HomeMy WebLinkAboutApproved solar plan 9997 173rd st1.1.1PROJECT NOTES:1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THENATIONAL ELECTRIC CODE (NEC) ARTICLE 690, ALLMANUFACTURERS’S LISTING AND INSTALLATION INSTRUCTIONS, ANDTHE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVINGJURISDICTION’S (AHJ) APPLICABLE CODES.1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVEDAND PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION1.1.4 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE ISINTEGRATED WITH THE MICROINVERTER IN ACCORDANCE WITH NEC690.41(B)1.1.5 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVEINVERTERS, AND SOURCE CIRCUIT COMBINER BOXES AREIDENTIFIED AND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS ASREQUIRED BY NEC 690.4: PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS CFIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY1.1.6 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDEDTEMP COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGECALCULATED ACCORDING TO NEC 690.7.1.1.7 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS,AND SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN APHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTEDFOR THE APPLICATION PER 690.4 (D). SHALL BE INSTALLEDACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING[NEC 110.3].1.1.8 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDINGCODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALLPLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THENEC AND AHJ.1.2.1 SCOPE OF WORK:1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN ANDSPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEMRETROFIT. PRIME CONTRACTOR WILL BE RESPONSIBLE FORCOLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN, SPECIFY,AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THEPHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.1.3.1 WORK INCLUDES:1.3.2 PV ROOF ATTACHMENTS - UNIRAC FLAT FLASHING1.3.3 PV RACKING SYSTEM INSTALLATION - UNIRAC LIGHT1.3.4 PV MODULE AND INVERTER INSTALLATION - TRINA SOLAR TSM-320DD06H.05(II) / ENPHASE IQ7PLUS-72-2-US1.3.5 PV EQUIPMENT GROUNDING1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX1.3.7 PV LOAD CENTERS (IF INCLUDED)1.3.8 PV METERING/MONITORING (IF INCLUDED)1.3.9 PV DISCONNECTS1.3.10 PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.3.11 PV FINAL COMMISSIONING1.3.12 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV1.3.13 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODEGENERAL NOTESSCOPE OF WORKSYSTEM SIZE: STC: 25 X 320W = 8.000KWPTC: 25 X 297.8W = 7.445KW DC(25) TRINA SOLAR TSM-320DD06H.05(II)(25) ENPHASE IQ7PLUS-72-2-USATTACHMENT TYPE: UNIRAC FLAT FLASHINGMSP UPGRADE: NOOWNERNAME:DANIEL ZIENTARAPROJECT MANAGERNAME:KEVIN VICKERSPHONE: (763) 412-5714CONTRACTORNAME:GOLDEN ELECTRICPHONE: (763) 412-5714AUTHORITIES HAVING JURISDICTIONBUILDING: CITY OF LAKEVILLEZONING: CITY OF LAKEVILLEUTILITY: DAKOTA ELECTRIC ASSOCIATIONDESIGN SPECIFICATIONSOCCUPANCY: IICONSTRUCTION: SINGLE-FAMILYZONING:RESIDENTIALGROUND SNOW LOAD: 50 PSFWIND EXPOSURE: BWIND SPEED: 115 MPHAPPLICABLE CODES & STANDARDSBUILDING: MSBC 2020, MSRC 2020ELECTRICAL: NEC 2017FIRE:MSFC 2020PROJECT INFORMATIONNEW PV SYSTEM: 8.000 kWpZIENTARA RESIDENCE9997 173RD STREET WESTLAKEVILLE, MN 55044ASSESSOR'S #: 221320201160BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160T-001.00COVER PAGE(SHEET 1)01AERIAL