HomeMy WebLinkAboutLA196741 - Approved Al Sigrid Iversen Drawings wStamp 10 1 2021EXISTINGSNAPNRACKSITE MAP & PV LAYOUTELECTRICAL 1-LINE DIAGRAM ATTACHMENT LAYOUTSYSTEM LABELING DETAILINVERTER DATA SHEETSHEET INDEXPROPERTY PLANMODULE DATA SHEETRACKING DATA SHEETATTACHMENT DATA SHEETPV 1.0PV 2.0PV 4.0PV 5.1PV 6.0D 8.0D 9.0D 10.0SYSTEM RATINGEQUIPMENT SUMMARYELECTRICAL INFORMATIONMAIN SERVICE PANEL BUS SIZE:MAIN SERVICE BREAKER SIZE:MOUNTING SYSTEM:BUILDING INFORMATIONCONSTRUCTION TYPE: V-BOCCUPANCY: R3ROOF:Truss 2 x 4 @ 24" O.C.Comp ShingleVICINITY MAP (SCALE: NTS)SATELLITE VIEW (SCALE: NTS)GENERAL NOTES1.All electrical materials shall be new and listed by recognizedelectrical testing laboratory Custom made equipment shall have complete test data submittedby the manufacturer attesting to its safety2.Outdoor equipment shall be NEMA 3R rated or equivalent3.All metallic equipment shall be grounded4.Contractor shall obtain electrical permits prior to installation andshall coordinate all inspections, testing commissioning andacceptance with the client, utility co. and city inspectors as needed.5.The electrical contractor shall verify the exact locations of servicepoints and service sizes with the serving utility company andcomply with all utility companies requirements.6.Drawings are diagrammatic only, routing of raceways shall beoption of the contractor unless otherwise noted and shall becoordinated with other trades.7.If the roof material or the roof structure not adequate for PVinstallation, call the engineer of record print to installation. Thecontractor is responsible to verify that the roof is capable ofwithstanding the extra weight.8.If the distances for cable runs are different than shown, thecontractor shall notify the electrical engineer to validate the wiresize. Final drawings will be red-lined and updated as appropriate.9.Whenever a discrepancy in quality of equipment arises on thedrawing or specifications, the contractor shall be responsible forproviding and installing all materials and services required by thestrictest conditions noted on the drawings or in the specificationsto ensure complete compliance and longevity of the operablesystem required by the engineer of record.PHOTOVOLTAIC NOTES:1.Rooftop mounted photovoltaic panels and modules shall be tested,listed and identified by recognized testing laboratory2.Solar system shall not cover any plumbing or mechanical vents3.Modules and support structures shall be grounded unless racking has integrated ground.4.Removal of an interactive inverter or other equipment shall notdisconnect the bonding connection between the groundingelectrode conductor and the photovoltaic source and/or outputcircuit grounded conductors.5.All PV modules and associated equipment and wiring shall beprotected from physical damage.6.Live parts of PV source circuits and PV output circuits over 150v toground shall not be accessible to other than qualified persons while energized.7.Inverter is equipped with integrated DC disconnect, thus providingground fault protection8.All conductors shall be copper and 75 deg rated9.A single conductor shall be permitted to be used to perform themultiple functions of dc grounding, AC grounding and bondingbetween AC and DC systems.10.Non-current carrying metal parts of equipment shall be effectivelybonded together. Bond both ends of raceways.150A150A09/29/2021Property Address:Owner:Al & Sigrid IversenProperty Type:Single Family ResidenceDrawn by:New@engineerinc.ioDate:DC 10.64 KW STCAC 10.00 KW STC20676 Jaguar Ave Lakeville, MN 