HomeMy WebLinkAboutLA189954 PlansVSE Project Number: U1991.0723.211 April 12, 2021 All Energy Solar ATTENTION: Brian Allen 1264 Energy Lane St Paul, MN 55108 REFERENCE: Darren Residence (33132): 8826 191st Court, Lakeville, MN 55044 Solar Array Installation To Whom It May Concern: Per your request,we have reviewed the existing structure at the above referenced site.The purpose of our review was to determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on the panel layout plan. Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation. Design Parameters Code: 2020 Minnesota Building Code (2018 IBC) Risk Category: II Design wind speed: 109 mph (3-sec gust) per ASCE 7-16 Wind exposure category: C Ground snow load, Pg: 50 psf Existing Roof Structure Roof structure: 2x4 manufactured trusses @ 24" O.C. Roofing material: composite shingles Roof slope: 26° Connection to Roof Mounting connection: (1) 5/16" lag screw w/ min. 2.5" threaded embedment into framing at max. 48" o.c. along rails (2) rails per row of panels, evenly spaced; panel length perpendicular to the rails not to exceed 68 in. Rail cantilever shall not exceed 50% of connection spacing. Conclusions Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation. The gravity loads,and thus the stresses of the structural elements,in the area of the solar array are either decreased or increased by no more than 5%.Therefore,the requirements of Section 806.2 of the 2020 Minnesota Conservation Code for Existing Buildings are met and the structure is permitted to remain unaltered. 651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com VSE Project Number: U1991.0723.211 Darren House Residence 4/12/2021 The solar array will be flush-mounted (no more than 10"above the roof surface)and parallel to the roof surface.Thus,we conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible. The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift), the governing load case.Because the increase in lateral forces is less than 10%,this addition meets the requirements of the exception in Section 806.3 of the 2020 Minnesota Conservation Code for Existing Buildings.Thus the existing lateral force resisting system is permitted to remain unaltered. Limitations Installation of the solar panels must be performed in accordance with manufacturer recommendations.All work performed must be in accordance with accepted industry-wide methods and applicable safety standards.The contractor must notify Vector Structural Engineering,LLC should any damage,deterioration or discrepancies between the as-built condition of the structure and the condition described in this letter be found.Connections to existing roof framing must be staggered,except at array ends,so as not to overload any existing structural member.The use of solar panel support span tables provided by others is allowed only where the building type,site conditions,site-specific design parameters,and solar panel configuration match the description of the span tables.The design of the solar panel racking (mounts,rails,etc.)and electrical engineering is the responsibility of others.Waterproofing around the roof penetrations is the responsibility of others.Vector Structural Engineering assumes no responsibility for improper installation of the solar array. VECTOR STRUCTURAL ENGINEERING, LLC 04/12/2021 _______________________________________________________ Brett Veazie, P.E. Project Engineer Enclosures BDV/anr