HomeMy WebLinkAboutLA186552 - Approved plansCOMPANY INFORMATION
CLIENT INFORMATION
SYSTEM DETAILS
PROJECT-PAGE TITLE
ALL ENERGY SOLAR, INC
1264 ENERGY LANE
ST PAUL, MN 55108
(800) 620-3370
INFO@ALLENERGYSOLAR.COM
PAGE NUMBER
A0
REVISIONS
LAST: 11/23/20 BX
AZIMUTH
NOTES:
1. (30) ENPHASE IQ7PLUS
INVERTER(S)
2. ARRAY 1:
33° TILT, 180° AZIMUTH
3. ARRAY 2:
(Array 2 Tilt)° TILT, (Array 2
Azimuth)° AZIMUTH
6. ARRAY 3:
(Array 3 Tilt)° TILT, (Array 3
Azimuth)° AZIMUTH
7. ARRAY 4:
(Array 4 Tilt)° TILT, (Array 4
Azimuth)° AZIMUTH
COVER PAGE
MICHELLE BIGGS
19751 HENNING AVE
LAKEVILLE, MN 55044
PO 39974
N
HENNING AVE
ARRAY 1
REC 365
30
FLUSH ROOF MOUNT
10.95
Panel Type
# of Panels
System Size (kW)
COMPANY INFORMATION
CLIENT INFORMATION
SYSTEM DETAILS
PROJECT-PAGE TITLE
ALL ENERGY SOLAR, INC
1264 ENERGY LANE
ST PAUL, MN 55108
(800) 620-3370
INFO@ALLENERGYSOLAR.COM
PAGE NUMBER
A1
REVISIONS
LAST: 11/23/20 BX
AZIMUTH
ACCOUNT: 200010016138
PREMISE:
METER: I077072999
PROPERTY MAP
N
MICHELLE BIGGS
19751 HENNING AVE
LAKEVILLE, MN 55044
PO 39974
NOTES:
1. (30) ENPHASE IQ7PLUS
INVERTER(S) = 8.7kW AC
2. ARRAY 1:
180° AZIMUTH, 33° TILT
(30) REC 365W = 10.95kW
3. ARRAY 2:
(Array 2 Azimuth)° AZIMUTH,
(Array 2 Tilt)° TILT
((Array 2 Panel Qty)) REC 365W =
(Array 2 kW)kW
4. ARRAY 3:
(Array 3 Azimuth)° AZIMUTH,
(Array 3 Tilt)° TILT
((Array 3 Panel Qty)) REC 365W =
(Array 3 kW)kW
5. ARRAY 4:
(Array 4 Azimuth)° AZIMUTH,
(Array 4 Tilt)° TILT
((Array 4 Panel Qty)) REC 365W =
(Array 4 kW)kW
ARRAY 1
HENNING AVE
BOS
SOLAR MODULES COVER
~21% OF ROOF PLAN
FIRE CODE
ACCESS PATHWAYS
COMPANY INFORMATION
CLIENT INFORMATION
SYSTEM DETAILS
PROJECT-PAGE TITLE
ALL ENERGY SOLAR, INC
1264 ENERGY LANE
ST PAUL, MN 55108
(800) 620-3370
INFO@ALLENERGYSOLAR.COM
PAGE NUMBER
A2
REVISIONS
LAST: 11/23/20 BX
NOTES:
1. ELEVATIONS MAY
VARY DEPENDING ON
GROUND ELEVATION
BUT ARE DRAWN TO
THE BEST OF OUR
ABILITY
2. 2x4 TRUSS 24" OC
ELEVATION
DRAWINGS
MICHELLE BIGGS
19751 HENNING AVE
LAKEVILLE, MN 55044
PO 39974
SETBACKS:
18" FROM RIDGE
36" FROM EDGE
SOUTH ELEVATION
WEST ELEVATION
FIRE CODE
ACCESS PATHWAYS
34'-9"33'-7"25'-2"24'-0"
COMPANY INFORMATION
CLIENT INFORMATION
SYSTEM DETAILS
PROJECT-PAGE TITLE
ALL ENERGY SOLAR, INC
1264 ENERGY LANE
ST PAUL, MN 55108
(800) 620-3370
INFO@ALLENERGYSOLAR.COM
PAGE NUMBER
A3
REVISIONS
LAST: 11/23/20 BX
