Design drawings of the proposed system including a site plan, roof plan and connection details for the solar panels. This information was prepared by Illumine Industries Solar Engineers and will be utilized for approval and construction of the proposed system. 3. Photographs of the interior and exterior of the roof system identifying existing structural members and their conditions. Based on the above information we have evaluated the structural capacity of the proposed roof system to support the additional loads imposed by the solar panels and have the following comments related to our review and evaluation: Description of Structure: The existing residence is typical wood framing construction with the roof system consisting of truss system with all chords constructed of 2 x 4 dimensional lumber at 24” on center. The attic space is unfinished and photos indicate that there was free access to visually inspect the size and condition of the roof rafters. All wood material utilized for the roof system is assumed to be Doug-Fir #2 or better with standard construction components. The existing roofing material consists of an asphalt shingles. Photos of the dwelling also indicate that there is a permanent foundation. A. Loading Criteria Used  115 MPH wind loading based on ASCE 7-16 Exposure Category “B” at a slope of 29 degrees  7 PSF = Dead Load roofing/framing Live Load = 20 PSF Snow Load = 50 PSF  3 PSF = Dead Load solar Ballast System/hardware Total Dead Load =10 PSF The above values are within acceptable limits of recognized industry standards for similar structures in accordance with the Minnesota Uniform Construction Code (2018 MRC). Analysis performed of the existing roof structure utilizing the above loading criteria indicates that the existing rafters will support the additional panel loading without damage, if installed correctly. Page 2 of 2 B. Solar Panel Anchorage 1. The solar panels shall be mounted in accordance with the most recent “IronRidge Installation Manual”, which can be found on the IronRidge website (http://IronRidge.com/). If during solar panel installation, the roof framing members appear unstable or deflect non-uniformly, our office should be notified before proceeding with the installation. 2. Maximum allowable pullout per lag screw is 235 lbs/inch of penetration as identified in the National Design Standards (NDS) of timber construction specifications for Doug-Fir (North Lumber) assumed. Based on our evaluation, the pullout value, utilizing a penetration depth of 2 ½”, is less than what is allowable per connection and therefore is adequate. Based on the variable factors for the existing roof framing and installation tolerances, using a thread depth of 2 ½” with a minimum size of 5/16” lag screw per attachment point for panel anchor mounts should be adequate with a sufficient factor of safety. 