PHOTONOT TO SCALENEWS02PLAT MAPNOT TO SCALESHEET LIST TABLESHEET NUMBERSHEET TITLET-001COVER PAGEG-001NOTESA-101SITE PLANA-102ELECTRICAL PLANA-103SOLAR ATTACHMENT PLANE-601LINE DIAGRAME-602DESIGN TABLESE-603PLACARDSE-604PLACARDSS-501ASSEMBLY DETAILSR-001RESOURCE DOCUMENTR-002RESOURCE DOCUMENTR-003RESOURCE DOCUMENTR-004RESOURCE DOCUMENTR-005RESOURCE DOCUMENT173RD STREET WEST CEC2019M 2.1.1SITE NOTES:2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHAREGULATIONS.2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM ISA UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING,MECHANICAL, OR BUILDING ROOF VENTS.2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING ANDPROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC110.26.2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED INACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'SINSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THEBUILDING OR STRUCTURE.2.2.1EQUIPMENT LOCATIONS:2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC110.26.2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOREXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C)AND NEC TABLES 310.15 (B)(2)(A) AND 310.15 (B)(3)(C).2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULESACCORDING TO NEC 690.34.2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTERIS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT.2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNELACCORDING TO NEC APPLICABLE CODES.2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOROUTDOOR USAGE WHEN APPROPRIATE.2.3.1STRUCTURAL NOTES:2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TOCODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE ADESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND AMINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY,ACCORDING TO RAI MANUFACTURER’S INSTRUCTIONS.2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS.IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCALREQUIREMENTS.2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED ANDSEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY A LICENSEDCONTRACTOR.2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THESPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BESTAGGERED AMONGST THE ROOF FRAMING MEMBERS.2.4.1WIRING & CONDUIT NOTES:2.4.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODEREQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.2.4.3 CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.2.4.4 VOLTAGE DROP LIMITED TO 1.5%.2.4.5 DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRINGSYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLEWIRING CLIPS.2.4.6 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GREYIN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGETO BE MARKED ORANGE [NEC 110.15].4.5.1GROUNDING NOTES:2.5.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FORSUCH USE.2.5.3 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 ANDMINIMUM NEC TABLE 250.122.2.5.4 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).2.5.5 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC690.45 AND MICROINVERTER MANUFACTORERS’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“LINE SIDE” (TYPICALLY THE UPPER TERMINALS).2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BELOCKABLE, AND BE A VISIBLE-BREAK SWITCH2.6.4 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE ARAPID SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCYRESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D).2.6.5 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9,AND 240.2.6.6 MICROINVERTER BRANCHES CONNECTED TO A SINGLE BREAKER ORGROUPED FUSES IN ACCORDANCE WITH NEC 110.3(B).2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTIONACCORDING TO NEC 690.11 AND UL1699B.2.7.1INTERCONNECTION NOTES:2.7.