55044CONTRACTORAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comTHE INSTALLATION OF SOLAR ARRAYS ANDPHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITHTHE FOLLOWING CODES:·2020 National Electrical Code·2018 International Building Code·2018 International Residential Code·2020 Minnesota Residential Code·2020 Minnesota Building Code·2020 Minnesota Energy Code·2020 Minnesota Accessibility Code·2020 Minnesota State Fire Code·2018 International Fire Code·2018 International Energy Conservation Code·2018 Mechanical CodeAS ADOPTED BY THE STATE OF MINNESOTAALL OTHER ORDINANCE ADOPTED BY THELOCAL GOVERNING AGENCIESGOVERNING CODESPV 3.128 SILFAB 380 WATT MODULES WITH P400 POWEROPTIMIZERS, SOLAREDGE HD WAVE 10.0 KW INVERTEROPTIMIZER DATA SHEETPV 7.0D 11.0SURGE PROTECTIOND 12.0 ATTACHMENT DETAILPV 5.2D 13.0INVERTER CERTIFICATIOND 14.0PV INSPECTION CHECKLISTINVERTER CERTIFICATIONPLACARDPV 3.27/20/2021Date Certified andSigned: 10/1/2021
SOLAR MODULES___SILFAB 380 WattModel #SIL-380-BKEMT type ConduitSolar Module(N) Junction BoxJB.........................................................28MSP(E) Main Service Panel150AINDEX(N) Production MeterPM...........AC...................(N) 60A Utility AC(N) OptimizerNOTE: Conduit in attic shallbe minimum 18 inches from roof sheating* Roof access is not located in areas that require placement of ground ladders over exterior wall openings (R324.6.1).SITE MAP & PVLAYOUTPV 1.0PV SYSTEMAS INDICATEDScale:Project:Drawn by:New@engineerinc.ioProject Name:Property Adress:09/29/2021Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044DATE:CONTRACTORIN(N) Inverter.........................Wolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comNOTE: No clearance issue Distance between all equipments is maximum 10"(E) Main MeterMM........................FMT type Conduit..............SECONDARY INTERCONNECTIONEQUIPMENT ELEVATIONMainServicePanelUtility ACDisconnect4'MainMeterOutsideOutsideInsideInsideDakota Electric#:TBDNote: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENT..........................SolarEdgeStorEdgeNOTE:A 36-inchwide pathwayshall be provided to the emergencyescape and rescue opening.From roofINVERTERINVERTER TYPE: Central:Solar Edge Single Phase 10.0 kWHD Wave Technology InverterModel #SE10000H-US(240V)ProductionMeter10"<10'36'' fire setback36'' fire
P
a
t
h
w
a
y MSPMMPMACINJB''Roof Access''Solar PV Array28 - Silfab 380W Modules28 - P400 Power OptimizerPitch: 18 DegOrientation: 195 DegaaaaaaaaaaaaaabbbbbbbbbbbbbbSCALE:3/32" = 1'-0" 180° 90° 270°0°SWNE7/20/2021Date Certified andSigned: 10/1/2021
6000(4) #10 AWG THWN/THWN-2(1) #8 AWG GND3/4" FMT, 25 FEET1J BOXNEMA3RSolarEdge Power OptimizerRated DC Input Power -Maximum Input Voltage - 80 VdcMPPT Range - 8 to 80 VdcMaximum Input Current - 12.5 AdcMaximum Output Current - 15 AdcString Limitations - 8 to 25Optimizers, watts STC per string maximum.Solaredge optimizers have integratedrapid shut downP400400 watts14STRING - A2
PV 2.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044ELECTRICAL 1-LINE DIAGRAMCONTRACTOR60A FUSED AC DISCONNECT,WITH 60A FUSESUTILITY AC DISCONNECT VISIBLE-OPENLOCKABLE, READILY ACCESSIBLENEMA3R120 / 240V42AWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comEXISTING______ MAINSERVICEPANEL120/240V,1P, 3WGEC(E) GROUNDINGELECTRODE SYSTEM150ANOTE: Service Panel does not contain center fed Main Breaker:SECONDARY INTERCONNECTIONATT:PLEASE REFER TO WH NETMEETERING GUIDE:APPENDIX GThe lockable visible disconnect must be located within 5 feet from the GeneralService Meter and must be