I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota. Brett Veazie, License No. 56392, Expiration Date: 30-June-2022 04/12/2021 651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com JOB NO.:U1991.0723.211 SUBJECT:WIND PRESSURE PROJECT:Darren House Residence Label:Note: Calculations per ASCE 7-16 SITE-SPECIFIC WIND PARAMETERS: Basic Wind Speed [mph]:109 Notes:Exposure Category:C Risk Category:II Importance Factor, I: ADDITIONAL INPUT & CALCULATIONS: Height of Roof, h [ft]:35 (Approximate) Comp/Cladding Location:Gable Roofs 20° < θ ≤ 27° Enclosure Classification: Zone 1, 2e GCp:1.50 Zone 1, 2e γa:0.78 Zone 2n, 2r, 3e GCp:2.44 Zone 2n, 2r, 3e γa:0.78 Zone 3r GCp:2.86 Zone 3r γa:0.78 γa:0.40 α:9.5 Table 26.11-1 zg [ft]:900 Table 26.11-1 Kh:1.01 Table 26.10-1 Ke:0.96 Table 26.9-1 Kzt:1 Equation 26.8-1 Kd:0.85 Table 26.6-1 Velocity Pressure, qh [psf]:25.2 Equation 26.10-1 γE:1.50 Section 29.4.4 γC:0.94 Section 29.4.4 γP:1.20 Section 29.4.4 p = q h (GC p )(γ E )(γ a ) p = q h (GC rn ), (GC rn ) = (γ p )(γ c )(γ E )(GC rn )nom Zone 1, 2e, p [psf]:44.2 psf (1.0 W) Zone 2n, 2r, 3e, p [psf]:71.8 psf (1.0 W) Zone 3r, p [psf]:84.1 psf (1.0 W) (a =3 ft) Fig. 29.4-8 WIND PRESSURES:Equation 29.4-7 Solar Panel Array Enclosed Buildings Figure 30.3-2C (negative coeff.) Components and Cladding Wind Calculations JOB NO.:U1991.0723.211 SUBJECT:CONNECTION PROJECT:Darren House Residence Calculate Uplift Forces on Connection Pressure (0.6 Dead -0.6 Wind) (psf) Max Connection Spacing1 (ft) Max Trib. Area2 (ft2) Max Uplift Force (lbs) Zone 1, 2e 24.8 4.0 11.3 282 Zone 2n, 2r, 3e 41.4 4.0 11.3 470 Zone 3r 48.8 4.0 11.3 553 Calculate Connection Capacity Lag Screw Size [in]:5/16 Cd:1.6 NDS Table 2.3.2 Embedment3 [in]:2.5 Grade: Nominal Capacity [lbs/in]:205 NDS Table 12.2A Number of Screws:1 Prying Coefficient:1.4 Total Capacity [lbs]:586 Determine Result Maximum Demand [lbs]:553 Lag Screw Capacity [lbs]:586 Result:Capacity > Demand, Connection is adequate. Notes 1. 'Max Connection Spacing' is the spacing between connections along the rails. 3. Embedment is measured from the top of the framing member to the beginning of the tapered tip of the lag screw. Embedment in sheathing or other material is not effective. The length of the tapered tip is not part of the embedment length. 2. 'Max Trib Area' is the product of the 'Max Connection Spacing' and 1/2 the panel width/height perpendicular to the rails. (2) rails per row of panels. Length of panels perpendicular to the rails shall not exceed 68". SPF (G = 0.42) VECTOR STRUCTURAL ENGINEERS JOB NO.:U1991.0723.211 SUBJECT:GRAVITY LOADS PROJECT:Darren House Residence GRAVITY LOADS Roof Pitch: 5.9 :12 ROOF DEAD LOAD (D) Increase due to pitch Material weight [psf] Composite Shingles 1.11 2.0 1/2" Plywood 1.11 1.0 Framing 1.00 3.0 Insulation 1.00 0.5 1/2" Gypsum Clg.1.11 2.0 M, E & Misc 1.00 1.5 Total Existing Roof DL PV Array DL 1.11 3 DL:1.11 ROOF LIVE LOAD (Lr) Existing Design Roof Live Load [psf]20 ASCE 7-16 Table 4.3-1 Roof Live Load With PV Array [psf]0 SNOW LOAD (S):w/ Solar Array Roof Slope [x:12]:5.9 Roof Slope [°]:26 Ground Snow Load, pg [psf]:50 ASCE 7-16, Section 7.2 Terrain Category:C ASCE 7-16, Table 7.3-1 Exposure of Roof:Fully Exposed ASCE 7-16, Table 7.3-1 Exposure Factor, Ce:0.9 ASCE 7-16, Table 7.3-1 Thermal Factor, Ct:1.1 ASCE 7-16, Table 7.3-2 Risk Category:II ASCE 7-16, Table 1.5-1 Importance Factor, Is:1.0 ASCE 7-16, Table 1.5-2 Flat Roof Snow Load, pf [psf]:35 ASCE 7-16, Equation 7.3-1 Minimum Roof Snow Load, pm [psf]:0 ASCE 7-16, Section 7.3.4 Unobstructed Slippery Surface?No ASCE 7-16, Section 7.4 Slope Factor Figure:Figure 7-2b ASCE 7-16, Section 7.4 Roof Slope Factor, Cs:1.00 ASCE 7-16, Figure 7.4-1 Sloped Roof Snow Load, ps [psf]:35 ASCE 7-16, Equation 7.4-1 Design Snow Load, S [psf]:3535 5.9 26 50 C Fully Exposed 0.9 1.1 II 1.0 35 0 No Figure 7-2b 1.00 35 Design material weight [psf] 2.2 1.1 3.0 0.5 2.2 1.5 10.6 3.1 #VALUE! 