AZIMUTH
ACCOUNT: 200010016138
PREMISE:
METER: I077072999
SITE MAP
N
MICHELLE BIGGS & DAVID
BIGGS
19751 HENNING AVE
LAKEVILLE, MN 55044
PO 39974
NOTES:
1. (30) ENPHASE IQ7PLUS
INVERTER(S) = 8.7kW AC
2. ARRAY 1:
180° AZIMUTH, 33° TILT
(30) REC 365W = 10.95kW
3. ARRAY 2:
(Array 2 Azimuth)° AZIMUTH,
(Array 2 Tilt)° TILT
((Array 2 Panel Qty)) REC 365W =
(Array 2 kW)kW
4. ARRAY 3:
(Array 3 Azimuth)° AZIMUTH,
(Array 3 Tilt)° TILT
((Array 3 Panel Qty)) REC 365W =
(Array 3 kW)kW
5. ARRAY 4:
(Array 4 Azimuth)° AZIMUTH,
(Array 4 Tilt)° TILT
((Array 4 Panel Qty)) REC 365W =
(Array 4 kW)kW
NOTES:
1. LOCATION OF SERVICE PANEL AND ELECTRICAL
EQUIPMENT ARE SHOWN. FINAL LOCATION MAY CHANGE
2. LOCATION OF SERVICE PANEL AND ADDITIONAL
ELECTRICAL EQUIPMENT NOT DRAWN TO SCALE
3. PV INTERCONNECTION IS A SECONDARY
INTERCONNECTION
4. AC DISCONNECT AND PRODUCTION METER IN
READILY ACCESSIBLE LOCATION WITHIN 10' OF MAIN
SERVICE METER/BI-DIRECTIONAL METER. 24/7
UNESCORTED KEYLESS ACCESS TO BE PROVIDED FOR
UTILITY AC DISCONNECT, PV PRODUCTION METER, & BI-
DIRECTIONAL METER.
5. PV EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE
WITH NEC 690 AND POSTED WITH APPLICABLE
WARNINGS, SIGNAGE, AND PLAQUES PER NEC 705-10,
690-17, & 690-64 (b)(5).
6. CIRCUITS:
(3) CIRCUIT(S) OF 10 (20AMPS EACH)
((Qty of circuits with the number of inverters optimizers above))
CIRCUIT(S) OF (Qty of inverters/optimizers in a circuit/string)
([Amps] (If Enphase. Based on 15 or 20A breakers)AMPS
EACH)
((Qty of circuits with the number of inverters optimizers above))
CIRCUIT(S) OF (Qty of inverters/optimizers in a circuit/string)
([Amps] (If Enphase. Based on 15 or 20A breakers)AMPS
EACH)
((Qty of circuits with the number of inverters optimizers above))
CIRCUIT(S) OF (Qty of inverters/optimizers in a circuit/string)
([Amps] (If Enphase. Based on 15 or 20A breakers)AMPS
EACH)
((Qty of circuits with the number of inverters optimizers above))
CIRCUIT(S) OF (Qty of inverters/optimizers in a circuit/string)
([Amps] (If Enphase. Based on 15 or 20A breakers)AMPS
EACH)
1 2
3
4
5
6
LABELS LOCATED ON PV PRODUCTION METER, BI-
DIRECTIONAL METER, AC DISCONNECT(S), INVERTER(S),
AND APPROPRIATE LABELS ON MAIN ELECTRIC SERVICE.
ALL LABELS ARE PERMANENT, WEATHERPROOF, AND
DURABLE
THERE ARE NO CLEARANCE ISSUES DUE TO OVERHEAD
POWERLINES.
