Wyssling Consulting
76 North Meadowbrook Drive
Alpine, UT 84004
Scott E. Wyssling, PE, PP, CME office (201) 874-3483
swyssling@wysslingconsulting.com
August 28, 2021
Everlight Solar Construction
PO Box 930550
Verona, WI 53593
Re: Engineering Services
Lindsay Residence
9402 212th Street West, Lakeville, MN
4.680 kW System
To Whom It May Concern:
Pursuant to your request, we have reviewed the following information regarding solar panel installation on
the roof of the above referenced home:
1. Site Visit/Verification Form prepared by an Everlight Solar representative identifying
specific site information including size and spacing of trusses for the existing roof structure.
2. Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information was prepared by Everlight Solar and will be
utilized for approval and construction of the proposed system.
3. Photographs of the interior and exterior of the roof system identifying existing structural
members and their conditions.
Based on the above information we have evaluated the structural capacity of the existing roof system to
support the additional loads imposed by the solar panels and have the following comments related to our
review and evaluation:
Description of Residence:
The existing residence is typical wood framing construction with the roof system consisting of truss system
with all chords constructed of 2 x 4 dimensional lumber at 24” on center. The attic space is unfinished and
photos indicate that there was free access to visually inspect the size and condition of the roof trusses. All
wood material utilized for the roof system is assumed to be Doug-Fir #2 or better with standard construction
components. The existing roofing material consists of composite asphalt shingles. Photos of the dwelling
also indicate that there is a permanent foundation.
A. Loading Criteria Used
115 MPH wind loading based on ASCE 7-16 Exposure Category “C” at a slope of 30 degrees
7 PSF = Dead Load roofing/framing Live Load = 20 PSF Snow Load = 50 PSF
3 PSF = Dead Load solar panels/mounting hardware
Total Dead Load =10 PSF
The above values are within acceptable limits of recognized industry standards for similar
structures in accordance with the Minnesota Residential Code (2018 IRC). Analysis performed of
the existing roof structure utilizing the above loading criteria indicates that the existing trusses will
support the additional panel loading without damage, if installed correctly.
Page 2 of 2
B. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent “Quick Mount E-Mount
Installation Instructions”, which can be found on the IronRidge website (http://ironridge.com/). If
during solar panel installation, the roof framing members appear unstable or deflect non-uniformly,
our office should be notified before proceeding with the installation.
2. Maximum allowable pullout per lag screw is 235 lbs/inch of penetration as identified in the National
Design Standards (NDS) of timber construction specifications for Doug-Fir (North Lumber)
assumed. Based on our evaluation, the pullout value, utilizing a penetration depth of 2 ½”, is less
than what is allowable per connection and therefore is adequate. Based on the variable factors for
the existing roof framing and installation tolerances, using a thread depth of 2 ½” with a minimum
size of 5/16” lag screw per attachment point for panel anchor mounts should be adequate with a
sufficient factor of safety.
3. Considering the roof slopes, the size, spacing, condition of roof, the panel supports shall be placed
no greater than 48” o/c.
4. Panel supports connections shall be staggered to distribute load to adjacent trusses.
Based on the above evaluation, it is the opinion of this office that with appropriate panel anchors being utilized
the roof system will adequately support the additional loading imposed by the solar panels. This evaluation is in
conformance with the Minnesota Residential Code (2018 IRC), current industry standards, and is based on
information supplied to us at the time of this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
Very truly yours,
Scott E. Wyssling, PE
Minnesota License No. 57927
Dakota Electric
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
DATE:
August 28, 2021
PV01 COVER PAGE
PV02 SITE PLAN
PV03 ROOF ATTACHMENTS
PV04 MOUNTING DETAIL
PV05 LINE DIAGRAM
PV06 LABELS
PV07 PLACARD
PV08 SITE PHOTOS
COVER PAGE - PV01
DRAWN BY: SoloCAD
1.INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE
690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING.
2.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL
EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.
3.ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM
PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250
4.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER
UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES.
5.ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.8]
6.DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.31]
7.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE.
PHOTOVOLTAIC (PV) SYSTEM SPECIFICATIONS
AERIAL VIEW:
SHEET INDEX: EQUIPMENT:
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
(13) Silfab SIL-360 NX mono PERC PV MODULES
(7) AP Systems YC600 INVERTER(S)
RACKING: IronRidge - 48" O.C.