2020 MBC, Section 1607.13.5 Existing JOB NO.:U1991.0723.211 SUBJECT:LOAD COMPARISON PROJECT:Darren House Residence Summary of Loads Existing With PV Array D [psf]11 14 Lr [psf]20 0 S [psf]35 35 Maximum Gravity Loads: Existing With PV Array (D + Lr) / Cd [psf]24 15 ASCE 7-16, Section 2.4.1 (D + S) / Cd [psf]39 42 ASCE 7-16, Section 2.4.1 Maximum Gravity Load [psf]:39 42 Maximum Member Forces: GEOMETRY Span(ft)46.5 (Approximate) Solar Panel Array Start, a (ft)0.0 (Approximate) Solar Panel Array Length, b (ft)20.5 (Approximate) Framing Spacing (ft)2.0 MEMBER FORCES Existing With PV Array Vertical Reaction, V1 (lbs)1828 1913 OK Vertical Reaction, V2 (lbs)1828 1852 OK Existing With PV Array Moment @ Center, M (lbs-ft)21253 21811 OK Ratio The gravity loads, and thus the stresses of the structural elements, in the area of the solar array are either decreased or increased by no more than 5%. Therefore, the requirements of Section 806.2 of the 2020 Minnesota Conservation Code for Existing Buildings are met and the structure is permitted to remain unaltered. (Cd = Load Duration Factor = 0.9 for D, 1.15 for S, and 1.25 for Lr) Ratio 103% 105% 101% VECTOR STRUCTURAL ENGINEERS JOB NO.:U1991.0723.211 SUBJECT:SOLAR LAYOUT PROJECT:Darren House Residence 1 2 3 4 5 67 <10'ARRAY 1 COMPANY INFORMATION CLIENT INFORMATION SYSTEM DETAILS PROJECT-PAGE TITLE ALL ENERGY SOLAR, INC 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 INFO@ALLENERGYSOLAR.COM PAGE NUMBER A0 REVISIONS LAST: 04/8/21 BX AZIMUTH NOTES: 1. (29) ENPHASE IQ7PLUS INVERTER(S) 2. ARRAY 1: 26° TILT, 180° AZIMUTH 3. ARRAY 2: (Array 2 Tilt)° TILT, (Array 2 Azimuth)° AZIMUTH 6. ARRAY 3: (Array 3 Tilt)° TILT, (Array 3 Azimuth)° AZIMUTH 7. ARRAY 4: (Array 4 Tilt)° TILT, (Array 4 Azimuth)° AZIMUTH COVER PAGE DARREN HOUSE 8826 191ST CT LAKEVILLE, MN 55044 PO 33132 N 191ST CT ARRAY 1 REC 365 BOB 29 Flush Roof Mount 10.585 Panel Type # of Panels System Size (kW) COMPANY INFORMATION CLIENT INFORMATION SYSTEM DETAILS PROJECT-PAGE TITLE ALL ENERGY SOLAR, INC 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 INFO@ALLENERGYSOLAR.COM PAGE NUMBER A1 REVISIONS LAST: 04/8/21 BX AZIMUTH ACCOUNT: 200010034220 PREMISE: METER: 1ND89990969 PROPERTY MAP N DARREN HOUSE 8826 191ST CT LAKEVILLE, MN 55044 PO 33132 NOTES: 1. (29) ENPHASE IQ7PLUS INVERTER(S) = 8.41kW AC 2. ARRAY 1: 180° AZIMUTH, 26° TILT (29) REC 365W = 10.585kW 3. ARRAY 2: (Array 2 Azimuth)° AZIMUTH, (Array 2 Tilt)° TILT ((Array 2 Panel Qty)) REC 365W = (Array 2 kW)kW 4. ARRAY 3: (Array 3 Azimuth)° AZIMUTH, (Array 3 Tilt)° TILT ((Array 3 Panel Qty)) REC 365W = (Array 3 kW)kW 5. ARRAY 4: (Array 4 Azimuth)° AZIMUTH, (Array 4 Tilt)° TILT ((Array 4 Panel Qty)) REC 365W = (Array 4 kW)kW ARRAY 1 191ST CT BOS SOLAR MODULES COVER ~15% OF ROOF PLAN FIRE CODE ACCESS PATHWAYS COMPANY INFORMATION CLIENT INFORMATION SYSTEM DETAILS PROJECT-PAGE TITLE ALL ENERGY SOLAR, INC 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 INFO@ALLENERGYSOLAR.COM PAGE NUMBER A2 REVISIONS LAST: 04/8/21 BX NOTES: 1. ELEVATIONS MAY VARY DEPENDING ON GROUND ELEVATION BUT ARE DRAWN TO THE BEST OF OUR ABILITY 2. 