3. Considering the roof slopes, the size, spacing, condition of roof, the panel supports shall be placed no greater than 48” o/c. 4. Panel supports connections shall be staggered to distribute load to adjacent rafters. Based on the above evaluation, it is the opinion of this office that with appropriate hardware being utilized the roof system will adequately support the additional loading imposed by the solar panels. This evaluation is in conformance with the Minnesota Uniform Construction Code, current industry and standards, and based on information supplied to us at the time of this report. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Very truly yours, Scott E. Wyssling Minnesota License No. 57927 UM PMMSP AC CB VICINITY MAP ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: SITE PLAN LAYOUT CONDUIT RUN 1'-6" FIRE SETBACK KAT AND ERIC ADAIR - 13.135kW DC, 12.913kW AC COVER PAGE T-1 PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION 1.MODULES ARE LISTED UNDER UL 1703 AND CONFORM TO THE STANDARDS. 2.INVERTERS ARE LISTED UNDER UL 1741 AND CONFORM TO THE STANDARDS. 3.DRAWINGS ARE DIAGRAMMATIC, INDICATING GENERAL ARRANGEMENT OF THE PV SYSTEM AND THE ACTUAL SITE CONDITION MIGHT VARY. 4.WORKING CLEARANCES AROUND THE NEW PV ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH NEC 110.26. 5.ALL GROUND WIRING CONNECTED TO THE MAIN SERVICE GROUNDING IN MAIN SERVICE PANEL/ SERVICE EQUIPMENT. 6.ALL CONDUCTORS SHALL BE 600V, 75°C STANDARD COPPER UNLESS OTHERWISE NOTED. 7.WHEN REQUIRED, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 8.THE SYSTEM WILL NOT BE INTERCONNECTED BY THE CONTRACTOR UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND/OR THE UTILITY. 9.ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREES, WIRES OR SIGNS. 10.PV ARRAY COMBINER/JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING GENERAL NOTES SCALE:1"=30'-0" (E) MAIN SERVICE METER BI-DIRECTIONAL-1PHASE, 3WIRE 120/240V (EXTERIOR) (N) 100AMP UTILITY AC DISCONNECT(EXTERIOR)(VISIBLE BLADE, LOCKABLE, READILY ACCESSIBLE, LABELED, LOCATED WITHIN 10' OF MAIN SERVICE METER, NO CLEARANCE ISSUES) (N) UTILITY OWNED PV PRODUCTION METER(EXTERIOR)120V/240V, 1 PHASE, 3 WIRE, BYPASS LEVER, 200A (LOCATED NEXT TO UTILITY AC DISCONNECT, 24/7 READILY ACCESSIBLE, LABELED,LOCATED WITHIN 10' OF MAIN SERVICE METER, NO CLEARANCE ISSUES) (E) 150A MAIN SERVICE PANEL (EXTERIOR) SHEET CATALOG INDEX NO.DESCRIPTION T-1 COVER PAGE M-1 MOUNTING DETAIL M-2 STRUCTURAL DETAIL M-3 INSTALLATION CALCULATION E-1 SINGLE LINE DIAGRAM S-1 OPTIMIZER MAP AND STRING CONFIGURATION PL-1 LABELING & WARNING SIGNS PL-2 WARNING PLACARDS SS SPEC SHEET(S) ·ELECTRIC CODE: NEC 2020 ·FIRE CODE: IFC 2018 ·BUILDING CODE: MBC 2018 ·RESIDENTIAL CODE: MRC 2018 APPLICABLE CODES PROPERTY LINE PHOTOVOLTAIC ARRAY ON THE ROOF DRIVE WAY IDEN AVEAPPROX 676'HUXLEY AVEPROPERTYLINENOTE: NO GATE OR FENCE TOTAL AREA OF ROOF (SQ.FT)2462 TOTAL ARRAY AREA (SQ.FT)784.5156 TOTAL AREA OF ARRAY COVERED IN THE ROOF (%)31.86 3' FIRE SETBACK (N) ENPHASE COMBINER + CABINET 120/240 NEMA 3R INSTALL (4) 20A BREAKERS (ONLY FOR SOLAR, NO LOADS TO BE ADDED) (UL 1741 CERTIFIED) 1'(MAXIMUM 1' SPACING BETWEEN COMPONENTS) GENERAL SYSTEM INFORMATION: SYSTEM SIZE: 13135W DC, 12913W AC MODULES: (37)LG SOLAR LG355N1C-V5 INVERTER: (37)ENPHASE IQ7A-72-2-US , BRANCH DETAILS: 1X10, 1X9, 1X9 AND 1X9 ENPHASE BRANCHES SCOPE OF WORK 147'-6" 76' 153' 7'-10" 5' 39'-2" 49'-6" AERIAL VIEW ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION MOUNTING DETAIL M-1 NOTE:PENETRATIONS ARE STAGGERED 1.STRUCTURAL ROOF MEMBER LOCATIONS ARE ESTIMATED AND SHOULD BE LOCATED AND VERIFIED BY THE CONTRACTOR WHEN LAG BOLT PENETRATION OR MECHANICAL ATTACHMENT TO THE STRUCTURE IS REQUIRED. 