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12(B)]2.7.3 THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS OUTPUT MAYNOT EXCEED 120% OF BUSBAR RATING [NEC 705.12(D)(2)(3)].2.7.4 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUITCURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THEBUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THEBUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE LOCATED OPPOSITEEND OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(2)(3)].2.7.5 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTALRATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OFBUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BEEXCLUDED ACCORDING TO NEC 705.12 (B)(2)(3)(C).2.7.6 FEEDER TAP INTERCONECTION (LOAD SIDE) ACCORDING TO NEC 705.12(B)(2)(1)2.7.7 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.12 (A) WITHSERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230.422.7.8 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPTFROM ADDITIONAL FASTENING [NEC 705.12 (B)(5)].BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160G-001.00NOTES(SHEET 2) GENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGE3. NO SPECIAL ACCESS INSTRUCTIONSPROPERTY LINEBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160A-101.00(SHEET 3)AREA OF WORKENTRANCESITE PLAN01/24" = 1'-0"SITE PLAN0112' 24'173RD STREET WESTNEWSMETERAC DISCONNECTAC COMBINER BOX19'-0"39'-7"14'-3"53'-3" MODULE:TRINA SOLARTSM-320DD06H.05(II)320 WATTS39.06''65.94''GENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGE3. NO SPECIAL ACCESS INSTRUCTIONSMODULE STRINGINGMODULE STRINGINGBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160A-102.00(SHEET 4)A(N) (1) JUNCTION BOXEXTERIOR PV EQUIPMENTBELECTRICAL PLANINTERIOR PV EQUIPMENT01/8" = 1'ELECTRICAL PLAN014' 8'ARRAY 3 - 1.280 kW[x4] (N) MODULESTILT: 25 DEGREESROOF PITCH: 5:12AZIMUTH: 270 DEGREESNEWS(E) (1) METER(N) (1) AC DISCONNECT(E) (1) MAIN ELECTRICAL PANEL(N) (1) AC COMBINER BOXARRAY 4 - 2.240 KW[X7] (N) MODULESTILT: 25 DEGREESROOF PITCH: 5:12AZIMUTH: 270 DEGREESARRAY 2 - 1.920 kW[x6] (N) MODULESTILT: 25 DEGREESROOF PITCH: 5:12AZIMUTH: 180 DEGREESARRAY 1 - 2.560 kW[x8] (N) MODULESTILT: 25 DEGREESROOF PITCH: 5:12AZIMUTH: 180 DEGREESAAAAAAAABBBBBBBBBBBAABAAA GENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGEROOF TRUSSESMODULE:TRINA SOLARTSM-320DD06H.05(II)320 WATTS39.06''65.94''BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160NEWS01/8" = 1'SOLAR ATTACHMENT PLAN014' 8'FLUSH MOUNT SOLAR MODULESATTACHED TO ROOF SURFACE (SEESHEET S-501 FOR MOUNTING DETAILS)ROOF MATERIAL IS ASPHALT SHINGLEA-103.00(SHEET 5)SOLAR ATTACHMENT PLAN22'-1"13'-1"16'-6"16'-6" AMODULE STRINGINGGTO (E)LOADSKWHR(E) GROUNDINGELECTRODEGROUNDROD (N)MAIN75A[x1] METER240/120V, 1 PHASE, 3WMAIN SERVICE PANEL240/120 V 1Ø, 3WMAIN BUSS: 100AGSW160A0310' MAX 0.75" EMT(2) #8 THWN(1) #8 GROUND[x1] JUNCTION BOX[x25] SOLAR MODULESMAKE: TRINA SOLARMODEL: TSM-320DD06H.05(II)[x25] MICROINVERTERSMAKE: ENPHASEMODEL: IQ7PLUS-72-2-USMAX