2x4 TRUSS 24" OC ELEVATION DRAWINGS DARREN HOUSE 8826 191ST CT LAKEVILLE, MN 55044 PO 33132 SETBACKS: 18" FROM RIDGE 18" FROM BOTH SIDES OF VALLEY 36" FROM EDGE SOUTH ELEVATION WEST ELEVATION 38'-10"37'-6"27'-7"27'-0" COMPANY INFORMATION CLIENT INFORMATION SYSTEM DETAILS PROJECT-PAGE TITLE ALL ENERGY SOLAR, INC 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 INFO@ALLENERGYSOLAR.COM PAGE NUMBER A3 REVISIONS LAST: 04/8/21 BX *STRINGING TO BE DETERMINED ON SITE 2x4 TRUSS 24" OC RAIL AND STRINGING DIAGRAM AZIMUTH <aCustName(s)> <aCustAddress1> <aCustAddress2> <aCustAddress3> PO <aCustPONumber> N DARREN HOUSE 8826 191ST CT LAKEVILLE, MN 55044 PO 33132 (29) REC REC365AA MODULES (29) ENPHASE IQ7PLUS INVERTER(S) CIRCUITS: (2) CIRCUIT(S) OF 8 MICROS (1) CIRCUIT(S) OF 13 MICROS ((Qty of circuits with the number of inverters optimizers above)) CIRCUIT(S) OF (Qty of inverters/optimizers in a circuit/string) MICROS ((Qty of circuits with the number of inverters optimizers above)) CIRCUIT(S) OF (Qty of inverters/optimizers in a circuit/string) MICROS ((Qty of circuits with the number of inverters optimizers above)) CIRCUIT(S) OF (Qty of inverters/optimizers in a circuit/string) MICROS SNAP-N-RACK MOUNTING HARDWARE: 1. (59) L-FEET 2. (8) RAIL SPLICES 3. CLAMPS (50) MIDCLAMPS (16) ENDCLAMPS 4. RAIL LENGTHS: (15) 168" RAILS MAX CIRCUIT LENGTH (120/240V) 15A BREAKER 20A BREAKER ENPHASE IQ7 12 16 ENPHASE IQ7+9 13 ENPHASE IQ7X 9 12 ENPHASE IQ7A 8 11 44" 8"323" 273" 18" 36" COMPANY INFORMATION CLIENT INFORMATION SYSTEM DETAILS PROJECT-PAGE TITLE ALL ENERGY SOLAR, INC 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 INFO@ALLENERGYSOLAR.COM PAGE NUMBER A4 REVISIONS LAST: 04/8/21 BX AZIMUTH ACCOUNT: 200010034220 PREMISE: METER: 1ND89990969 SITE MAP N DARREN HOUSE 8826 191ST CT LAKEVILLE, MN 55044 PO 33132 NOTES: 1. (29) ENPHASE IQ7PLUS INVERTER(S) = 8.41kW AC 2. ARRAY 1: 180° AZIMUTH, 26° TILT (29) REC 365W = 10.585kW 3. ARRAY 2: (Array 2 Azimuth)° AZIMUTH, (Array 2 Tilt)° TILT ((Array 2 Panel Qty)) REC 365W = (Array 2 kW)kW 4. ARRAY 3: (Array 3 Azimuth)° AZIMUTH, (Array 3 Tilt)° TILT ((Array 3 Panel Qty)) REC 365W = (Array 3 kW)kW 5. ARRAY 4: (Array 4 Azimuth)° AZIMUTH, (Array 4 Tilt)° TILT ((Array 4 Panel Qty)) REC 365W = (Array 4 kW)kW NOTES: 1. LOCATION OF SERVICE PANEL AND ELECTRICAL EQUIPMENT ARE SHOWN. FINAL LOCATION MAY CHANGE 2. LOCATION OF SERVICE PANEL AND ADDITIONAL ELECTRICAL EQUIPMENT NOT DRAWN TO SCALE 3. PV INTERCONNECTION IS A SECONDARY INTERCONNECTION 4. AC DISCONNECT AND PRODUCTION METER IN READILY ACCESSIBLE LOCATION WITHIN 10' OF MAIN SERVICE METER/BI-DIRECTIONAL METER. 24/7 UNESCORTED KEYLESS ACCESS TO BE PROVIDED FOR UTILITY AC DISCONNECT, PV PRODUCTION METER, & BI-DIRECTIONAL METER. 5. PV EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH NEC 690 AND POSTED WITH APPLICABLE WARNINGS, SIGNAGE, AND PLAQUES PER NEC 705-10, 690-17, & 690-64 (b)(5). 