located onthe exterior of the buildingMeter Socket must be 150A ratedand must have lever BypassFor smaller DERs, using the PoC as theReference Point of Applicability allows the DERequipment type testing certification to be utilizedas the main method by which compliancewith the Standard is verified. The PoC might bethe terminals of an inverter, for example,and utilizing a UL 1741 certified and listedinverter would be sufficient to demonstrateStandard compliance.Note: Production Meter lockable and have lever-bypass Utility AC disconnect visible-open type lockable and readily accessible Inverters are UL 1741 certified (See Inverter Data sheet) In locations where there is no local Public Authority, the customer is exempt frominspection, and/or the service has been shut off or disconnected for more than 365 days (1 year),the licensed electrician or wireman shall submit a signed and dated Dakota Electric ElectricalInspection Certificate to the Company’s Builders Call Line attesting that the electrical installationhas been completed and installed according to the current National Electrical Code®, the DakotaElectric Standard for Electric Installation and Use, and any other applicable codes that apply beforeelectric service is energized.AtticWall
MAIN METER120/240V,1P, 3W(4) #10 AWG THWN/THWN-2(1) #8 AWG GND3/4" EMT, 5 FEET114STRING - B2NOTE:UTILITY HAS 24 HOURUNRESTRICTED ACCESS TO ALL PVSYSTEM COMPONENTS LOCATED ATSERVICE ENTRANCE.If there is cold water bonding and UFER , noadditional supplementary rod is requiredIf there is no UFER new ground rod shall beinstalledIf existing ground rod is more than 25-OHMthan a new ground rod shall be installedEXISTINGNON CENTER _____MAIN C/B150A(2) #10 AWG PV WIRE,(1) #10 AWG EGCFREE IN THE AIRSurge ProtectionREFERENCE POIN OF APPLICABILITYSILFAB 380WATT MODULES28P400POWER OPTIMIZER28(3) #6AWG THWN/THWN-2(1) #6 AWG GND 3/4" EMT, 2 FEETDakota Electric#:TBDNote: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTSolar Edge single phaseHD Wave 10.0kW TechnologyInverter have IntegratedDC Disconnect safety switchand Arc Fault ProtectionINVERTERSOLAR EDGE HD WAVE 10.0 kWMODEL #SE10000H-US(240V)LINE SIDE TAP(3) #6AWG THWN/THWN-2(1) #6 AWG GND 3/4" EMT,2 FEETLine42ADrawn by:New@engineerinc.io09/29/2021DATE:PV Production meter socket musthave lever bypass/bypassProduction meter is required based on the der sizeand program under which the application is submittedSQUARE-D-200A PVproduction meter socket withstamped brass aluminium orstainless steel tag labeled inaccordance with NEC andAHJ requirmentslocated within 5' of main.Inverter output wired to loadside terminal of meter1 phase 3-wire 120/240VLoad42A(3) #6AWG THWN/THWN-2(1) #6 AWG GND 3/4" EMT,2 FEETPV ARRAY RATINGWIRE SIZE CALCULATIONPV ARRAYFROM JUNCTION BOX TO INVERTERNumber Modules28TypeSIL-380BKSILFAB 380Maximum Current (A)14 * 380 / 400 = 13.3Number Inverters1Solar Edge 10kW Inverter with OptimizersSE10000H-US (240V)Considers Continuous (A)13.3 * 1.25 = 16.62LocationWatts STC, (Watts/Module) 28 * 380 = 10640Short Circuit Current (A)16.62 * 1.25 = 20.78Array CurrentsI-SC10.49AI-MP9.92ARaceway Height From Roof (Temp 39+22=61C)3 1/2"Module VoltageV-OC45.69VV-MP38.32VTemp. Derate Factor (A)20.78 / 0.71 = 29.26SYSTEM POWER#of wire(#of Strings*2)6Number Of Strings2Max Number of Modules Per String12More Than 3 CCC Adjist. Factor0.8Max DC Wattage In Strings14 * 380 = 5320 < 6000 (Watts)Max AC Voltage 120/240VAdjusted Conductor Ampacity(A)29.26/ 0.8 = 36.58FROM INVERTER TO MAIN PANELWire Size from NEC Table 310.15(b)1610 AWGTotal Current (A)42Ambiend Tem Factor Per NEC Table 310.15(b)(2)(a)0.71Total AC Wattage (Watts)10000Consider Continuous (A)42 * 1.25 = 52.5Temperature Adjustment52.5 / 0.91 = 57.69AConductor Size From NEC Table 310.166 AWGDC 10.64 KW STCAC 10.00 KW STC7/20/2021Date Certified andSigned: 10/1/2021
