HomeMy WebLinkAboutLA192728 - Approved Site Plan Binder - Norton_StampedUMACMSPPMLCACSITE PLAN-1 PV-1.0 JAMES NORTON - 9.500kW DC, 7.250kW AC SITE PLAN-1 PV-1.0 A SITE PLAN-1 SCALE: 3/32" = 1'-0" INDEX INDEX NO.DESCRIPTION SITE PLAN-1 SITE PLAN-2 GENERAL NOTES MOUNTING DETAILS STRUCTURAL DETAILS SINGLE LINE DIAGRAM WARNING PLACARDS SPEC SHEET(S) PV-1.0 PV-1.1 PV-2.0 PV-3.0 PV-3.1 PV-4.0 PV-5.0 SS ELECTRIC CODE NEC 2020 FIRE CODE IFC 2018 RESIDENTIAL CODE MRC 2020 BUILDING CODE MBC 2020 WIND SPEED 109 MPH SNOW LOAD 50 PSF GENERAL INFORMATION PV-1.0 A1 VICINITY MAP SCALE: NTS CUSTOMER INFORMATION NAME&ADDRESS: 44°42'16.43"N 93°16'28.65"W APN:226-460-403-060 AHJ:MN-CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC ASSOCIATION SYSTEM INFORMATION DESIGNER/CHECKED BY: SP/PR PROJECT NUMBER:CCEN-002808 SCALE:AS NOTED PAPER SIZE:17"x11" JAMES NORTON 16955 JASPER PATH, LAKEVILLE, MN 55044. ENGINEER OF RECORD DATE:6/24/2021 REV:A 10361 JAMESTOWN ST NE BLAINE, MN 55449 763-450-9769 LIC:ELEC#EA006457 LIC:GEN#BC638279 DC SYSTEM SIZE: 9500W AC SYSTEM SIZE: 7250W MODULES: (25)LG NEON LG380Q1K-A6 INVERTER: (25)ENPHASE IQ7PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 1 BRANCH OF 13 MICRO INVERTERS(13 MODULES), 1 BRANCH OF 12 MICRO INVERTERS(12 MODULES). ACCOUNT #200002071496 METER #1ND91232406 DISTANCE BETWEEN EQUIPMENT FROM TO DISTANCE(FT) MODULE ENPHASE IQ COMBINER 3 30 ENPHASE IQ COMBINER 3 UTILITY AC DISCONNECT 1 UTILITY AC DISCONNECT UTILITY PV PRODUCTION METER 1 UTILITY PV PRODUCTION METER FUSED DISCONNECT 1 FUSED DISCONNECT UTILITY METER 1 UTILITY METER MAIN SERVICE PANEL 1 TOTAL AREA OF ROOF 2916 TOTAL ARRAY AREA 487.7 TOTAL AREA OF ROOF COVERED IN ARRAY 16.72% 1'-6" FIRE SETBACK 3' FIRE SETBACK (N) FUSED DISCONNECT(EXTERIOR) NOTE: 1.NO CLEARANCE ISSUES WITH EXITING OVERHEAD LINES 2.PRODUCTION METER AND PV UTILITY DISCONNECTS ARE ·LOCATED WITHIN 10' OF MAIN SERVICE/BILLING METER ·VISIBLE,LOCKABLE,READILY ACCESIBLE AND 24/7 ACCESS 3.DESIGN COMPLY WITH NEC AND NEC690 4.LABELS SHALL BE WEATHERPROOF,DURABLE,AND PERMANENTLY MOUNTED 5.24/7 UNSCORTED KEYLESS ACCESS TO METERS AND UTILITY AC DISCONNECTS. 6.SECONDARY INTERCONNECTION 7.PV MODULES ARE UL1703 RATED. 8.MICRO INVERTERS ARE UL1741 RATED. MIN.1'CLEARANCE(E) MAIN SERVICE PANEL(INTERIOR) PHOTOVOLTAIC ARRAY ON THE ROOF (N) UTILITY AC DISCONNECT(EXTERIOR) (N) UTILITY PV PRODUCTION METER(EXTERIOR) (E) UTILITY METER(EXTERIOR) CONDUIT RUN (N) ENPHASE IQ COMBINER 3(EXTERIOR)ST A TE OF M I N N E SOTA52544 ENGINEERPAULK.ZACH E RPROFESSIONAL LICENSED I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota. Signature: _______________________________________ Typed or Printed Name: ____________________________ Date: _______________ License Number:______________52544 EXP. 06/30/2022 16955 JASPER PATH LAKEVILLE, MN 55044 UMACMSPPMLCACSITE PLAN-2 PV-1.1 JAMES NORTON - 9.500kW DC, 7.250kW AC SITE PLAN-2 PV-1.1 A SITE PLAN-2 SCALE: 