6. CIRCUITS: (2) CIRCUIT(S) OF 8 (15AMPS EACH) (1) CIRCUIT(S) OF 13 (20AMPS EACH) ((Qty of circuits with the number of inverters optimizers above)) CIRCUIT(S) OF (Qty of inverters/optimizers in a circuit/string) ([Amps] (If Enphase. Based on 15 or 20A breakers)AMPS EACH) ((Qty of circuits with the number of inverters optimizers above)) CIRCUIT(S) OF (Qty of inverters/optimizers in a circuit/string) ([Amps] (If Enphase. Based on 15 or 20A breakers)AMPS EACH) ((Qty of circuits with the number of inverters optimizers above)) CIRCUIT(S) OF (Qty of inverters/optimizers in a circuit/string) ([Amps] (If Enphase. Based on 15 or 20A breakers)AMPS EACH) 1 2 3 4 5 6 CALL-OUTS: 1: SOLAR PANELS 2: INVERTERS 3: ENPHASE IQ COMBINER PANEL 4: UTILITY FUSED AC DISCONNECT 5: PV PRODUCTION METER 6: BI-DIRECTIONAL METER 7: MAIN ELECTRIC SERVICE DISTANCES SOLAR PANELS - INVERTERS: 5' MAX INVERTERS - IQ COMBINER PANEL: 75' MAX IQ COMBINER PANEL - UTILITY FUSED AC DISCONNECT: 2' UTILITY FUSED AC DISCONNECT - PV PRODUCTION METER: 2' PV PRODUCTION METER - BI-DIRECTIONAL METER: 2' BI-DIRECTIONAL METER - MAIN ELECTRIC SERVICE: 2' LABELS LOCATED ON PV PRODUCTION METER, BI- DIRECTIONAL METER, AC DISCONNECT(S), INVERTER(S), AND APPROPRIATE LABELS ON MAIN ELECTRIC SERVICE. ALL LABELS ARE PERMANENT, WEATHERPROOF, AND DURABLE THERE ARE NO CLEARANCE ISSUES DUE TO OVERHEAD POWERLINES. 7 <10'425' HUXLEY AVE 191ST CT ARRAY 1 α experience performance 375 wp Power rec Alphα black Series ELIGIBLE FOR www.recgroup.com 28 [1.1] 1721±2.5 [67.75 ±0.1] 802 [31.5]455 [17.9]975±2.5 [38.4±0.1]1016±2.5 [40 ±0.1]17 [0.7]45 [1.5] 1000 [39] 1200 [47] Scale: 1:1.57 11±0.2 [0.43 ±0.8]6.6±0.2 [0.26 ±0.08]20.5±0.5 [0.78 ±0.08] 30 [1.18] 22.5 [0.9] 621 ±3 [24.5 ±0.12] GR GR GR Ref: PM-DS-12-02-Rev- D2 07.20Specifications subject to change without notice.CERTIFICATIONS WARRANTY LOW LIGHT BEHAVIOUR TEMPERATURE RATINGS* MAXIMUM RATINGS Measurements in mm [in] 100 200 300 400 500 600 700 800 900 1000 85 90 95 100 105 Irradiance (W/m²) Typical low irradiance performance of module at STC:Rel. Efficiency (%)Nominal Module Operating Temperature:44°C (±2°C) Temperature coefficient of PMAX:-0.26 %/°C Temperature coefficient of VOC:-0.24 %/°C Temperature coefficient of ISC:0.04 %/°C *The temperature coefficients stated are linear values Operational temperature:-40 ... +85°C Maximum system voltage:1000 V Design load (+): snow Maximum test load (+): 4666 Pa (97.5 lbs/sq ft)+ 7000 Pa (146 lbs/sq ft)* Design load (-): wind Maximum test load (-): 2666 Pa (55.6 lbs/sq ft)+ 4000 Pa (83.5 lbs/sq ft)* Max series fuse rating:25 A Max reverse current:25 A + Calculated using a safety factor of 1.5 * See installation manual for mounting instructions IEC 61215:2016, IEC 61730:2016, UL 1703, UL 61730 IEC 62804 PID IEC 61701 Salt Mist IEC 62716 Ammonia Resistance UL 1703 Fire Type Class 2 IEC 62782 Dynamic Mechanical Load IEC 61215-2:2016 Hailstone (35mm) AS4040.2 NCC 2016 Cyclic Wind Load ISO 14001:2004, ISO 9001:2015, OHSAS 18001:2007, IEC 62941 Standard REC ProTrust Installed by an REC Certified Solar Professional No Yes Yes System Size All ≤25 kW 25-500 kW Product Warranty (yrs)20 25 25 Power Warranty (yrs)25 25 25 Labor Warranty (yrs)0 25 10 Power in Year 1 98%98%98% Annual Degradation 0.25%0.25%0.25% Power in Year 25 92%92%92% See warranty documents for details. Conditions apply. ELECTRICAL DATA Product Code*: RECxxxAA Black Power Output - PMAX (Wp) 355 360 365 370 375 Watt Class Sorting - (W)-0/+5 -0/+5 -0/+5 -0/+5 -0/+5 Nominal Power Voltage - VMPP (V) 36.4 36.7 37.1 37.4 37.8 Nominal Power Current - IMPP (A) 9.77 9.82 9.85 9.9 9.94 Open Circuit Voltage - VOC (V) 43.6 43.9 44.0 44.1 44.2 Short Circuit Current - ISC (A) 10.47 10.49 10.52 10.55 10.58 Power Density (W/sq ft)18.88 19.15 19.41 19.68 19.94 Panel