2.ROOFTOP PENETRATIONS FOR SOLAR RACKING WILL BE COMPLETED AND SEALED WITH APPROVED SEALANT PER CODE BY A LICENSED CONTRACTOR. 3.LAGS MUST HAVE A MINIMUM 2.5" THREAD EMBEDMENT INTO THE STRUCTURAL MEMBER. 4.ALL PV RACKING ATTACHMENTS SHALL BE STAGGERED BY ROW BETWEEN THE ROOF FRAMING MEMBERS AS NECESSARY. 5.ROOF MOUNTED STANDARD RAIL REQUIRES ONE THERMAL EXPANSION GAP FOR EVERY RUN OF RAIL GREATER THAN 40'. 6.ALL CONDUCTORS AND CONDUITS ON THE ROOF SHALL BE MINIMUM 2.5" ABOVE THE ROOF SURFACE (INCLUDING CABLES UNDERNEATH MODULES AND RACKING). 7.THE PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL OR BUILDING ROOF VENTS. ROOF ACCESS PATHWAYS AND SETBACKS: IFC 605.11.1.2.2 HIP ROOF LAYOUTS PANELS AND MODULES INSTALLED ON GROUP R-3 BUILDINGS WITH HIP ROOF LAYOUTS SHALL BE LOCATED IN A MANNER THAT PROVIDES TWO, 3-FOOT WIDE ACCESS PATHWAYS FROM THE EAVE TO THE RIDGE ON EACH ROOF SLOPE WHERE PANELS AND MODULES ARE LOCATED. THE ACCESS PATHWAY SHALL BE AT A LOCATION ON THE BUILDING CAPABLE OF SUPPORTING THE FIRE FIGHTERS ACCESSING THE ROOF. IFC 605.11.1.2.3 SINGLE-RIDGED ROOFS PANELS AND MODULES INSTALLED ON GROUP R-3 BUILDINGS WITH A SINGLE RIDGE SHALL BE LOCATED IN A MANNER THAT PROVIDES TWO, 3-FOOT WIDE ACCESS PATHWAYS FROM THE EAVE TO THE RIDGE ON EACH ROOF SLOPE WHERE PANELS AND MODULES ARE LOCATED. IFC 605.11.1.2.4 ROOFS WITH HIPS AND VALLEYS PANELS AND MODULES INSTALLED ON GROUP R-3 BUILDINGS WITH ROOF HIPS AND VALLEYS SHALL NOT BE LOCATED CLOSER THAN 18 INCHES TO A HIP OR A VALLEY WHERE PANELS/MODULES ARE TO BE PLACED ON BOTH SIDES OF A HIP OR VALLEY. WHERE PANELS ARE TO BE LOCATED ON ONLY ONE SIDE OF A HIP OR VALLEY THAT IS OF EQUAL LENGTH, THE PANELS SHALL BE PERMITTED TO BE PLACED DIRECTLY ADJACENT TO THE HIP OR VALLEY. EXCEPTION: THESE REQUIREMENT SHALL NOT APPLY TO ROOFS WITH SLOPES OF TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR LESS. INSTALLATION NOTES ALUMINIUM RAILS SCALE:1"=10'-0" 2 X 4 PRE-FABRICATED TRUSSES@2'-0"SPACING ARRAY MP-1 ARRAY MP-2 SITE INFORMATION - WIND SPEED: 115 MPH AND SNOW LOAD: 50 PSF SR. NO AZIMUTH PITCH NO. OF MODULES ARRAY AREA (SQ. FT.)ROOF TYPE ATTACHMENT ROOF EXPOSURE FRAME TYPE FRAME SIZE FRAME SPACING MAX RAIL SPAN OVER HANG MP-01 88°29°22 466.5 COMPOSITION SHINGLE FLASH FOOT ATTIC PRE-FABRICATED TRUSSES 2 X 4 2'-0"4'-0"2'-0" MP-02 268°29°15 318.0 COMPOSITION SHINGLE FLASH FOOT ATTIC PRE-FABRICATED TRUSSES 2 X 4 2'-0"4'-0"2'-0" 3' 3' 3' 4' TOTAL AREA OF ROOF (SQ.FT)2462 TOTAL ARRAY AREA (SQ.FT)784.5156 TOTAL AREA OF ARRAY COVERED IN THE ROOF (%)31.86 MODULE END CLAMPMID CLAMPMODULE ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION STRUCTURAL DETAIL M-2 MODULES DATA LG SOLAR LG355N1C-V5 