OCCUPANCY: R-3
ZONING: RESIDENTIAL
2020 NEC
2020 MRC
2020 MFC
2020 MBC
STREET VIEW:
GENERAL NOTES
APPLICABLE GOVERNING CODES SITE SPECIFICATIONS
AC
PV
MSPM
C
JB
Dakota Electric
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
DATE:
August 28, 2021
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
EQUIPMENT LEGEND:
INVERTERVISIBLE, LOCKABLE, LABELED
AC DISCONNECT
METER SOCKET
(FOR UTILITY PV METER)
UTILITY METER
MAIN SERVICE PANEL LC LOAD CENTER
FIRE ACCESS PATHWAY (3' TYP)
C
INV
PV
AC
MSP
M
COMBINER BOX PROPERTY LINE
BATT BATTERY(IES)
VISIBLE, LOCKABLE,
LABELED AC DISCONNECT
LOCATED WITHIN 10'
OF UTILITY METER
SUB SUB PANEL
ENGINEER STAMP
(IF APPLICABLE)
SITE PLAN - PV02
DRAWN BY: SoloCAD
FRONT OF HOME
MP1
PITCH: 30°
AZIMUTH: 180°
9402 212th Street West
124'-3"
61'-5"
2'
2'
2'
ROOF INFO:
ROOF TYPE asphalt_shingle
ROOF FRAMING manufactured_truss
RAFTER/TOP CHORD SIZE 2x4
RAFTER/TOP CHORD SPACING 24"
ATTACHMENT SPACING 48
AC
PV
MSPM
C
JB
EQUIPMENT INFORMATION:
RAIL MANUFACTURER IronRidge
RAIL PART NUMBER XR-10
ATTACHMENTS Quick Mount PV - E-Mount Lag
ATTACHMENT QTY 24
SPLICE QTY 4
MIDCLAMP QTY 22
ENDCLAMP QTY 8
ROOF INFO:
Dakota Electric
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
DATE:
August 28, 2021
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
ENGINEER STAMP
(IF APPLICABLE)
PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA:
PV MODULE COUNT:13
ARRAY AREA:MODULE COUNT * 18.06ft² = 234.78
ROOF AREA:1667 ft²
PERCENT OF ROOF COVERED:14%
ARRAY WEIGHT:MODULE COUNT * 50lbs = 650
DISTRIBUTED LOAD:ARRAY LBS/ATTACHMENTS = 27.08
POINT LOAD: (lbs/ft²)(ARRAY) WEIGHT/AREA = 2.77 lbs/ft²ROOF ATTACHMENTS - PV03
DRAWN BY: SoloCAD
18'' TYP 36" FIRE PATHWAY ACCESS
DETAIL, MOUNTING AND FLASHING
PV MODULE FRAME
IRONRIDGE RAIL
END CLAMP DETAILS
IRONRIDGE UNIVERSAL
FASTENING OBJECT
1"
PV MODULE FRAME
IRONRIDGE RAIL
MID CLAMP DETAILS
IRONRIDGE UNIVERSAL
FASTENING OBJECT
IRONRIDGE XR RAIL
QMSE
E-MOUNT LAG
2'-8" MIN -
3'-10" MAX
3
IRONRIDGE XR RAIL
PV MODULE
48" MAX.1'-8"
MAX.