1"=20'-0" CUSTOMER INFORMATION NAME&ADDRESS: 44°42'16.43"N 93°16'28.65"W APN:226-460-403-060 AHJ:MN-CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC ASSOCIATION SYSTEM INFORMATION DESIGNER/CHECKED BY: SP/PR PROJECT NUMBER:CCEN-002808 SCALE:AS NOTED PAPER SIZE:17"x11" JAMES NORTON 16955 JASPER PATH, LAKEVILLE, MN 55044. ENGINEER OF RECORD DATE:6/24/2021 REV:A 10361 JAMESTOWN ST NE BLAINE, MN 55449 763-450-9769 LIC:ELEC#EA006457 LIC:GEN#BC638279 DC SYSTEM SIZE: 9500W AC SYSTEM SIZE: 7250W MODULES: (25)LG NEON LG380Q1K-A6 INVERTER: (25)ENPHASE IQ7PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 1 BRANCH OF 13 MICRO INVERTERS(13 MODULES), 1 BRANCH OF 12 MICRO INVERTERS(12 MODULES).JASPER CIRAPPROX.300'WIDTH.40'JAVELIN A V E APPROX.32 0 ' WIDTH.30 ' FENCE 1 PHOTOVOLTAIC ARRAY ON THE ROOF PROPERTY LINE 138'-11"151'-1"39'-8"72'-6" 9'-6"46'-6"DRIVE WAY JASPE R P A T HWALK WAYFENCE 2 ST A TE OF M I N N E SOTA52544 ENGINEERPAULK.Z ACH E R PROFESSIONAL LICENSED I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota. Signature: _______________________________________ Typed or Printed Name: ____________________________ Date: _______________ License Number:______________52544 EXP. 06/30/2022 16955 JASPER PATH LAKEVILLE, MN 55044 GENERAL NOTES PV-2.0 CUSTOMER INFORMATION NAME&ADDRESS: 44°42'16.43"N 93°16'28.65"W APN:226-460-403-060 AHJ:MN-CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC ASSOCIATION SYSTEM INFORMATION DESIGNER/CHECKED BY: SP/PR PROJECT NUMBER:CCEN-002808 SCALE:AS NOTED PAPER SIZE:17"x11" JAMES NORTON 16955 JASPER PATH, LAKEVILLE, MN 55044. ENGINEER OF RECORD DATE:6/24/2021 REV:A 10361 JAMESTOWN ST NE BLAINE, MN 55449 763-450-9769 LIC:ELEC#EA006457 LIC:GEN#BC638279 DC SYSTEM SIZE: 9500W AC SYSTEM SIZE: 7250W MODULES: (25)LG NEON LG380Q1K-A6 INVERTER: (25)ENPHASE IQ7PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 1 BRANCH OF 13 MICRO INVERTERS(13 MODULES), 1 BRANCH OF 12 MICRO INVERTERS(12 MODULES). GENERAL NOTES GENERAL NOTES 1.MODULES ARE LISTED UNDER UL 1703 AND CONFORM TO THE STANDARDS. 2.INVERTERS ARE LISTED UNDER UL 1741 AND CONFORM TO THE STANDARDS. 3.DRAWINGS ARE DIAGRAMMATIC, INDICATING GENERAL ARRANGEMENT OF THE PV SYSTEM AND THE ACTUAL SITE CONDITION MIGHT VARY. 4.WORKING CLEARANCES AROUND THE NEW PV ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH NEC CODE. 5.ALL GROUND WIRING CONNECTED TO THE MAIN SERVICE GROUNDING IN MAIN SERVICE PANEL/ SERVICE EQUIPMENT. 6.ALL CONDUCTORS SHALL BE 600V, 75°C STANDARD COPPER UNLESS OTHERWISE NOTED. 7.WHEN REQUIRED, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 8.THE SYSTEM WILL NOT BE INTERCONNECTED BY THE CONTRACTOR UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND/OR THE UTILITY. 9.ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREES, WIRES OR SIGNS. 10.PV ARRAY COMBINER/JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING EQUIPMENT LOCATION: 11.ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC CODE. 12.WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC CODE AND NEC TABLES. 13.JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC CODE. 14.ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 15.ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC APPLICABLE CODES. 16.ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE . STRUCTURAL NOTES: 17.RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS. 18.JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. 19.ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED WITH APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR. 20.ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 21.WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. WIRING & CONDUIT NOTES: 22.ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING. 23.CONDUCTORS SIZED ACCORDING TO NEC CODE. 24.DC WIRING LIMITED TO MODULE FOOTPRINT. MICRO INVERTER WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY WITH SUITABLE WIRING CLIPS. 25.AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GREY IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [NEC CODE]. INTERCONNECTION NOTES: 26.LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC CODE] 27.THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAY NOT EXCEED 120% OF BUSBAR RATING [NEC CODE]. 28.WHEN SUM OF THE PV SOURCES EQUALS >100% OF BUSBAR RATING, PV DEDICATED BACKFFED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC CODE]. 29.AT MULTIPLE PV OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVER CURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE COMBINED OVER CURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC CODE. 30.FEEDER TAP INTER CONNECTION (LOAD SIDE) ACCORDING TO NEC CODE 31.SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC CODE (A) WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC CODE 32. BACK FEEDING BREAKER FOR UTILITY-INTERACTIVE INVERTER OUTPUT IS EXEMPT FROM ADDITIONAL FASTENING [NEC CODE]. GROUNDING NOTES: 33.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. 34.PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC CODE AND MINIMUM NEC TABLE. 35.METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN ACCORD. 36.EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC CODE AND MICRO INVERTER MANUFACTURER'S INSTRUCTIONS. 37.EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. 38.THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. 39.GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [NEC CODE] 40.THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC CODE. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC CODE AND AHJ. 41.GROUND-FAULT DETECTION SHALL COMPLY WITH NEC CODE IN GENERAL AND NEC CODE SPECIFICALLY. 42.DISCONNECTION AND OVER-CURRENT PROTECTION NOTES: 43.DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS). 