MODULE DIMS 69"x44.25"x1.57" LAG SCREWS 5/16"x3.5":2.5"MIN EMBEDMENT MID-CLAMP AND END-CLAMP ANATOMY SCALE:NTS GROUNDING LUG MID CLAMP ASSEMBLY MODULE FRAME RAIL MODULE TO MODULE & MODULE TO RAIL GROUNDING MID-CLAMP SCALE: NTS GROUNDING DETAILS IRONRIDGE RAIL IRONRIDGE INTERNAL SPLICE SELF-DRILLING SCREW SCALE: NTS RAIL TO RAIL T-BOLT 2 X 4 TRUSSES @2'-0"SPACING COMPOSITION SHINGLE ROOF MODULE 5/16" X 3.5" LAG SCREW 1 BOLT PER PENETRATION LOAD BEARING WALL SCALE:NTS ROOF FRAMING DETAILS ATTACHMENT DETAIL-FLASH FOOT FLASH FOOTSOLAR MODULE RAIL 5/16 HEX-BOLT STAINLESS STEEL 5/16" HANGER BOLT 2.5" EMBEDMENT PILOT HOLE REQUIRED 6" MAX DEAD LOAD CALCULATIONS BOM QUANTITY LBS/UNIT TOTAL WEIGHT (LBS) MODULES 37 42.8 1583.60 MID-CLAMP 56 0.050 2.80 END-CLAMP 36 0.050 1.80 RAIL LENGTH 148 0.680 100.64 SPLICE BAR 12 0.360 4.32 FLASH FOOT 88 1.35 118.80 MICRO-INVERTER 37 2.38 88.06 TOTAL WEIGHT OF THE SYSTEM (LBS)1900.02 TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)784.52 WEIGHT PER SQ. FT.(LBS)2.42 WEIGHT PER PENETRATION (LBS)21.59 ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION INSTALLATION CALCULATION M-3 MODULES DATA LG SOLAR LG355N1C-V5 MODULE DIMS 69"x44.25"x1.57" INSTALLATION CALCULATION KAT AND ERIC ADAIR - 13.135kW DC, 12.913kW AC ARRAY-2, ASPHALT SHINGLES IRONRIDGE FLASH FOOT 48" SPACING 1 MODULES X 4 = 4 ATTACHMENT RAIL LENGTH/ROW: 48.25(44.25" MODULE(1) +2" ENDCLAMP(2) +0.5" MIDCLAMP(0)) USE(1) 14' RAIL =168"-48.25" = CUT(119.75")X4 ARRAY-3, ASPHALT SHINGLES IRONRIDGE FLASH FOOT 48" SPACING 6 MODULES X 2.1 = 13 ATTACHMENT RAIL LENGTH/ROW: 272(44.25" MODULE(6) +2" ENDCLAMP(2) +0.5" MIDCLAMP(5)) USE(2) 14' RAIL + (1) SPLICE BAR =336"-272" = CUT(64")X2 ARRAY-1, ASPHALT SHINGLES IRONRIDGE FLASH FOOT 48" SPACING 5 MODULES X 2.4 = 12 ATTACHMENT RAIL LENGTH/ROW: 227.25(44.25" MODULE(5) +2" ENDCLAMP(2) +0.5" MIDCLAMP(4)) USE(2) 14' RAIL + (1) SPLICE BAR =336"-227.25" = CUT(108.75")X10 ARRAY-4, ASPHALT SHINGLES IRONRIDGE FLASH FOOT 48" SPACING 4 MODULES X 2.25 = 9 ATTACHMENT RAIL LENGTH/ROW: 182.5(44.25" MODULE(4) +2" ENDCLAMP(2) +0.5" MIDCLAMP(3)) USE(1) 17' RAIL =204"-182.5" = CUT(21.5")X2 4 (N)PV REVENUE METER M 4 (N)100A UTILITY AC DISCONNECT 70A FUSE1' LINE (N) 100AMP UTILITY AC DISCONNECT(EXTERIOR)(VISIBLE BLADE, LOCKABLE, READILY ACCESSIBLE, LABELED, LOCATED WITHIN 10' OF MAIN SERVICE METER, NO CLEARANCE ISSUES) (N) UTILITY OWNED PV PRODUCTION METER(EXTERIOR)120V/240V, 200A (LOCATED NEXT TO UTILITY AC DISCONNECT, READILY ACCESSIBLE, LABELED, LOCATED WITHIN 10' OF MAIN SERVICE METER, NO CLEARANCE ISSUES) (E)150A END FED MAIN PANEL UTILITY GRID (E)150A MAINBREAKER(E) GROUND ELECTRODE SUPPLY SIDE TAP 4 EXISTING 120/240V 1PH 60HZ METER#:DAKOTA ELECTRIC 73 283 910M 20' 1' (1) BRANCH OF (9) MICRO-INVERTERS (1) BRANCH OF (9) MICRO-INVERTERS (1) BRANCH OF (9) MICRO-INVERTERS (N)JUNCTION BOX OR EQUI. 1 DC CONDUCTORS AC CONDUCTORS20A 10A 20A 20A 20A AC COMBINER WITH ENPHASE ENVOY-S EN-X-IQ-AM1-240-2 120/240 NEMA 3R INSTALL (4)20A PV 2P BREAKERS ENPHASE IQ COMBINER + CABINET (ONLY FOR SOLAR, NO LOADS TO BE ADDED) (37)LG SOLAR LG355N1C-V5,MODULES WITH (37)ENPHASE IQ7A-72-2-US , 1-PHASE, 290W OUTPUT, 240V INVERTER, (UL1741 CERTIFIED) INVERTER COMPLIES WITH UL1741 5' (1) BRANCH OF (10) MICRO-INVERTERS 2 20' SINGLE LINE DIAGRAM: DC SYSTEM SIZE - 13135W, AC SYSTEM SIZE - 12913W ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION SINGLE LINE DIAGRAM E-1 1.