CALL-OUTS:
1: SOLAR PANELS
2: INVERTERS
3: ENPHASE IQ COMBINER PANEL
4: UTILITY AC DISCONNECT
5: PV PRODUCTION METER
6: MAIN ELECTRIC SERVICE
7: BI-DIRECTIONAL METER
8: OFF PEAK METER
DISTANCES
SOLAR PANELS - INVERTERS: 5' MAX
INVERTERS - IQ COMBINER PANEL: 75' MAX
IQ COMBINER PANEL - UTILITY AC DISCONNECT: 2'
UTILITY AC DISCONNECT - PV PRODUCTION METER: 2'
PV PRODUCTION METER - MAIN ELECTRIC SERVICE: 5'
MAIN ELECTRIC SERVICE - BI-DIRECTIONAL METER: 5'
7
<10'80'
HIBBING WAY HENNING AVE
ARRAY 1
8
COMPANY INFORMATION
CLIENT INFORMATION
SYSTEM DETAILS
PROJECT-PAGE TITLE
ALL ENERGY SOLAR, INC
1264 ENERGY LANE
ST PAUL, MN 55108
(800) 620-3370
INFO@ALLENERGYSOLAR.COM
PAGE NUMBER
A4
REVISIONS
LAST: 11/23/20 BX
*STRINGING TO BE
DETERMINED ON SITE
2x4 TRUSS 24" OC
RAIL AND
STRINGING
DIAGRAM
AZIMUTH
<aCustName(s)>
<aCustAddress1>
<aCustAddress2>
<aCustAddress3>
PO <aCustPONumber>
N
MICHELLE BIGGS
19751 HENNING AVE
LAKEVILLE, MN 55044
PO 39974
SNAP-N-RACKSNR FLASHING
MODULE
2x4 TRUSS 24" OC
(30) REC REC365AA MODULES
(30) ENPHASE IQ7PLUS
INVERTER(S)
CIRCUITS:
(3) CIRCUIT(S) OF 10 MICROS
((Qty of circuits with the number of
inverters optimizers above))
CIRCUIT(S) OF (Qty of
inverters/optimizers in a
circuit/string) MICROS
((Qty of circuits with the number of
inverters optimizers above))
CIRCUIT(S) OF (Qty of
inverters/optimizers in a
circuit/string) MICROS
((Qty of circuits with the number of
inverters optimizers above))
CIRCUIT(S) OF (Qty of
inverters/optimizers in a
circuit/string) MICROS
((Qty of circuits with the number of
inverters optimizers above))
CIRCUIT(S) OF (Qty of
inverters/optimizers in a
circuit/string) MICROS
SNAP-N-RACK
MOUNTING HARDWARE:
1. (73) L-FEET
2. (10) RAIL SPLICES
3. CLAMPS
(48) MIDCLAMPS
(24) ENDCLAMPS
4. RAIL LENGTHS:
(20) 168" RAILS
LEGEND:
TERM CAP:
OPEN END:
MAX CIRCUIT
LENGTH (120/240V)
15A
BREAKER
20A
BREAKER
ENPHASE IQ7 12 16
ENPHASE IQ7+9 13
ENPHASE IQ7X 9 12
ENPHASE IQ7A 8 11
102"39'-9"98"
31"
14'-9"
18"
36"
ROOFTECH MINI
ATTACHMENTS
FIRE CODE
ACCESS
PATHWAYS
COMPANY INFORMATION
CLIENT INFORMATION
SYSTEM DETAILS
PROJECT-PAGE TITLE
ALL ENERGY SOLAR, INC
1264 ENERGY LANE
ST PAUL, MN 55108
(800) 620-3370
INFO@ALLENERGYSOLAR.COM
PAGE NUMBER
A5
REVISIONS
LAST: 11/23/20 BX
*DISTANCES NOT TO SCALE
SYSTEM SIZE: 10.95kW DC
MAXIMUM POWER: 8.7 kW AC
OPERATING VOLTAGE: 120/240V
MAXIMUM CURRENT: 36.3A
ACCOUNT: 200010016138
PREMISE:
METER: I077072999
NOTES:
1. DESIGN MEETS NEC CODE
AND SHALL BE INSTALLED IN
ACCORDANCE WITH NEC 690
AND POSTED WITH APPLICABLE
WARNINGS, SIGNAGE, AND
PLAQUES PER NEC 705-10, 690-
17, & 690-64 (b) (5)
2. SOLAR MODULES, INVERTERS,
AND CORRESPONDING
ELECTRICAL EQUIPMENT ARE
LISTED.
3. INVERTERS ARE UL 1741
LISTED
4. PV INTERCONNECTION IS A
SECONDARY INTERCONNECTION
ELECTRICAL
LINE DIAGRAM
TO UTILITY
MICHELLE BIGGS & DAVID
BIGGS
19751 HENNING AVE
LAKEVILLE, MN 55044
PO 39974
5' MAX
ENPHASE IQ COMBINER PANEL
120/240V: 125A: 1 PHASE
PLACARD INDICATING
"NO LOAD TO BE SERVED"
SEE LABEL(S) 10, 13, 14, 16, 19
ON FOLLOWING PAGES
UTILITY
AC DISCONNECT
VISIBLE-OPEN TYPE, LOCKABLE,
READILY ACCESSIBLE
1 PHASE, 60A, 120/240V
SEE LABEL(S) 10, 14, 15, 16, 18, 19, 20