44.DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH 45.RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 10 FT OF PV ARRAY OR 5 FT INSIDE A BUILDING WITHIN 10 SECONDS. CONTROLLED CONDUCTORS ≤30V AND ≤240VA [NEC CODE]. LOCATION OF LABEL ACCORDING TO AHJ. 46.ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC CODE. 47.MICRO INVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN ACCORDANCE WITH NEC CODE. 2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO NEC CODE AND UL1699B.ST A TE OF M I N N E SOTA52544 ENGINEERPAULK.Z ACH E RPROFESSIONAL LICENSED I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota. Signature: _______________________________________ Typed or Printed Name: ____________________________ Date: _______________ License Number:______________52544 EXP. 06/30/2022 16955 JASPER PATH LAKEVILLE, MN 55044 MOUNTING DETAILS PV-3.0 CUSTOMER INFORMATION NAME&ADDRESS: 44°42'16.43"N 93°16'28.65"W APN:226-460-403-060 AHJ:MN-CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC ASSOCIATION SYSTEM INFORMATION DESIGNER/CHECKED BY: SP/PR PROJECT NUMBER:CCEN-002808 SCALE:AS NOTED PAPER SIZE:17"x11" JAMES NORTON 16955 JASPER PATH, LAKEVILLE, MN 55044. ENGINEER OF RECORD DATE:6/24/2021 REV:A 10361 JAMESTOWN ST NE BLAINE, MN 55449 763-450-9769 LIC:ELEC#EA006457 LIC:GEN#BC638279 DC SYSTEM SIZE: 9500W AC SYSTEM SIZE: 7250W MODULES: (25)LG NEON LG380Q1K-A6 INVERTER: (25)ENPHASE IQ7PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 1 BRANCH OF 13 MICRO INVERTERS(13 MODULES), 1 BRANCH OF 12 MICRO INVERTERS(12 MODULES). PV-3.0 B MOUNTING DETAILS SCALE:3/32"=1'-0" DEAD LOAD CALCULATIONS BOM QUANTITY LBS/UNIT TOTAL WEIGHT (LBS) MODULES 25 40.7 1017.50 MID-CLAMP 36 0.050 1.80 END-CLAMP 28 0.050 1.40 RAIL LENGTH 186 0.680 126.48 SPLICE BAR 8 0.360 2.88 SNAPNRACK FLASHED L FOOT 60 1.47 88.20 MICRO-INVERTER 25 2.38 59.50 TOTAL WEIGHT OF THE SYSTEM (LBS)1297.76 TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)487.82 WEIGHT PER SQ. FT.(LBS)2.66 WEIGHT PER PENETRATION (LBS)21.63 SITE INFORMATION SR.NO AZIMUTH PITCH NO. OF MODULES ARRAY AREA (SQ. FT.)ROOF TYPE ATTACHMENT ROOF EXPOSURE FRAME TYPE FRAME SIZE FRAME SPACING MAX RAIL SPAN OVER HANG MP-01 163°34°11 214.6 COMPOSITION SHINGLES SNAPNRACK FLASHED L FOOT ATTIC PRE-FABRICATED TRUSSES 2 X 4 2'-0"4'-0"2'-0" MP-02 163°32°7 136.6 COMPOSITION SHINGLE SNAPNRACK FLASHED L FOOT ATTIC PRE-FABRICATED TRUSSES 2 X 4 2'-0"4'-0"2'-0" MP-03 163°32°7 136.6 COMPOSITION SHINGLE SNAPNRACK FLASHED L FOOT ATTIC PRE-FABRICATED TRUSSES 2 X 4 2'-0"4'-0"2'-0" MODULES DATA LG NEON LG380Q1K-A6 MODULE DIMS 68.5"x41.02"x1.57" LAG SCREWS 5/16"x3.5":2.5"MIN EMBEDMENT UPLIFT CALCULATIONS UPLIFT 14634.7 LBS PULL OUT STRENGTH 36900 LBS POINT LOADING 17 LBS AERIAL VIEW MINIMUM FIRE ACCESS PATHWAYS PER IFC 2018 RIDGE TO ARRAY: 1'-6" EAVE TO ARRAY : 3'-0" HIP/VALLEY W/ ADJACENT ARRAY: 3'-0" EACH SIDE HIP/VALLEY W/O ADJACENT ARRAY: 0'-0" NOTE: INSTALLER TO VERIFY RAFTER