Efficiency (%) 20.3 20.6 20.9 21.2 21.4 Power Output - PMAX (Wp)271 274 278 282 286 Nominal Power Voltage - VMPP (V) 34.3 34.6 35.0 35.2 35.6 Nominal Power Current - IMPP (A) 7.89 7.93 7.96 8.00 8.03 Open Circuit Voltage - VOC (V) 41.1 41.4 41.5 41.6 41.6 Short Circuit Current - ISC (A) 8.46 8.47 8.50 8.52 8.55 Values at standard test conditions (STC: air mass AM 1.5, irradiance 10.75 W/sq ft (1000 W/m²), temperature 77°F (25°C), based on a production spread with a tolerance of PMAX, VOC & ISC ±3% within one watt class. Nominal module operating temperature (NMOT: air mass AM 1.5, irradiance 800 W/m², temperature 68°F (20°C), windspeed 3.3 ft/s (1 m/s). * Where xxx indicates the nominal power class (PMAX) at STC above. GENERAL DATA Cell type: 120 half-cut cells with REC heterojunction cell technology 6 strings of 20 cells in series Glass:0.13 in (3.2 mm) solar glass with anti-reflection surface treatment Backsheet:Highly resistant polymeric construction (black) Frame:Anodized aluminum (black) Junction box:3-part, 3 bypass diodes, IP67 rated in accordance with IEC 62790 Connectors:Stäubli MC4 PV-KBT4/KST4, 12 AWG (4 mm²) in accordance with IEC 62852 IP68 only when connected Cable:12 AWG (4 mm²) PV wire, 39 + 47 in (1 + 1.2 m)in accordance with EN 50618 Dimensions:67.8 x 40 x 1.2 in (1721 x 1016 x 30 mm) 18.8 sq ft (1.75 m²) Weight:43 lbs (19.5 kg) Origin:Made in Singapore STC NMOTREC ALPHα BLACK SERIESPRODUCT DATASHEET REC Group is an international pioneering solar energy company dedicated to empowering consumers with clean, affordable solar power in order to facilitate global energy transitions. Committed to quality and innovation, REC offers photovoltaic modules with leading high quality, backed by an exceptional low warranty claims rate of less than 100ppm. Founded in Norway in 1996, REC employs 2,000 people and has an annual solar panel capacity of 1.8 GW. With over 10 GW installed worldwide, REC is empowering more than 16 million people with clean solar energy. REC Group is a Bluestar Elkem company with headquarters in Norway, operational headquarters in Singapore, and regional bases in North America, Europe, and Asia-Pacific. snapnrack.com Ultra Rail Industry leading Wire Management Solutions Single Tool Installation Mounts available for all roof types All SnapNrack Module Clamps & Accessories are compatible with both raiil profi les Start Installing Ultra Rail Today UR-40 UR-60 The Ultimate Value in Rooftop Solar Solar Mounting Solutions © 2016 by SnapNrack Solar Mounting Solutions. All rights reserved 877-732-2860 www.snapnrack.com contact@snapnrack.com SnapNrack_Ultra Rail Sales Brochure_v.1.4 SnapNrack Solar Mounting Solutions are engineered to optimize material use and labor resources and improve overall installation quality and safety. Quality. Innovative. Superior. Unparalleled Wire Management • Open rail channel provides room for running wires resulting in a long-lasting quality install • Industry best wire management o ering includes Junction Boxes, Universal Wire Clamps, MLPE Attachment Kits, and Conduit Clamps • System is fully bonded and listed to UL 2703 Standard © 2019 by SnapNrack Solar Mounting Solutions. All rights reserved 877-732-2860 www.snapnrack.com contact@snapnrack.com SnapNrack Ultra Rail System A sleek, straightforward rail solution for mounting solar modules on all roof types. Ultra Rail features two rail profi les; UR-40 is a lightweight rail profi le that