21
FRONT VIEW
10" MIN -
1'-4"
MAX
2'-8" MIN -
3'-10" MAX
10" MIN -
1'-4"
MAX
SIDE VIEW3
21 (E) RAFTER/TOP CHORDS
(E) RAFTER/TOP CHORD
208.26
104.13
69.421
34.94
22.39
.694
42.52
(56.4)(65.39)
EQUIPMENT INFORMATION:
RAIL MANUFACTURER IronRidge
RAIL PART NUMBER XR-10
ATTACHMENTS Quick Mount PV - E-Mount Lag
ATTACHMENT QTY 24
SPLICE QTY 4
MIDCLAMP QTY 22
ENDCLAMP QTY 8
ROOF INFO:
ROOF INFO:
ROOF TYPE asphalt_shingle
ROOF FRAMING manufactured_truss
RAFTER/TOP CHORD SIZE 2x4
RAFTER/TOP CHORD SPACING 24"
ATTACHMENT SPACING 48
Dakota Electric
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
DATE:
August 28, 2021
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA:
PV MODULE COUNT:13
ARRAY AREA:MODULE COUNT * 18.06ft² = 234.78
ROOF AREA:1667 ft²
PERCENT OF ROOF COVERED:14%
ARRAY WEIGHT:MODULE COUNT * 50lbs = 650
DISTRIBUTED LOAD:ARRAY LBS/ATTACHMENTS = 27.08
POINT LOAD: (lbs/ft²)(ARRAY) WEIGHT/AREA = 2.77 lbs/ft²
ENGINEER STAMP
(IF APPLICABLE)
MOUNTING DETAIL - PV04
DRAWN BY: SoloCAD
STRING (1): 15.96 A AC, 13 MODULES
N
G
AC COMBINER BOX
SOLAR LOADS ONLY
UL 1741 COMPLIANT
AC
DC
AC
DC
7 INVERTERS
J-BOX
(N) 100A
(1) 20A-2P
J-BOX12 3
4
(E) LOADS
N
G
(E)GROUNDING
ELECTRODE
INTERCONNECTION NOTES
1. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9] & [NEC 230.95]
2. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC705.12(A)] WITH SERVICE ENTRANCE CONDUCTORS IN
ACCORDANCE WITH [NEC 240.21(B)]
DISCONNECT NOTES
1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS
REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS)
2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A
VISIBLE-BREAK SWITCH.
3. FUSED AC DISCONNECT TO BE USED.
(E)
120/240 VAC
TO UTILITY GRID
SUPPLY SIDE CONNECTION:
NEC 230.46, NEC 230.79,
NEC 705.12(A).
K4977-INT MILBANK
LUG KIT TO BE ADDED
(E) 150A-2P
(E) 150A MAIN SERVICE PANELUTILITY PV PRODUCTION
METER BASE
4 4
(N) 20A FUSES
PV AC DISCONNECT
60A FUSED, AIC 10kA
VISIBLE, LOCKABLE,
LABELED, OPEN
240V, 2-POLE LINE SIDE
LOAD SIDE
DATE:
August 28, 2021
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
Dakota Electric
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
GROUNDING & GENERAL NOTES:
1. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE.
2. DC GEC AND AC EGC TO REMAIN UNSPLICED, OR SPLICED TO EXISTING ELECTRODE
3. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE
INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION.
4. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD - JUNCTION
BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS.
5. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER
AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT.
ENGINEER STAMP
(IF APPLICABLE)
LINE DIAGRAM - PV05
DRAWN BY: SoloCAD
VISIBLE, LOCKABLE,
LABELED AC DISCONNECT
LOCATED WITHIN 10'
OF UTILITY METER
Conduit & Conductor Schedule
TAG WIRE GAUGE DESCRIPTION QTY CONDUIT SIZE CONDUCTOR
RATING
# OF CONDUCTORS
DERATE TEMP. DERATE CONDUCTOR RATING
W/DERATES CONDUIT FILL
1 12-2 TC-ER, THWN-2, COPPER (L 1, L 2)(2)N/A - FREE AIR 30A N/A - FREE AIR 0.96 28.8A N/A - FREE AIR
6 AWG BARE, COPPER (GROUND)(1)
2 10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER - (L 1, L 2)(2)3/4" EMT 40A 1 0.96 38.4A 11.9%10 AWG THWN-2, or THHN, or 10/2 NM-B COPPER - (GROUND)(1)
3 10 AWG THHN/THWN-2, COPPER - (L1, L2)(2)3/4" EMT 40A 1 0.96 38.4A 11.9%
10 AWG THHN/THWN-2 - (GROUND)(1)
4 6 AWG THWN-2 COPPER - (L1, L2, NEUTRAL)(3)3/4" EMT 65A 1 0.96 62.4A 35.5%8 AWG THWN-2 COPPER - (GROUND)(1)
EQUIPMENT SCHEDULE:
TYPE:QTY:DESCRIPTION:RATING:
MODULES:(13)Silfab SIL-360 NX mono PERC 360 W
INVERTERS:(7)AP Systems YC600 548 W
AC DISCONNECT(S):(1)PV AC DISCONNECT, 240V, 2-POLE 60A
Dakota Electric
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
DATE:
August 28, 2021
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
LABEL 6
MARKED AT AC DISCONNECTING MEANS.