BREAKER SIZE:(100A x 1.2 ) - 75 A = 45 A90' MAX 0.75" EMT(4) #10 THWN(2) #6 GROUND! WARNING !DUAL POWER SOURCES.SECOND SOURCE IS PV SYSTEMPHOTOVOLTAICAC DISCONNECTOPERATING CURRENT: 30.25 A ACOPERATING VOLTAGE: 240 V AC! WARNING !ELECTRIC SHOCK HAZARDTERMINALS ON THE LINE AND LOAD SIDES MAYBE ENERGIZED IN THE OPEN POSITION.DC VOLTAGE IS ALWAYS PRESENT WHENSOLAR MODULES ARE EXPLOSED TO SUNLIGHT! CAUTION !PHOTOVOLTAIC SYSTEMCIRCUIT IS BACKFEDINTERACTIVE PHOTOVOLTAIC SYSTEMCONNECTEDRAPID SHUTDOWN SWITCHFOR SOLAR PV SYSTEMINTERACTIVE PHOTOVOLTAIC SYSTEMCONNECTEDPHOTOVOLTAIC SYSTEM DISCONNECT LOCATEDEAST SIDE OF THE HOUSESOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAYSOLAR ELECTRICPV PANELSUTILITYAC DISCONNECTWARNING: PHOTOVOLTAICPOWER SOURCEPV PRODUCTIONMETER! WARNING !ELECTRIC SHOCK HAZARDIF A GROUND FAULT IS INDICATED, NORMALLYGROUNDED CONDUCTORS MAY BEUNGROUNDED AND ENERGIZED.! WARNING !INVERTER OUTPUT CONNECTION.DO NOT RELOCATE THISOVERCURRENT DEVICELOAD CENTER CONTAINS ONLYGENERATION CIRCUITS, AND NOUNUSED POSITIONS OR LOADS[x1] UTILITY AC DISCONNECT240/120V, 60A, 1 PHASE, 3WVISIBLE-OPEN TYPE, LOCKABLE, READILYACCESSIBLEMAKE: SQUARE DMODEL: D222RB(REFERENCE POINT OF APPLICABILITY)TEST AND VERIFICATION FEATURESCONDUCTED HERE PER TEST PROCEDURETO UTILITYGRID (UG)0210' MAX 0.75" EMT(2) #8 THWN(1) #8 GROUNDGCB120A[X1] AC COMBINER BOXMAKE: ENPHASEMODEL: IQ COMBINER 3240/120V, 125A, 1 PHASE, 3WCB220A1. PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN DISCONNECTPER NEC 690.132. SYSTEM COMPLIANT WITH ALL CURRENT NEC CODESIN BRANCH13AIN BRANCH12B01CB310AENPHASE ENVOYCOMMUNICATIONSGATEWAYBMODULE STRINGINGCB440A(E)UTILITYMETERSOLAR FRAMING SEPARATELYGROUNDED BY AUX ROD#6 BARE COPPER AUX.GROUND PERNEC 690.47DERATEDCONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONSID TYPICALCONDUCTORCONDUITCURRENT-CARRYINGCONDUCTORS IN CONDUITOCPDEGCTEMP. CORR.FACTORCONDUIT FILLFACTORCONT.CURRENTMAX. CURRENT(125%)BASE AMP.DERATEDAMP.TERM. TEMP. RATINGAMP. @ TERMINAL01110 AWG THWN-2, COPPER0.75'' DIA EMT420A6 AWG THWN-2, COPPER0.96 (32.1 °C)0.815.73A 19.66A40A 30.72A75°C35A0218 AWG THWN-2, COPPER0.75'' DIA EMT2N/A8 AWG THWN-2, COPPER0.96 (32.1 °C)130.25A 37.81A55A52.8A75°C50A03 18 AWG THWN-2, COPPER0.75'' DIA EMT240A8 AWG THWN-2, COPPER0.96 (32.1 °C)130.25A 37.81A55A52.8A75°C50AE-601.00(SHEET 6)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160LINE DIAGRAM SYSTEM SUMMARYBRANCH #1BRANCH #2INVERTERS PER BRANCH1312MAX AC CURRENT15.73A14.52AMAX AC OUTPUT POWER3,835W3,540WARRAY STC POWER8,000WARRAY PTC POWER7,445WMAX AC CURRENT30.25AMAX AC POWER7,375WDERATED (CEC) AC POWER7,222WDISCONNECTSINVERTERSOCPDSMODULESASHRAE EXTREME LOW-35.2°C (-31.4°F), SOURCE: AIRLAKE (44.63°; -93.22°)ASHRAE 2% HIGH32.1°C (89.8°F), SOURCE: AIRLAKE (44.63°; -93.22°)REF.QTY.RATED CURRENTMAX VOLTAGECB1-2 220A240VACCB3110A240VACCB4 140A240VACREF.QTY.MAKE AND MODELRATED CURRENT MAX RATED VOLTAGESW1 1SQUARE D DU222RB OR EQUIV.60A240VACREF.QTY.MAKE AND MODELPMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATINGPM1-25 25TRINA SOLAR TSM-320DD06H.05(II)320W 297.8W 10A 9.6A 40.6V 33.3V-0.118V/°C (-0.29%/°C)20AREF.QTY.MAKE AND MODELACVOLTAGEGROUNDOCPDRATINGRATEDPOWERMAX OUTPUTCURRENTMAX INPUTCURRENTMAX INPUTVOLTAGECEC WEIGHTEDEFFICIENCYI1-25 25ENPHASE IQ7PLUS-72-2-US240VFLOATING20A 290W1.21A15A 60V97.0%BILL OF MATERIALSCATEGORYMAKEMODEL NUMBERREFQTYUNITQTY/UNITDESCRIPTIONMODULETRINA SOLARTSM-320DD06H.05(II)PM1-25 