Loading...
HomeMy WebLinkAboutLA188772 - Approved plans Shawn Vaughan Engineering 3-4-21_nBgU6TMtG Wyssling Consulting 76 North Meadowbrook Drive Alpine, UT 84004 Scott E. Wyssling, PE, PP, CME office (201) 874-3483 swyssling@wysslingconsulting.com March 4, 2021 Everlight Solar Construction PO Box 930550 Verona, WI 53593 Re: Engineering Services Vaughan Residence 19763 Idealic Avenue, Lakeville, MN 10.412 kW System To Whom It May Concern: Pursuant to your request, we have reviewed the following information regarding solar panel installation on the roof of the above referenced home: 1. Site Visit/Verification Form prepared by an Everlight Solar representative identifying specific site information including size and spacing of rafters for the existing roof structure. 2. Design drawings of the proposed system including a site plan, roof plan and connection details for the solar panels. This information was prepared by Everlight Solar and will be utilized for approval and construction of the proposed system. 3. Photographs of the interior and exterior of the roof system identifying existing structural members and their conditions. Based on the above information we have evaluated the structural capacity of the existing roof system to support the additional loads imposed by the solar panels and have the following comments related to our review and evaluation: Description of Residence: The existing residence is typical wood framing construction with the roof system consisting of truss system with all chords constructed of 2 x 4 dimensional lumber at 24” on center. The attic space is unfinished and photos indicate that there was free access to visually inspect the size and condition of the roof rafters. All wood material utilized for the roof system is assumed to be Doug-Fir #2 or better with standard construction components. The existing roofing material consists of composite asphalt shingles. Photos of the dwelling also indicate that there is a permanent foundation. A. Loading Criteria Used • 115 MPH wind loading based on ASCE 7-16 Exposure Category “C” at a slope of 25 degrees • 7 PSF = Dead Load roofing/framing Live Load = 20 PSF Snow Load = 50 PSF • 3 PSF = Dead Load solar panels/mounting hardware Total Dead Load =10 PSF The above values are within acceptable limits of recognized industry standards for similar structures in accordance with the Minnesota Residential Code (2018 IRC). Analysis performed of the existing roof structure utilizing the above loading criteria indicates that the existing rafters will support the additional panel loading without damage, if installed correctly. Page 2 of 2 B. Solar Panel Anchorage 1. The solar panels shall be mounted in accordance with the most recent “IronRidge Solar Installation Manual”, which can be found on the IronRidge Solar website (http://ironridgesolar.com/). If during solar panel installation, the roof framing members appear unstable or deflect non-uniformly, our office should be notified before proceeding with the installation. 2. Maximum allowable pullout per lag screw is 235 lbs/inch of penetration as identified in the National Design Standards (NDS) of timber construction specifications for Doug-Fir (North Lumber) assumed. Based on our evaluation, the pullout value, utilizing a penetration depth of 2 ½”, is less than what is allowable per connection and therefore is adequate. Based on the variable factors for the existing roof framing and installation tolerances, using a thread depth of 2 ½” with a minimum size of 5/16” lag screw per attachment point for panel anchor mounts should be adequate with a sufficient factor of safety. 