is suitable for most geographic regions and maintains all the great features of SnapNrack rail, while UR-60 is a heavier duty rail profi le that provides a larger rail channel and increased span capabilities. Both are compatible with all existing mounts, module clamps, and accessories for ease of install. The Entire System is a Snap to Install • New Ultra Rail Mounts include snap-in brackets for attaching rail • Compatible with all the SnapNrack Mid Clamps and End Clamps customers love • Universal End Clamps and snap-in End Caps provide a clean look to the array edge Heavy Duty UR-60 Rail • UR-60 rail profi le provides increased span capabilities for high wind speeds and snow loads • Taller, stronger rail profi le includes profi le- specifi c rail splice and end cap • All existing mounts, module clamps, and accessories are retained for the same great install experience SnapNrack Umbrella Sealing Technology • Innovative Flashing Elevates Protection. New fl ashing uses a fully formed raised cone to prevent any potential water from getting into penetration. Feel secure as the fl ashing is one piece and doesn’t rely on multiple parts sealing together. • Mechanical Design Creates a Lifelong Seal. Patented Umbrella technology utilizes unique Umbrella Washer to seal lag bolt, L Foot, and fl ashing and prevent any potential roof leaks. Technology passes UL 2582 Wind Driven Rain Test without a rubber seal, however rubber gasket is included for extra peace of mind. • Single Fastener Eliminates Extra Steps. Utilize one lag bolt with Umbrella Washer to secure the entire mount assembly and fl ashing. No longer necessary to attach a base, then a fl ashing, then a mount as all are secured in one step. • Single Tool Installation. SnapNrack was the fi rst in the industry to develop a complete system that only requires a single tool. That tradition is continued as a ½” socket is still the only tool necessary to secure the mount as well as all other parts of the system. snapnrack.com Featuring New Innovative Flashing Smaller 9”x12” size allows for easier insertion under shingles Alignment markers make it easy to locate pilot holes Rounded corners make for easier insertion & eliminate corner points from folding up Note: Flashing shown in yellow for illustration purposes only. © 2018 by SnapNrack Solar Mounting Solutions. All rights reserved 877-732-2860 www.snapnrack.com contact@snapnrack.com snapnrack.com Ultra Rail, UR-40 Rail System Spans Wind (mph) 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 190 Snow (psf)0 5 10 15 20 25 30 35 40 45 50 60 70 80 90 100 110 120 System Span Key 6 ft Spans 4 ft Spans 2 ft Spans This table was prepared in compliance with applicable engineering codes and standards. Values are based on the following: • ASCE 7-10 • Chapter 30 Wind Loads & Chapter 7 Snow Loads • Roof Slope: 7 - 27 deg • Roof Height: 0 - 30 ft • Exposure: B • Roof Zone: 1 • Module Orientation: Portrait • Module Type: 60 Cell Modules • Roof Type: Comp Industry Leading Spans for a Light Rail Solution Visit SnapNrack.com for detailed span tables and certifi cations. Certifi cations SnapNrack Ultra Rail system has been evaluated by Underwriters Laboratories (UL) and Listed to UL/ANSI Standard 2703 for Mechanical Loading and Fire. Additionally it is listed to UL 2582 for wind-driven rain. Raised Cone Flashing Single Lag Secures Mount to Roof Pre-assembled Ultra Rail L Foot & Clamp Pre-assembled Ultra Rail