25 PIECES 1TRINA SOLAR TSM-320DD06H.05(II) 320W 120 HALF-CUT CELLS, MONOCRYSTALLINE SILICONINVERTERENPHASEIQ7PLUS-72-2-USI1-2525 PIECES 1ENPHASE IQ7PLUS-72-2-US 290W INVERTERDISCONNECTSQUARE DDU222RBSW11 PIECE 1SQUARE D DU222RB, 2-POLE, 60A, 240VAC OR EQUIVALENTMISC ELECTRICAL EQUIPMENTGEN-CABLE-CLIPHDWR28-153 125 PIECES 1 GENERIC CABLE CLIPAC COMBINER PANELENPHASE-IQ3-PANELEP11 PIECE 1ENPHASE IQ COMBINER 3 (X-IQ-AM1-240-3)MONITORINGENPHASE-ENVOYENV11 PIECE 1 ENPHASE ENVOYWIRINGENPHASEQ-12-17-240EN1-25 25 PIECES 1ENPHASE ENGAGE (TM) TRUNK CABLEWIRINGENPHASEQ-TERM-10EN261BUNDLE10ENPHASE ENGAGE (TM) BRANCH TERMINATORWIRINGENPHASEQ-SEAL-10EN271BUNDLE10ENPHASE ENGAGE (TM) WATERTIGHT SEALING CAPWIRINGGEN-10-AWG-THWN-2-CU-RDWR190 FEET 110 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-10-AWG-THWN-2-CU-BLKWR190 FEET 110 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-8-AWG-THWN-2-CU-RDWR2-3 20 FEET 18 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-8-AWG-THWN-2-CU-BLKWR2-3 20 FEET 18 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-8-AWG-THWN-2-CU-WHWR2-3 20 FEET 18 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIRINGGEN-8-AWG-THWN-2-CU-GRWR2-3 20 FEET 18 AWG THWN-2, COPPER, GREEN (GROUND)WIRINGGEN-6-AWG-THWN-2-CU-GRWR145FEET 16 AWG THWN-2, COPPER, GREEN (GROUND)WIREWAYENPHASEET-SPLK-05EN51BUNDLE 5ENPHASE ENGAGE (TM) ENGAGE COUPLERWIREWAYGEN-EMT-0.75'' DIAWW1-3 65 FEET 1EMT CONDUIT, 0.75'' DIAOCPDGENERIC MANUFACTURERGEN-CB-20A-240VACCB1-22 PIECES 1CIRCUIT BREAKER, 20A, 240VACOCPDGENERIC MANUFACTURERGEN-CB-10A-240VACCB31 PIECE 1CIRCUIT BREAKER, 10A, 240VACOCPDGENERIC MANUFACTURERGEN-CB-40A-240VACCB41 PIECE 1CIRCUIT BREAKER, 40A, 240VACTRANSITION BOXGENERIC MANUFACTURERGEN-AWB-TB-4-4XJB11 PIECE 1TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKSE-602.00(SHEET 7)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160DESIGN TABLES GRADE(N) AC DISCONNECTTO PV ARRAY(E) UTILITYTO (E) MEP(INSIDE)(N) AC COMBINER BOX(E) METERE-603.00(SHEET 8)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 22132020116001EQUIPMENT ELEVATIONNOT TO SCALEPLACARDS 1! WARNING !DUAL POWER SOURCES.SECOND SOURCE IS PV SYSTEMLABEL 6PHOTOVOLTAICAC DISCONNECTOPERATING CURRENT: 30.25 A ACOPERATING VOLTAGE: 240 V ACLABEL 5AT POINT OF INTERCONNECTION, MARKEDAT DISCONNECTING MEANS[NEC 690.54]! WARNING !ELECTRIC SHOCK HAZARDTERMINALS ON BOTH LINE AND LOAD SIDESMAY BE ENERGIZED IN THE OPEN POSITION.LABEL 3AT EACH DISCONNECTING MEANS FORPHOTOVOLTAIC EQUIPMENT[NEC 690.13 AND 690.15]PHOTOVOLTAICAC DISCONNECTWARNING: PHOTOVOLTAICPOWER SOURCELABEL 11AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRINGMETHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERESEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,OR FLOORS.[NEC 690.31(G)]LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;REFLECTIVE[IFC 605.11.1.1]LABEL 12AT EACH AC DISCONNECTING MEANS[NEC 690.13(B)]! CAUTION !PHOTOVOLTAIC SYSTEMCIRCUIT IS BACKFED! WARNING !POWER SOURCE OUTPUTCONNECTION - DO NOT RELOCATETHIS OVERCURRENT DEVISELABEL 13AT POINT OF INTERCONNECTIONOVERCURRENT DEVICE[NEC 705.12(B)(2)(3)(B)]INTERACTIVE PHOTOVOLTAIC SYSTEMCONNECTEDLABEL 8AT UTILITY METER[NEC 690.56(B)]PHOTOVOLTAIC SYSTEMEQUIPPED WITH RAPIDSHUTDOWNLABEL 10AT RAPID SHUTDOWN SWITCH[NEC 690.56(C)].LETTERS AT LEAST 3/8 INCH; WHITE ON REDBACKGROUND; REFLECTIVE[IFC 605.11.1.1]LABEL 7LABELING NOTES1.1 LABELING REQUIREMENTS BASED ON THE 2017 ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD1910.145, ANSI Z5351.