ON FOLLOWING PAGES
5'
EXISTING
CONDUIT
AC
DC
2' MAX 3/4" EMT:
(2) #8 THWN
(1) #10 NEUTRAL
(1) #10 GROUND
SQUARE D
LOAD PANEL
SEE LABEL(S) 14, 16, 35, 36, 37
ON FOLLOWING PAGES
120/240V
225A RATED BUS
200A
MAIN
50A
REC
REC365AA
RATED POWER
AT STC:365W
VMP:37.10V
IMP:9.85A
VOC:44.00V
ISC:10.52A
MODULE DETAILS:
(30)
(30) REC
REC365AA
10.95kW
(30) ENPHASE
IQ7PLUS
120/240V
(3) CIRCUIT(S) OF 10 (20A EA)
((Qty of circuits with the number
of inverters optimizers above))
CIRCUIT(S) OF (Qty of
inverters/optimizers in a
circuit/string) ([Amps] (If
Enphase. Based on 15 or 20A
breakers)A EA)
((Qty of circuits with the number
of inverters optimizers above))
CIRCUIT(S) OF (Qty of
inverters/optimizers in a
circuit/string) ([Amps] (If
Enphase. Based on 15 or 20A
breakers)A EA)
((Qty of circuits with the number
of inverters optimizers above))
CIRCUIT(S) OF (Qty of
inverters/optimizers in a
circuit/string) ([Amps] (If
Enphase. Based on 15 or 20A
breakers)A EA)
((Qty of circuits with the number
of inverters optimizers above))
CIRCUIT(S) OF (Qty of
inverters/optimizers in a
circuit/string) ([Amps] (If
Enphase. Based on 15 or 20A
breakers)A EA)
INVERTER DETAILS:
ENPHASE IQ7PLUS-72-2-US
Rating: 290 W
CEC Weighted Efficiency: 97 %
Max DC Voltage: 60.V V
Max AC Output Current: 1.21 A
Nominal Voltage Range:
240V / 211-264V (1-Phase)
Nominal Frequency: 60 Hz
DAKOTA ELECTRIC
ASSOCIATION
BI-DIRECTIONAL METER
120/240V, 1-PHASE, 3-WIRE
SEE LABEL(S) 41, 42, 43
ON FOLLOWING PAGES
75' MAX 3/4" EMT:
(6) #10 THWN
(1) #10 GROUND
2' MAX 3/4" EMT:
(2) #6 THWN
(1) #6 NEUTRAL
(1) #10 GROUND
5' MAX 3/4" EMT:
(2) #6 THWN
(1) #6 NEUTRAL
(1) #10 GROUND
DAKOTA ELECTRIC
ASSOCIATION
PRODUCTION METER
120/240V, 200A WITH
BYPASS
1-PHASE, 3-WIRE
SEE LABEL(S) 21 ON
FOLLOWING PAGES
LINE/
TOP
LOAD/
BOTTOM
COMPANY INFORMATION
CLIENT INFORMATION
SYSTEM DETAILS
PROJECT-PAGE TITLE
ALL ENERGY SOLAR, INC
1264 ENERGY LANE
ST PAUL, MN 55108
(800) 620-3370
INFO@ALLENERGYSOLAR.COM
PAGE NUMBER
A6
REVISIONS
LAST: 11/23/20 BX
LABELS ARE WEATHERPROOF,
DURABLE, PERMANENTLY
MOUNTED, AND COMPLY WITH
NEC 690
ACCOUNT: 200010016138
PREMISE:
METER: I077072999
LABELS
MICHELLE BIGGS & DAVID
BIGGS
19751 HENNING AVE
LAKEVILLE, MN 55044
PO 39974
COMPANY INFORMATION
CLIENT INFORMATION
SYSTEM DETAILS
PROJECT-PAGE TITLE
ALL ENERGY SOLAR, INC
1264 ENERGY LANE
ST PAUL, MN 55108
(800) 620-3370
INFO@ALLENERGYSOLAR.COM
PAGE NUMBER
A7
REVISIONS
LAST: 11/23/20 BX
LABELS 2
LABELS ARE WEATHERPROOF,
DURABLE, PERMANENTLY
MOUNTED, AND COMPLY WITH
NEC 690
ACCOUNT: 200010016138
PREMISE:
METER: I077072999
43
18
HOUSE SERVICE DISCONNECT
(INSIDE)
MICHELLE BIGGS & DAVID
BIGGS
19751 HENNING AVE
LAKEVILLE, MN 55044
PO 39974
CAUTION:MULTIPLE SOURCES OF POWER:
N
All Energy Solar
www.allenergysolar.com
(800) 620-3370
SOLAR ARRAY
PV DISCONNECT
PV COMBINER PANEL
INTERCONNECTION
DISCONNECT SWITCH
17
DUAL POWER SOURCE
PHOTOVOLTAIC CIRCUIT
Operating Voltage: 120/240
Maximum Current: 36.3 Amps
Maximum Power: 8.7 KW
MAXIMUM VOLTAGE
MAXIMUM CIRCUIT CURRENT
MAX RATED OUTPUT CURRENT OF
THE CHARGE CONTROLLER
OR DC-TO-DC CONVERTER
(IF INSTALLED)
22
P H O T O V O L T A I C
D C D I S C O N N E C T