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER NEC 310.0(D). 2.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER NEC 310.8(C). 3.MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%. 4.ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED. 5.BREAKER/FUSE SIZES CONFORMS TO NEC 240.6 CODE SECTION. 6.AC GROUNDING ELECTRODE CONDUCTOR SIZED PER NEC 250.66. 7.AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON NEC 690.31(C). 8.AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON NEC 310.15(B)(2)(C). 9.MAX. SYSTEM VOLTAGE CORRECTION IS PER NEC 690.7. 10.CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE NEC 310.16. ELECTRICAL NOTES MICRO INVERTER SPECIFICATIONS MODEL ENPHASE IQ7A-72-2-US POWER RATING 349W MAX OUTPUT CURRENT 1.45A CEC WEIGHTED EFFICIENCY 97% MAX NO OF MICRO INVERTERS/BRANCH 11 MAX DC VOLTAGE 58V MODULE SPECIFICATION MODEL LG SOLAR LG355N1C-V5 MODULE POWER @ STC 355W OPEN CIRCUIT VOLTAGE:Voc 41.4V MAX POWER VOLTAGE:Vmp 35.7V SHORT CIRCUIT VOLTAGE:Isc 10.65A MAX POWER CURRENT:Imp 9.95A ELECTRICAL CALCULATIONS AC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS >> ·REQUIRED CONDUCTOR AMPACITY: INVERTER OUTPUT CURRENT X #OF INVERTERSXMAX CURRENT PER 690.8(A)(3)X125% PER 690.8(B)(2)(A) ·CORRECTED AMPACITY CALCULATIONS:AMPACITY X TEMPERATURE DERATE FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY ·DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(B)(2)(2) < DERATED CONDUCTOR AMPACITY SUPPLY SIDE TAP CONNECTION SHALL BE MADE WITH 2017 NEC 240.21 ART SUPPLY SIDE TAP CONNECTION SHALL BE MADE WITH MILBANK (K4977-INT) LUG CONNECTORS PRODUCTION METER SHALL BE WIRED SUCH THAT THE DER SYSTEM IS THE SOURCE MAIN SERVICE METER BI-DIRECTIONAL-1PHASE, 3WIRE 120/240V NOTE: 1. THE PV AC DISCONNECTS WILL INCLUDE A YELLOW W BLACK LETTERING PLACARD SAYING "PV AC DISCONNECT". 2. THE UTILITY METER WILL HAVE A YELLOW W BLACK LETTERING PLACARD SAYING "PHOTOVOLTAIC SYSTEM CONNECTED". CONDUIT SCHEDULE TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND 1 NONE (2) 12AWG ENPHASE Q CABLE PER BRANCH CIRCUIT NONE (1) 12AWG ENPHASE Q CABLE 2 3/4"EMT OR EQUIV (8) 10AWG THHN/THWN-2 NONE (1) 10AWG THHN/THWN-2 3 1"EMT OR EQUIV (2) 4 AWG THHN/THWN-2 (1)4 AWG THHN/THWN-2 (1) 8AWG THHN/THWN-2 NOTE: MAIN PANEL RATING:150A, MAIN BREAKER RATING:150A LINE SIDE TAP: 100% ALLOWABLE BACKFEED IS =150A OCPD CALCULATIONS: INVERTER OVERCURRENT PROTECTION= INVERTER O/P I X CONTINUOUS LOAD(1.25) =1.45x1.25x37=67.06A=>PV BREAKER = 70A TOTAL REQUIRED PV BREAKER SIZE / FUSE SIZE=>70A PV BREAKER AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR AMPACITY CHECK 1 1.45 X 10 =14.50 X 1.25 =18.13A 30 X 0.87 X 1 =26.10A 18.13A <26.10A 2 1.45 X 10 =14.50 X 1.25 =18.13A 40 X 0.87 X 1 =34.80A 18.13A <34.80A 3 1.45 X 37 =53.65 X 1.25 =67.06A 95 X 0.87 X 1 =82.65A 67.06A <82.65A ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION OPTIMIZER MAP AND STRING CONFIGURATION S-1 MODULES DATA LG SOLAR LG355N1C-V5 MODULE DIMS 69"x44.25"x1.57" OPTIMIZER MAP STRING CALCULATION KAT AND ERIC ADAIR - 13.135kW DC, 12.913kW AC STRING CONFIGURATION ENPHASE IQ7A-72-2-US A 10 MODULES B 9 MODULES C 9 MODULES D 9 MODULES MAX STRING LENGTH 11 MODULES AA A A AA A A AAB B B B B B BB B C C C C C C C CC D D D DD D D D D ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION LABELING AND WARNING SIGNS PL-1 NOTE: LABELS SHALL BE WEATHERPROOF, DURABLE, AND PERMANENTLY MOUNTED. THIS PHOTOVOLTAIC INSTALLATION WILL MEET OR EXCEED THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE (NEC) AND WILL PASS ELECTRICAL INSPECTION PRIOR TO UTILITY COMMISSIONING. THE STATE-LICENSED ELECTRICAL INSPECTOR WILL ALREADY HAVE VERIFIED ALL NEC REQUIREMENTS, INCLUDING LABELING. ALL OUTDOOR LABELS ARE UV STABLE REFLECTIVE VINYL W/ACRYLIC LAMINATE, PERMANENTLY ATTACHED.OPERATING TEMPERATURE: -40ºF TO 175ºF, CERTIFIED: UL969 LINE SIDE TAP LABEL #1,4,7,8,10,13,14 LABEL #3,8 LABEL #5 LABEL #5 LABEL #5 LABEL #6,12 JUNCTION BOX COMBINER + CABINET UTILITY AC DISCONNECT UTILITY OWNED PV PRODUCTION METER MAIN SERVICE PANEL PV PANEL ARRAY UTILITY SERVICE METER LABEL #16,17 UM PMMSP AC CB WARNING PLACARD ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: WARNING PLACARDS PL-2 PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION ! WARNING CAUTION: SOLAR CIRCUIT CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED LABEL LOCATION POINT OF INTERCONNECTION (PER CODE: NEC 705.12(D)(7) [ Not Required if Panel board is rated not less than sum of ampere ratings of all overcurrent devices supplying it] ELECTRIC SHOCK HAZARD THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED LABEL LOCATION DC DISCONNECT,INVERTER [PER CODE: NEC 690.35(F)] [To be used when inverter is ungrounded] WARNING:PHOTOVOLTAIC POWER SOURCE LABEL LOCATION CONDUIT, COMBINER BOX [PER CODE: NEC690.31(G)(3)(4) & NEC 690.13(G)(4)] WARNING-Electric Shock Hazard No User Serviceable Parts inside Contact authorized service provide for assistance LABEL LOCATION INVERTER, JUNCTION BOXES(ROOF), AC DISCONNECT [PER CODE: NEC 690.13.G.3 & NEC 690.13.G.4] LABEL LOCATION DISCONNECT, POINT OF INTERCONNECTION [PER CODE: NEC690.13(B)] LABEL LOCATION AC DISCONNECT , POINT OF INTERCONNECTION [PER CODE: NEC 690.54] LABEL LOCATION MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES AND CABLE ASSEMBLES AT LEAST EVERY 10 FT, AT TURNS AND ABOVE/BELOW PENETRATIONS AND ALL COMBINER/JUNCTION BOXES. (PER CODE: IFC605.11.1.4) LABEL LOCATION POINT OF INTERCONNECTION [PER CODE: NEC705.12(D)(4)] ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION AC DISCONNECT,POINT OF INTERCONNECTION [PER CODE: NEC 690.17(E)] DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING LABEL LOCATION AC DISCONNECT,POINT OF INTERCONNECTION [PER CODE: NEC 690.17(E)] LABEL LOCATION WEATHER RESISTANT MATERIAL, DURABLE ADHESDIVE, UL969 AS STANDARD TO WEATHER RATING (UL LISTING OF