[NEC 690.54]
LABEL 5
EQUIPMENT CONTAINING OVERCURRENT
DEVICES IN CIRCUITS SUPPLYING POWER TO
A BUSBAR OR CONDUCTOR SUPPLIED FROM
MULTIPLE SOURCES SHALL BE MARKED TO
INDICATE THE PRESENCE OF ALL
SOURCES.[NEC 705.12(B)(2)(3)(c)]
LABEL 3
PLACED ADJACENT TO THE BACK-FED BREAKER
FROM THE INVERTER IF TIE IN CONSISTS OF
LOAD SIDE CONNECTION TO BUSBAR.
[NEC 705.12(B)(2)(3)(c)]
*ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL
LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON THE ELECTRICAL DIAGRAM PAGE.
JUNCTION BOX
OR COMBINER BOX
MAIN SERVICE PANEL
AC DISCONNECT
EXISTING SUB PANEL
(IF WHERE POINT OF
INTERCONNECTION
IS MADE)
PV COMBINER
SUBPANEL -
IF USED TO COMBINE
PV OUTPUT CIRCUITS
AC
DC
INVERTER (S)
INTEGRATED DC DISCONNECT
2
8
6
9
5
(ONLY IF PV
INTERCONNECTION
CONSISTS OF LOAD
SIDE BREAKER)
7
1 1
1
5
(ONLY IF PV
INTERCONNECTION
CONSISTS OF LOAD
SIDE BREAKER)
7
3
LABELING DIAGRAM:
LABEL 7
AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS
AND ENCLOSURES OF JUNCTION BOXES, AND OTHER WIRING METHODS;
SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY
ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS.
[NEC 690.31(D)(2)]
LABEL 9
SIGN LOCATED ON OR NO MORE THAN 3FT
FROM INITIATION DEVICE
[NEC 690.56(C)(2)].
LABEL 8
FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND
CONDUCTORS LEAVING THE ARRAY:
SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM
SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL
IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME
LOCATION.
[NEC 690.56(C)(1)(A)]
LABEL 1
PLACED ON THE MAIN DISCONNECTING MEANS FOR
THE PV SYSTEM.
[NEC 690.13(B)]
LABELING NOTES:
1.LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO
DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND
MAKE APPROPRIATE ADJUSTMENTS.
2.LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRIC CODE, OSHA STANDARD
19010.145, ANSI Z535.
3.MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
4.LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED
[NEC 110.21]
5.LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND;
REFLECTIVE, AND PERMANENTLY AFFIXED [IFC 605.11.1.1]
3 4
1
LABEL 4
PLACED ON EQUIPMENT CONTAINING OVERCURRENT
DEVICES IN CIRCUITS SUPPLYING POWER TO
A BUSBAR OR CONDUCTOR SUPPLIED FROM
MULTIPLE SOURCES
[NEC 705.10(C)]
2
3 4
1
LABEL 2
FOR PV DISCONNECTING MEANS WHERE THE LINE AND
LOAD TERMINALS MAY BE ENERGIZED IN THE OPEN
POSITION.
[NEC 690.13(B)]
WARNING!
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
!WARNING
THIS EQUIPMENT IS FED BY MULTIPLE
SOURCES. TOTAL RATING OF ALL
OVERCURRENT DEVICES, EXCLUDING
MAIN SUPPLY OVERCURRENT
DEVICE, SHALL NOT EXCEED
AMPACITY OF BUSBAR.
PHOTOVOLTAIC AC DISCONNECT
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:
ELECTRIC SHOCK HAZARD
MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT
WARNING!
POWER SOURCE OUTPUT CONNECTION.
DO NOT RELOCATE THIS OVERCURRENT DEVICE.