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGEBACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535]DIRECTORYPERMANENT PLAQUE ORDIRECTORY PROVIDINGTHE LOCATION OF THESERVICEDISCONNECTING MEANSAND THE PHOTOVOLTAICSYSTEM DISCONNECTINGMEANS IF NOT IN THESAME LOCATION[NEC 690.56(B)]PLAQUEAT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 5 OR LABEL 6 MUST IDENTIFYPHOTOVOLTAIC SYSTEM[NEC 705.12(B)(4)]INTERACTIVE PHOTOVOLTAIC SYSTEMCONNECTEDPHOTOVOLTAIC SYSTEM DISCONNECT LOCATEDEAST SIDE OF THE HOUSEWHERE THE PV SYSTEMSARE REMOTELY LOCATEDFROM EACH OTHER, ADIRECTORY INACCORDANCE WITH 705.10SHALL BE PROVIDED ATEACH PV SYSTEMDISCONNECTING MEANS.PV SYSTEM EQUIPMENTAND DISCONNECTINGMEANS SHALL NOT BEINSTALLED IN BATHROOMS[NEC 690.4(D),(E)]SOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNTURN RAPID SHUTDOWNSWICH TO THE "OFF"POSITION TO SHUTDOWNPV SYSTEM AND REDUCESHOCK HAZARD IN ARRAYSOLAR ELECTRICPV PANELSLABEL 1AT RAPID SHUTDOWN SYSTEM[NEC 690.56(C)(1)(A)]. MAIN DISTRIBUTIONUTILITY DISCONNECTFRONTPV ARRAYBACK!CAUTION!POWER TO THIS BUILDING IS ALSO SUPPLIEDFROM ROOF MOUNTED SOLAR ARRAYS WITHSAFETY DISCONNECTS AS SHOWN:E-604.00(SHEET 9)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160NEWSPLACARDS 2PV ARRAYPV ARRAY SHEET KEYNOTES1. ROOF MATERIAL: ASPHALT SHINGLE2. ROOF STRUCTURE: TRUSS3. ATTACHMENT TYPE: UNIRAC FLAT FLASHING4. MODULE MANUFACTURER: TRINA SOLAR5. MODULE MODEL: TSM-320DD06H.05(II)6. MODULE LENGTH: 65.94''7. MODULE WIDTH: 39.06''8. MODULE WEIGHT: 41.4 LBS.9. SEE SHEET A-103 FOR DIMENSION(S)10. MIN. FIRE OFFSET: NO FIRE CODE ENFORCED11. TRUSS SPACING: 24 IN. O.C.12. TRUSS SIZE: 2X4 NOMINAL13. LAG BOLT SIZE: 5/16 IN.14. LAG BOLT EMBEDMENT: 2 IN.15. TOTAL # OF ATTACHMENTS: 8616. TOTAL AREA: 447.16 SQ. FT.17. TOTAL WEIGHT: 1220.6 LBS.18. WEIGHT PER ATTACHMENT: 14.19 LBS.19. DISTRIBUTED LOAD: 2.73 PSF20. MAX. HORIZONTAL STANDOFF: 48 IN.21. MAX. VERTICAL STANDOFF: LANDSCAPE: 26 IN., PORTRAIT: 33 IN.22. STANDOFF STAGGERING: YES23. RAIL MANUFACTURER (OR EQUIV.): UNIRAC24. RAIL MODEL (OR EQUIVALENT): LIGHT25. RAIL WEIGHT: 0.491 PLF.26. MAX. TRUSS SPAN: 12 FT, 20 FT.27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.S-501D52011121413151822ROOF SLOPE 910106217S-501D4315425242382721. FIELD VERIFY ALL MEASUREMENTSGENERAL NOTESBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160S-501.00(SHEET 9)ASSEMBLY DETAILSD4DETAIL (TRANSVERSE)NOT TO SCALED5DETAIL (LONGITUDINAL)NOT TO SCALED1RACKING DETAIL (TRANSVERSE)NOT TO SCALED3RACKING DETAIL (TOP)NOT TO SCALED2RACKING DETAIL (LONGITUDINAL)NOT TO SCALE BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160R-001.00(SHEET 11)RESOURCE DOCUMENT BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160R-002.00(SHEET 12)RESOURCE DOCUMENT BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160R-003.00(SHEET 12)RESOURCE DOCUMENT BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160R-004.00(SHEET 14)RESOURCE DOCUMENT BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 8.000 kWpENGINEER OF RECORD08.20.2020DESIGN BY:P.V.M.M.ZIENTARARESIDENCEPAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRICPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:(763)412-5714NO. EA7686744250 INLAND LANE N PLYMOUTHMINNESOTA 554469997 173RD STREET WESTLAKEVILLE, MN 55044APN: 221320201160R-005.00(SHEET 15)RESOURCE DOCUMENT