MARKINGS NOT REQUIRED), MIN 38" LETTER HEIGHT ARIAL OR SIMILAR FONT NON-BOLD,PLACED WITHIN THE MAIN SERVICE DISCONNECT,PLACED ON THE OUTSIDE OF THE COVER WHEN DISCONNECT IS OPERATED WITH THE SERVICE PANEL CLOSED. (PWER CODE: NEC690.15 ,690.13(B)) WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM ! ! !SOLAR DISCONNECT WARNING! WARNING INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS OVER-CURRENT DEVICE RATED AC OPERATING CURRENT AC NOMINAL OPERATING VOLTAGE 53.65 240 AMPS AC VAC PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH ! POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN !WARNING: SOLAR PHOTOVOLTAIC ARRAYS ON ROOF ALL PLACARDS SHALL BE WEATHERPROOF, DURABLE, AND PERMANENTLY MOUNTED. BACKGROUND ON ALL PLACARDS SHALL BE RED WITH WHITE LETTERING U.O.N. PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE. FASTENERS APPROVED BY THE LOCAL JURISDICTION PHOTOVOLTAIC "D/C" DISCONNECT TO BE LOCATED ON EXTERNAL D/C DISCONNECT #2 D/C DISCONNECT TO BE PERMANENTLY MARKED AS FOLLOWS PHOTOVOLTAIC UTILITY "A/C" DISCONNECT TO BE LOCATED ON EXTERNAL A/C DISCONNECT #3 UTILITY A/C DISCONNECT TO BE PERMANENTLY MARKED AS FOLLOWS NEC 690.54, 690.15 #7 CAUTION: PHOTOVOLTAIC SYSTEM IS LINESIDE TAP ELECTRIC SHOCK HAZARD IF GROUND FAULT IS INDICATED NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED WARNING #4 #1 #5 #6 #8 #10 #11 #12 #13 (E) UTILITY METER (EXTERIOR) (N) AC DISCONNECT (EXTERIOR) (N) PV PRODUCTION METER (EXTERIOR) (E) MAIN SERVICE PANEL(INTERIOR) PV PRODUCTION METER TO BE LOCATED ON PRODUCTION METER #15 GENERAL SERVICE METER PER UTILITY REQUIREMENT #16 PHOTOVOLTAIC SYSTEM CONNECTED #17 (N) ENPHASE COMBINER + CABINET (EXTERIOR) TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR ELECTRICPV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN LABEL LOCATION AC DISCONNECT , DC DISCONNECT,POINT OF INTERCONNECTION (PER CODE: NEC690.56(C)) ADDRESS: 18886 IDEN AVE, LAKEVILLE, MN 55044 SPEC SHEET ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: MODULE SPEC SHEET SS-1 PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION SPEC SHEET ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: INVERTER SPEC SHEET SS-2 PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION SPEC SHEET ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: COMBINER SPEC SHEET SS-3 PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION SPEC SHEET ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: LUG SPEC SHEET SS-4 PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION SPEC SHEET ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: MOUNT SPEC SHEET SS-5 PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION SPEC SHEET ADDRESS:18886 IDEN AVE, LAKEVILLE, MN 55044 44.675629, -93.249774 APN: 221-720-104-090 DESIGNER/CHECKED BY: CUSTOMER INFORMATION KRP/BH NAME:KAT AND ERIC ADAIR DATE:10/3/20 SCALE:AS NOTED REV:A AHJ:MN - CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC PRN NUMBER:PGS-014415 APPLICATION#: RAIL SPEC SHEET SS-6 PHONE: 763-438-1976 ADDRESS: 451 TAFT ST, NE MINNEAPOLIS, MN 55413 INSTALLER INFORMATION