3. Considering the roof slopes, the size, spacing, condition of roof, the panel supports shall be placed no greater than 48” o/c. 4. Panel supports connections shall be staggered to distribute load to adjacent trusses. Based on the above evaluation, it is the opinion of this office that with appropriate panel anchors being utilized the roof system will adequately support the additional loading imposed by the solar panels. This evaluation is in conformance with the Minnesota Residential Code (2018 IRC), current industry standards, and is based on information supplied to us at the time of this report. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Very truly yours, Scott E. Wyssling, PE Minnesota License No. 57927 SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701Xcel Energy MNPV01 COVER PAGE PV02 PROPERTY PLAN PV03 ROOF PLAN PV04 ROOF ATTACHMENTS + BOM PV05 MOUNTING DETAIL PV06 ELECTRICAL DIAGRAM PV07 LABELS PV08 PLACARD PV09 SITE PHOTOS DATE: March 3, 2021 PV01 PAGE: SHEET NAME: COVER PAGE DRAWN BY: SoloCAD GENERAL NOTES: 1.INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE 690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING. 2.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110. 3.ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250 4.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES. 5.ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.8] 6.DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.31] 7.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE. APPLICABLE GOVERNING CODES: DESCRIPTION OF DESIGN: INSTALLATION OF GRID -TIED, UTILITY INTERACTIVE PHOTOVOLTAIC SYSTEM AERIAL VIEW:STREET VIEW:SHEET INDEX: EQUIPMENT: MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERS RACKING: SolarRoofHook - 48" O.C. SITE SPECIFICATIONS: OCCUPANCY: R-3 ZONING: RESIDENTIAL 2020 NEC 2020 MRC 2020 MFC 2020 MBC SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSM MSP ACPVC JBJBCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701Xcel Energy MNDATE: March 3, 2021 PV02 PAGE: SHEET NAME: PROPERTY PLAN DRAWN BY: SoloCAD SCALE: EQUIPMENT LEGEND: INVERTER VISIBLE, LOCKABLE, LABELED AC DISCONNECT METER SOCKET (FOR UTILITY PV METER) UTILITY METER MAIN SERVICE PANEL LC LOAD CENTER FIRE ACCESS PATHWAY (3' TYP) C INV PV AC MSP M COMBINER BOX PROPERTY LINE 19763 Idealic AveMP2 PITCH: 25° AZIMUTH: 271°FRONT OF HOMEMP1 PITCH: 25° AZIMUTH: 91° BATT BATTERY(IES) VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED WITHIN 10' OF UTILITY METER1" = 26.42' CASE # 04376108 ALL PV EQUIPMENT INSTALLED WITHIN 10' OF UTILITY METER 24/7 UNESCORTED KEYLESS ACCESS SHALL BE PROVIDED TO XCEL ENERGY FOR ALL XCEL ENERGY OWNED METERS AND DISCONNECTS NO CLEARANCE ISSUES AROUND HOME OR SOLAR ARRAY ELECTRIC SERVICE LINES ARE UNDERGROUND NOT OVERHEAD SOLAR ARRAY INVERTERS BEHIND PANELS MAIN SERVICE PANEL LOCATED INSIDE 198th St W 275ft 71'-5" 251'-8" SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSM MSP ACPVC JBJB CONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701Xcel Energy MNDATE: March 3, 2021 PV03 PAGE: SHEET NAME: ROOF PLAN DRAWN BY: SoloCAD EQUIPMENT LEGEND: INVERTER VISIBLE, LOCKABLE, LABELED AC DISCONNECT METER SOCKET (FOR UTILITY PV METER) UTILITY METER MAIN SERVICE PANEL LC LOAD CENTER FIRE ACCESS PATHWAY (3' TYP) C INV PV AC MSP M COMBINER BOX FRONT OF HOMEMP2 PITCH: 25° AZIMUTH: 271° MP1 PITCH: 25° AZIMUTH: 91° BATT BATTERY(IES) VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED WITHIN 10' OF UTILITY METER 3'-0" TYP 1'-6" TYP 1'-6" TYP MSP JBJB SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701EQUIPMENT INFORMATION: RAIL MANUFACTURER IronRidge RAIL PART NUMBER XR-10 ATTACHMENTS Quickbolt ATTACHMENT QTY 66 MIDCLAMP QTY 66 ENDCLAMP QTY 16 SPLICE QTY 8 ROOF INFO: ROOF TYPE asphalt_shingle ROOF FRAMING manufactured_truss RAFTER/TOP CHORD SIZE 2x4 RAFTER/TOP CHORD SPACING 24 ATTACHMENT SPACING 48Xcel Energy MNDATE: March 3, 2021 PV04 PAGE: SHEET NAME: ROOF ATTACHMENTS + BOM DRAWN BY: SoloCAD ROOF ATTACHMENT COUNT:66 PV MODULE COUNT:37 ARRAY AREA:MODULE COUNT * 18.06ft² = 668.22 ROOF AREA:2247 ft² PERCENT OF ROOF COVERED:30% ARRAY WEIGHT:MODULE COUNT * 50lbs = 1850 DISTRIBUTED LOAD:ARRAY LBS/ATTACHMENTS = 28.03 POINT LOAD: (lbs/ft²)(ARRAY) WEIGHT/AREA = 2.77 lbs/ft² PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: RAIL L-FOOT/ATTACHMENT BRACKET (E) ROOF FRAMING 5/16" STAINLESS STEEL LAG-BOLT WITH 2-1/2" MIN. EMBEDMENT AND FLAT WASHER FLASHING PV MODULE (E) COMP SHINGLE ROOF (1 LAYER) RAIL END CLAMP PV MODULE MID CLAMP PV MODULE 4" 2 1 2" MIN. DEPTH RAIL RAIL FLASHING & LAG-BOLT 2'-8" MIN - 3'-10" MAX 3 RAIL PV MODULE " MAX."1'-8" MAX. 21 FRONT VIEW 10" MIN - 1'-4" MAX2'-8" MIN - 3'-10" MAX 10" MIN - 1'-4" MAX SIDE VIEW (E) RAFTER/TOP CHORDS (E) RAFTER/TOP CHORD DETAIL, MOUNTING AND FLASHING END CLAMP DETAILS MID CLAMP DETAILS 3 21 SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701EQUIPMENT INFORMATION: RAIL MANUFACTURER IronRidge RAIL PART NUMBER XR-10 ATTACHMENTS Quickbolt ATTACHMENT QTY 66 MIDCLAMP QTY 66 ENDCLAMP QTY 16 SPLICE QTY 8 ROOF INFO: ROOF TYPE asphalt_shingle ROOF FRAMING manufactured_truss RAFTER/TOP CHORD SIZE 2x4 RAFTER/TOP CHORD SPACING 24 ATTACHMENT SPACING 48Xcel Energy MNDATE: March 3, 2021 PV05 PAGE: SHEET NAME: MOUNTING DETAIL DRAWN BY: SoloCAD ROOF ATTACHMENT COUNT:66 PV MODULE COUNT:37 ARRAY AREA:MODULE COUNT * 18.06ft² = 668.22 ROOF AREA:2247 ft² PERCENT OF ROOF COVERED:30% ARRAY WEIGHT:MODULE COUNT * 50lbs = 1850 DISTRIBUTED LOAD:ARRAY LBS/ATTACHMENTS = 28.03 POINT LOAD: (lbs/ft²)(ARRAY) WEIGHT/AREA = 2.77 lbs/ft² PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: UTILITY PV PRODUCTION METER BASE PV AC DISCONNECT FUSED, AIC 10kA VISIBLE, LOCKABLE, LABELED, OPEN 240V, 2-POLE 4 4 (N) FUSES PV OCPD 4 (E) LOADS N G SUPPLY SIDE CONNECTION: NEC 230.46, NEC 230.79, NEC 705.12(A) LUG KIT TO BE ADDED (E)GROUNDING ELECTRODE INTERCONNECTION NOTES 1. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9] & [NEC 230.95] 2. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC705.12(A)] WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH [NEC 240.21(B)] DISCONNECT NOTES 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH. 3. FUSED AC DISCONNECT TO BE USED. (E) MAIN SERVICE PANEL (E) MAIN BREAKER (E) 120/240 VAC TO UTILITY GRID (E)UTILITY METER N G AC COMBINER BOX SOLAR LOADS ONLY UL 1741 COMPLIANT (N) 100A (3) 20A-2P J-BOX AC DC AC DC STRING [2] AC DC AC DC STRING [3] J-BOX J-BOX 3 1 1 2 2 AC DC AC DC STRING [1] J-BOX1 2 SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 7011 2 3 4(1) 12-2 TC-ER, THWN-2, COPPER (OR CODE APPROVED EQUIVALENT) (1) 6 AWG BARE, COPPER (GROUND) (1) 10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER - (POSITIVE) (1) 10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER - (NEGATIVE) (1) 10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER - (GROUND) (1) 3/4" LIQUID TIGHT OR EMT OR FMC (OR CODE APPROVED EQUIVALENT) (3) 10 AWG THHN/THWN-2, COPPER - (L1) (3) 10 AWG THHN/THWN-2 COPPER - (L2) (1) 10 AWG THHN/THWN-2 (GROUND) CONDUIT: 3/4" LIQUID TIGHT OR EMT (OR CODE APPROVED EQUIVALENT) (1) 6 AWG THWN-2 COPPER - (L1) (1) 6 AWG THWN-2 COPPER - (L2) (1) 6 AWG THWN-2 COPPER - (NEUTRAL) (1) 10 AWG THWN-2 COPPER - (GROUND) (1) CONDUIT: 3/4" LIQUID TIGHT OR EMT (OR CODE APPROVED EQUIVALENT) SERVICE EQUIPMENT & PV OCPD RATINGS MAIN BREAKER RATING 150A MAIN SERVICE BUS RATING 225A PV OCPD RATING 55A AC VOLTAGE 240V AC DISCONNECT RATING 60A STRINGS: STRING 1 14 PV MODULES STRING 2 14 PV MODULES STRING 3 9 PV MODULES Xcel Energy MNDATE: March 3, 2021 PV06 PAGE: SHEET NAME: ELECTRICAL DIAGRAM DRAWN BY: SoloCAD WIRE SCHEDULE EQUIPMENT SCHEDULE: TYPE:QTY:DESCRIPTION:RATING: MODULES:(37)Silfab SIL-330 NL 330 W INVERTERS:(19)AP Systems YC600 548 W AC DISCONNECT(S):(1)PV AC DISCONNECT, 240V, 2-POLE 60 A GROUNDING & GENERAL NOTES: 1. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE. 2. DC GEC AND AC EGC TO REMAIN UNSPLICED, OR SPLICED TO EXISTING ELECTRODE 3. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. 4. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD - JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS. 5. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT. CASE #: 04376108 DESIGN SHALL MEET NEC REQUIREMENTS AP Systems YC600 (240V) SPECS MAXIMUM INPUT VOLTAGE: MAXIMUM INPUT CURRENT: NOMINAL OUTPUT VOLTAGE: 240V NOMINAL OUTPUT CURRENT: 1-PHASE 60HZ UL 1741 LISTED REFERENCE POINT OF APPLICABILITY 55V 12A X2 2.28A UTILITY AC DISCONNECT 1-PH, 3-WIRE, 120/240V, 200A CUSTOMER OWNED NO LOADS OR STAGE SYSTEM ON DER SIDE OF PRODUCTION METER ALL PV EQUIPMENT INSTALLED WITHIN 10' OF UTILITY METER THE PV PRODUCTION METER SOCKET MUST HAVE LEVER BYPASS/BYPASS 240V RATED SERVICE SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701LABEL VALUES: DESCRIPTION VALUE: DC IMP:9.92 DC VMP:33.3 DC VOC:40.5 DC ISC:SEE DATASHEET DC SYSTEM SIZE (W):12210 AC OPERATING CURRENT:SEE DATASHEET AC VOLTAGE:240 Xcel Energy MNDATE: March 3, 2021 PV07 PAGE: SHEET NAME: LABELS DRAWN BY: SoloCAD LABEL 3 AT POINT OF INTERCONNECTION, MARKED AT AC DISCONNECTING MEANS. [NEC 690.54, NEC 690.13 (B)] LABEL 4 AT POINT OF INTERCONNECTION FOR EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUTS SUPPLYING POWER TO A BUSBAR OR CONDUCTOR SUPPLIED FORM MULTIPLE SOURCES, EACH SERVICE EQUIPMENT AND ALL ELECTRIC POWER PRODUCTION SOURCE LOCATIONS. [NEC 705.12(B)(3)] LABEL 5 PLACED ADJACENT TO THE BACK-FED BREAKER FROM THE INVERTER IF TIE IN CONSISTS OF LOAD SIDE CONNECTION TO BUSBAR. [NEC 705.12(D)(2)(3)(b)] *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON PV5 OF 3 LINE DIAGRAM. PV5 LINE DIAGRAM TO REFLECT ACTUAL REPRESENTATION OF PROPOSED SCOPE OF WORK. JUNCTION BOX OR COMBINER BOX MAIN SERVICE PANEL AC DISCONNECT EXISTING SUB PANEL (IF WHERE POINT OF INTERCONNECTION IS MADE) PV COMBINER SUBPANEL - IF USED TO COMBINE PV OUTPUT CIRCUITS AC DC INVERTER (S) INTEGRATED DC DISCONNECT 2 3 47 3 9 5 (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) 6 10 1 1 1 1 4 5 (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) 4 6 3 LABELING DIAGRAM: 12 11 8OR LABEL 6 AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND ENCLOSURES OF JUNCTION BOXES, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(G)(3&4)] LABEL 10 (ONLY IF 3 OR MORE SUPPLY SOURCES TO A BUSBAR) SIGN LOCATED AT LOAD CENTER IF IT CONTAINS 3 OR MORE POWER SOURCES. [NEC 705.12(D)(2)(3)(C)] LABEL 9 SIGN LOCATED AT RAPID SHUT DOWN DISCONNECT SWITCH [NEC 690.56(C)(3)]. LABEL 7 FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND CONDUCTORS LEAVING THE ARRAY: SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [NEC 690.56(C)(1)(A)] LABEL 8 FOR PV SYSTEMS THAT ONLY SHUT DOWN CONDUCTORS LEAVING THE ARRAY: SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [NEC 690.56(C)(1)(B)] LABEL 11 PLACARD TO BE PLACED AT THE MAIN BILLING METER PER XCEL ENERGY. LABEL 12 PLACARD TO BE PLACED AT AC DISCONNECT PER XCEL ENERGY. LABEL 1 FOR PV DISCONNECTING MEANS WHERE ALL TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION. [NEC 690.13(B), NEC 705.22] LABEL 2 AT EACH DC DISCONNECTING MEANS, INCLUDING THE DC DISCONNECT AT THE INVERTER. [NEC 690.53, NEC 690.13(B)] LABEL 13 SIGN LOCATED AT MAIN SERVICE DISCONNECTING MEANS IF ALL ELECTRICAL POWER SOURCE DISCONNECTING MEANS ARE GROUPED WITHIN 10' AND LINE OF SITE OF MAIN SERVICE DISCONNECT [NEC 690.56(B) & NEC 705.10]. LABEL 14 SIGN LOCATED AT AC COMBINER BOX FOR ALL MICRO-INVERTER / AC MODULE INSTALLS (IF APPLICABLE). 13 14 LABELING NOTES: 1.LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. 2.LABELING REQUIREMENTS BASED ON THE 2014 NATIONAL ELECTRIC CODE, OSHA STANDARD 19010.145, ANSI Z535. 3.MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 4.LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC 110.21] 5.LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLY AFFIXED [IFC 605.11.1.1] 3 4 1 43 240 0 0 UTILITY AC DISCONNECT LABEL 15 PLACARD TO BE PLACED AT BI-DIRECTIONAL METER PER XCEL ENERGY.PRODUCTION METER See attached label schedule. All labels weatherproof, durable, and permanently mounted. Demonstrate NEC 690 labeling requirements met. M MSP ACPVC JBJB SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701Xcel Energy MNPOWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: CAUTION DIRECTORY PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM. (ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN: NEC 690.56(B)&(C), [NEC 705.10]) DATE: March 3, 2021 PV08 PAGE: SHEET NAME: PLACARD DRAWN BY: SoloCAD MAIN DISTRIBUTION UTILITY DISCONNECT 19763 Idealic Ave, Lakeville MN 55044 FRONT OF HOMEPV ARRAY RAPID SHUTDOWN AC DISCONNECT SWITCH SYSTEM UTILIZES MICROINVERTERS LOCATED UNDER EACH SOLAR MODULE SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701Xcel Energy MNDATE: March 3, 2021 PV09 PAGE: SHEET NAME: SITE PHOTOS DRAWN BY: SoloCAD SITE PHOTOS: SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701Xcel Energy MNDATE: March 3, 2021 PV09.1 PAGE: SHEET NAME: SITE PHOTOS DRAWN BY: SoloCAD SITE PHOTOS: SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701Xcel Energy MNDATE: March 3, 2021 PV09.2 PAGE: SHEET NAME: SITE PHOTOS DRAWN BY: SoloCAD SITE PHOTOS: SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701Xcel Energy MNDATE: March 3, 2021 PV09.3 PAGE: SHEET NAME: SITE PHOTOS DRAWN BY: SoloCAD SITE PHOTOS: SITE INFORMATION: Shawn Vaughan 19763 Idealic Ave, Lakeville, MN 55044 MAX CONTINUOUS AC SYSTEM SIZE: 10.412 kW AC DC SYSTEM SIZE: 12.21 kW DC (37) Silfab SIL-330 NL PV MODULES (19) AP Systems YC600 INVERTERSCONTRACTOR INFORMATION:Everlight Solar ConstructionPO Box 930550Verona, WI 53593License# DCQ-111802116833.786.4387 ext. 701Xcel Energy MNDATE: March 3, 2021 PV10 TEST PROCEDURE PAGE: SHEET NAME: DRAWN BY: SoloCAD Contact Info and General 1.Name of Customer who owns service, the Xcel Energy “customer of record” for existing services 2.Installation premise address shall match application address 2.1 Address shall match the premise address for existing customer/services 3.Application OID, SRC, or case number assigned to the project 4.A note stating “All testing shall be performed by qualified personnel" Testing Applicable to all DER 5.The procedure shall provide steps to verify fixed power factor settings for each inverter meet the project requirements 6.The unintentional islanding test shall at minimum contain the following steps: 6.1 Steps that verify DER system is ready to be energized 6.2 Steps to verify labeling for the Main Service Panel, DER Protection, DC Disconnect, AC disconnect, Utility AC disconnect, Production Meter (when applicable) and other relevant labelling and signage 6.3 Steps to energize the DER system 6.4 While in normal operation, steps to verify the voltages at the DER AC terminals are within 5% of the combined DER AC voltage ratings and all LEDs, alarms, and/or LCD codes are “normal” 6.5 While in normal operation, steps to verify that all DER units are operational and producing power 6.6 Steps to simulate the loss of utility source11 for the unintentional islanding test shall be listed 6.6.1 Clearly identify the disconnection device being used to simulate this utility power outage 6.7 Using a voltmeter, verify the voltage at the inverter side of the AC disconnect has dropped to zero 6.7.1 Only customer-owned equipment shall be used for this verification. Xcel Energy will not provide special equipment for this verification. Xcel Energy provided meters shall not be used for this verification. 6.8 Using an ammeter or the DER’s display/metering, verify the DER has ceased to energize within two seconds. For three phase systems, three phase monitoring may be required. 7.Verify DER LEDs, alarms, and/or LCD codes are appropriate for loss of Utility source 8.Steps to restore the lost Utility source shall be listed 9.A step to verify that the inverter system delays five (5) minutes before resuming power output after the Utility source is restored shall be listed CASE #: 04376108 THESE SHEETS, DESIGNS, AND SPECS ARE PROPERTY OF SUN INCORPORATED. NO PART SHALL BE DUPLICATED OR USED FOR NONE OTHER THAN ITS SPECIFIC PROJECT WITHOUT WRITTEN CONSENT FROM SUN INCORPORATED.MOUNT SHEETSheet: 5File: \\SUN-SERVER\Sun Incorporated Jobs Master\Equipment\MOUNTS\QUICK MOUNT\QMPV-datasheet-QMHSS-LS-QuickHookSM-web.pdfMissing or invalid referenceSheet: 2File: \\SUN-SERVER\Sun Incorporated Jobs Master\Equipment\MOUNTS\QUICK MOUNT\QMPV-datasheet-QMHSS-LS-QuickHookSM-web.pdfMissing or invalid reference