WARNING!DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
PHOTOVOLTAIC POWER SOURCE
TURN RAPID SHUTDOWN
SWICH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
RAPID SHUTDOWN
SWITCH FOR
SOLAR PV SYSTEM
16
240
ENGINEER STAMP
(IF APPLICABLE)
LABELS - PV06
DRAWN BY: SoloCAD
AC
PV
MSPM
C
JB
Dakota Electric
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
DATE:
August 28, 2021
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED
SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN:
CAUTION
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE
SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM.
(ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN:
NEC 690.56(B)&(C), [NEC 705.10])
9402 212th Street West, Lakeville MN 55044
ENGINEER STAMP
(IF APPLICABLE)
PLACARD - PV07
DRAWN BY: SoloCAD
FRONT OF HOME
SYSTEM UTILIZES
MICROINVERTERS LOCATED
UNDER EACH SOLAR MODULE
MAIN DISTRIBUTION
UTILITY DISCONNECT
RAPID SHUTDOWN AC
DISCONNECT SWITCH
COMBINER BOX
PV ARRAY
Dakota Electric
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
DATE:
August 28, 2021
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
SITE PHOTOS:
ENGINEER STAMP
(IF APPLICABLE)
SITE PHOTOS - PV08
DRAWN BY: SoloCAD
Dakota Electric
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
DATE:
August 28, 2021
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
SITE PHOTOS:
ENGINEER STAMP
(IF APPLICABLE)
FRONT/BACK VIEWS - PV08.1
DRAWN BY: SoloCAD
Dakota Electric
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
DATE:
August 28, 2021
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
SITE PHOTOS:
ENGINEER STAMP
(IF APPLICABLE)
SIDE VIEWS - PV08.2
DRAWN BY: SoloCAD
Dakota Electric
SITE INFORMATION
Donna Lindsay
9402 212th Street West
Lakeville, MN 55044
AC SYSTEM SIZE: 3.836 kW AC
DC SYSTEM SIZE: 4.68 kW DC
Lat, 44.6424318
Long, -93.2561030999999
(13) Silfab SIL-360 NX mono PERC PV
MODULES
(7) AP Systems YC600 INVERTER(S)
DATE:
August 28, 2021
Everlight Solar Construction
7369 Highway 13 W
Savage, MN 55378
License# BC771658
833.786.4387 ext. 701
CONTRACTOR INFORMATION:
SITE PHOTOS:
ENGINEER STAMP
(IF APPLICABLE)
METER/OPEN MSP - PV08.3
DRAWN BY: SoloCAD
BAAARRABAAARRAINDUSTRY LEADING WARRANTYAll our products include an industry leading 25-year product workmanship and 30-year performance warranty.35+ YEARS OF SOLAR INNOVATIONLeveraging over 35+ years of worldwide experience in the solar industry, Silfab is dedicated to superior manufacturing processes and innovations such as Bifacial and Back Contact technologies, to ensure our partners have the latest in solar innovation.NORTH AMERICAN QUALITYSilfab is the leading automated solar module manufacturer in North America. Utilizing premium quality materials and strict quality control management to deliver PV modules. BAA / ARRA COMPLIANTSilfab panels are designed and manufactured to meet Buy American Act Compliance. The US State Department, US Military and FAA have all utilized Silfab panels in their solar installations. LIGHT AND DURABLE Engineered to accommodate high wind load conditions for test loads validated up to 4000Pa uplift. The light-weight frame is exclusively designed for wide-ranging racking compatibility and durability.QUALITY MATTERS Total automation ensures strict quality controls during the DOMESTIC OPERATIONSOur 500+ North American team is ready to help our partners win the hearts and minds of customers, providing customer AESTHETICALLY PLEASINGcommercial applications.PID RESISTANTPID Resistant due to advanced cell technology and material selection. In accordance to IEC 62804-1.