SIZE, SPACING AND SLOPED SPANS, AND NOTIFY ANY DISCREPANCIES BEFORE PROCEEDING. FIRE SETBACK ALUMINUM RAILS 2 X 4 PRE-FABRICATED TRUSSES @2'-0" SPACING ARRAY MP-01 ARRAY MP-02 ARRAY MP-03 4' 14'-4" 3' 1'-6"ST A TE OF M I N N E SOTA52544 ENGINEERPAULK.Z ACH E R PROFESSIONAL LICENSED I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota. Signature: _______________________________________ Typed or Printed Name: ____________________________ Date: _______________ License Number:______________52544 EXP. 06/30/2022 16955 JASPER PATH LAKEVILLE, MN 55044 STRUCTURAL DETAILS PV-3.1 CUSTOMER INFORMATION NAME&ADDRESS: 44°42'16.43"N 93°16'28.65"W APN:226-460-403-060 AHJ:MN-CITY OF LAKEVILLE UTILITY:DAKOTA ELECTRIC ASSOCIATION SYSTEM INFORMATION DESIGNER/CHECKED BY: SP/PR PROJECT NUMBER:CCEN-002808 SCALE:AS NOTED PAPER SIZE:17"x11" JAMES NORTON 16955 JASPER PATH, LAKEVILLE, MN 55044. ENGINEER OF RECORD DATE:6/24/2021 REV:A 10361 JAMESTOWN ST NE BLAINE, MN 55449 763-450-9769 LIC:ELEC#EA006457 LIC:GEN#BC638279 DC SYSTEM SIZE: 9500W AC SYSTEM SIZE: 7250W MODULES: (25)LG NEON LG380Q1K-A6 INVERTER: (25)ENPHASE IQ7PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 1 BRANCH OF 13 MICRO INVERTERS(13 MODULES), 1 BRANCH OF 12 MICRO INVERTERS(12 MODULES). MID-CLAMP & END CLAMP DETAIL GROUNDING DETAILS 5/16"-18 SS BOLT SS SPLIT LOCK WASHER (TORQUE TO 16FT-LBS) SNAPNRACK GROUNDING LUG BOUNDING CHANNEL NUT RAIL 6-12 AWG BARE COPPER WIRE NOTES: ·ALL HARDWARE IS INCLUDED FROM MANUFACTURER ·A MINIMUM OF ONE GROUND LUG IS TO BE INSTALLED ON EVERY CONTINUOUS ROW OF MODULES ·GROUNDING LUG MAY BE INSTALLED IN EITHER RAIL CHANNEL ·GROUNDING LUG MAY BE INSTALLED SO GROUND WIRE IS PARALLEL OR PERPENDICULAR TO RAIL ·ENSURE SPLIT LOCK WASHER IS INSTALLED ON TOP OF COPPER WIRE. SCALE:NTS SS BONDING PIN MID CLAMP ASSEMBLY MODULE FRAME RAIL CHANNEL NUT SNAPNRACK GROUNDING MID-CLAMP SCALE: NTS NTS REMOVAL OF ONE PIECE OF EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN ANY OTHER PIECES. SCALE:NTS GROUND BONDING JUMPERRACKING PV MODULE SELF TAPING SCREW MODULE TO MODULE & MODULE TO RAIL SNAPNRACK GROUNDING RAIL TO RAIL PV MODULE RAIL END CLAMP PV MODULE RAIL MID CLAMP SCALE: NTS ROOF FRAMING DETAIL SCALE: NTS 5/16 HEX-BOLT STAINLESS STEEL 5/16" HANGER BOLT 2.5" EMBEDMENT PILOT HOLE REQUIRED (E) COMPOSITION SHINGLES ROOF SNAPNRACK FLASHED L FOOT SNAPNRACK ULTRA RAIL PV MODULE (E) BUILDING STRUCTURE ATTACHMENT DETAIL-SNAPNRACK FLASHED L FOOT SCALE: NTS LOAD BEARING WALL SNAPNRACK FLASHED L FOOT SOLAR MODULE RAIL 6" MAX 2 X 4 PRE-FABRICATED TRUSSES@2'-0" SPACING ST A TE OF M I N N E SOTA52544 ENGINEERPAULK.Z ACH E R PROFESSIONAL LICENSED I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota. Signature: _______________________________________ Typed or Printed Name: ____________________________ Date: _______________ License Number:______________52544 EXP. 06/30/2022 16955 JASPER PATH LAKEVILLE, MN 55044