* Chubb provides error and omission insurance to Silfab Solar Inc.ProudPartner ofSilfab Solar Inc.240 Courtneypark Drive EastMississauga ON L5T 2Y3 CanadaTel +1 905-255-2501 | Fax +1 905-696-0267info@silfabsolar.com | www.silfabsolar.comSilfab Solar Inc.800 Cornwall AveBellingham WA 98225 USATel +1 360-569-4733SIL-360 NX mono PERCTest Conditions STC NOCTModule Power (Pmax) Wp 360 258Maximum power voltage (Vpmax) V 36.6 33.1Maximum power current (Ipmax) A 9.9 7.8Open circuit voltage (Voc) V 44.5 40.4Short circuit current (Isc) A 10.5 8.2% 19.7 17.6Maximum system voltage (VDC) V 1000Series fuse rating A 20Power Tolerance Wp 0 to +10• Sun simulator calibration reference modules from Fraunhofer Institute. Electrical characteristics may vary by ±5% and power by 0 to +10W.SIL-360 NX mono PERC +0.064 %/°C-0.28 %/°C-0.36 %/°CNOCT (± 2°C) 46 °COperating temperature -40/+85 °CSIL-360 NX mono PERCMetric ImperialModule weight 20±0.2 kg 44±0.4 lbsDimensions (H x L x D) 1832 mm x 1000 mm x 38 mm 72.13 in x 39.4 in x 1.5 inMaximum surface load (wind/snow)* 4000 Pa rear load / 5400 Pa front load 83.5/112.8 lb/ft^2Hail impact resistance ø 25 mm at 83 km/h ø 1 in at 51.6 mphCells66 - Si mono-PERC - 5 busbar158.75 x 158.75 mm66 - Si mono-PERC - 5 busbar62.25 x 62.25 inGlass3.2 mm high transmittance, tempered, 0.126 in high transmittance, tempered, Cables and connectors (refer to installation manual)1200 mm ø 5.7 mm, MC4 from Staubli 47.2 in, ø 0.22 (12AWG), MC4 from Staubli BacksheetFrame Anodized Aluminum (Black)Bypass diodesJunction BoxSIL-360 NX mono PERCModule product workmanship warranty 25 years**Linear power performance guarantee30 yearsst year91.6% end 12th year 85.1% end 25th year 82.6% end 30th yearSIL-360 NX mono PERCProductULC ORD C1703, UL1703, CEC listed***, UL 61215-1/-1-1/-2, UL 61730-1/-2, IEC 61215-1/-1-1/-2***. IEC 61730-1/-2***, CSA C22.2#61730-1/-2, IEC 62716Ammonia Corrosion; IEC61701:2011 Salt Mist Corrosion Certifed, UL Fire Rating: Type 2Factory ISO9001:2015All states except CaliforniaModules Per Pallet: 26Pallets Per Truck: 34Modules Per Truck: 8847.87" [200mm]16.67" [423.5mm]38.78" [985mm]2.36" [60mm]38.11" [968mm]Mounting Hole(x4)Drainage (x8)Ø4.2mm (x2)Grounding Hole47.24"[1200mm]39.37" [1000mm]72.13" [1832mm]1.5" [38mm]72.13" [1832mm]1.02" [26mm]0.07" [1.8mm]1.5" [38mm]0.47" [12mm]0.39" [10mm]0.28" [7mm]C C* Warning. Read the Safety and Installation Manual installing and operating modules.**12 year extendable to 25 years subject to regis-tration and conditions outlined under “Warranty” at www.silfabsolar.com.data are available for download at: www.silfabsolar.com/downloads.CaliforniaModules Per Pallet: 26Pallets Per Truck: 32Modules Per Truck: 832Everlight SolarTel 833-786-4387www.everlightsolar.com
Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com
Please consult serving utility for their requirements prior to ordering or installing, as specifications and approvals vary by utility and may require local
electrical inspector approval. All installations must be installed by a licensed electrician and must comply with all national and local codes, laws and
regulations. Milbank reserves the right to make changes in specifications and features shown without notice or obligation.
Catalog Number K4977-INT
Marketing Product Description Tap Connector Kit Internal
Hex Slide Nut With 14-1/0
Box Connector 300 Volt
Maximum 3 Per Kit
UPC 784572274365
Length (IN)8
Width (IN)1.536
Height (IN)7.5
Weight (LB)0.5
Brand Name Milbank
Type Wire Connector Kit
Application Metering Accessory
Standard Non UL Listed
Size 8L x 1.536W x 7.5H
Connection Mechanical
Conductor Range 12 AWG to 1/0 AWG
Consist Of Connector
Mounting Slide Nut
Number Of Conductors 0
Material Aluminum
Voltage Rating Up to 300 Volts Alternating
Current
Insulation None
Temperature Rating 75 Degrees Celsius
K4977-INT
1028693