PV 3.1PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comSYSTEM LABELING DETAILDrawn by:New@engineerinc.io09/29/2021DATE:PV ARRAYJ BOXPV SUB-PANELACDISCONNECTPVPRODUCTIONMETERMAIN SERVICEPANELMETER12333331617218135Note: LABELS SHALL COMPLY WITH NEC 690“Labels shall be weatherproof, durable and permanently mounted”42AProduction MeterLABEL 1Photovoltaic Power SourceLABEL 2CAUTION: SOLAR CIRCUITLABEL 3WARNINGELECTRIC SHOCK HAZARDTHE DC CONDUCTORS OF THISPHOTOVOLTAIC SYSTEM AREUNDERGROUND AND MAY BE ENERGIZEDLABEL 4WARNINGELECTRIC SHOCK HAZARDIF GROUND FAULT IS INDICATEDNORMALLY GROUNDED CONDUCTORSMAY BE UNDERGROUND AND ENERGIZEDLABEL 5WARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE AND LOADSIDES MAY BE ENERGIZED IN THE OPENPOSITIONLABEL 6WARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE AND LOADSIDES MAY BE ENERGIZED IN THE OPENPOSITIONDC VOLTAGE IS ALWAYS PRESENTWHEN SOLAR MODULESARE EXPOSED TO SUNLIGHTLABEL 7WARNINGLABEL 8TURN OF PHOTOVOLTAICAC DISCONNECT PRIOR TOWORKING INSIDE PANELDO NOT DISCONNECTUNDER LOADLABEL 9MAIN PV SYSTEMDISCONNECTLABEL 10MAIN PV SYSTEMAC DISCONNECTLABEL 11LABEL 12CAUTIONLABEL 13SOLAR ELECTRIC SYSTEMCONNECTEDWARNING-LABEL 14 DUAL POWER SOURCESECOND SOURCE IS PV SYSTEMCAUTIONLABEL 15PHOTOVOLTAIC SYSTEM CIRCUITIS BACKFEDLABEL 16PHOTOVOLTAIC AC DISCONNECTMAXIMUM AC OPERATING CURRENTMAXIMUM AC OPERATING CURRENTPHOTOVOLTAICLABEL 17UTILITY AC DISCONNECTPHOTOVOLTAICLABEL 18DC DISCONNECTNOMINAL OPERATING AC VOLTAGENOMINAL OPERATING AC FREQUANCYMAXIMUM AC POWERMAXIMUM AC CURRENTMAX OCERCURRENT DEVICE RATINGFOR AC MODULE PROTECTIONLABEL 19LABEL 20PV SYSTEM DC DISCONNECTOPERATING CURRENTOPERATING VOLTAGEMAXIMUM SYSTEM VOLTAGESHORT CIRCUIT CURRENTCAUTIONLABEL 21PHOTOVOLTAIC SOURCECONNECTED***ALL LABELS = RED THERMOPLASTIC/REFLECTIVE , Permanently mounted240VSOLAR DISCONNECT217/20/2021Date Certified andSigned: 10/1/2021
PLACARDPV 3.2PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comINSTALL 40A PVINSTALL 20A PVCAUTIONPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:CAUTIONPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:SERVICE 1 OF 2SERVICE 2 OF 220676 Jaguar Ave Lakeville, MN 5504420676 Jaguar Ave Lakeville, MN 55044Drawn by:New@engineerinc.io09/29/2021DATE:NWESNWESSERVICE POINT &UTILITY METERINGPV SYSTEM DISCONNECTFOR UTILITY OPERATIONPERFORMANCE METERSOLAR INVERTERSOLAR PV ARRAYSERVICE POINT &UTILITY METERINGPV SYSTEM DISCONNECTFOR UTILITY OPERATIONPERFORMANCE METERSOLAR INVERTERSOLAR PV ARRAY7/20/2021Date Certified andSigned: 10/1/2021
PROPERTY PLANLEGENDMSPMain Service Panel................ Production MeterPM.................. AC DisconnectAC.........................PV 4.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORInverterIN........................................Wolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comMMMain Meter............................Dakota Electric#:TBDNote: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTDrawn by:New@engineerinc.io09/29/2021DATE:Jaguar AveDRIVEWAY29'-1"33'-8"55'-9"173'-3"47'-3"155'-9"29'-10"84'-7"6'62'-9"PROPERTY LINEMSPMMPMACINSCALE:1/64" = 1'-0" 180° 90° 270°0°SWNE7/20/2021Date Certified andSigned: 10/1/2021
ATTACHMENTLAYOUTPV 5.1PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDESIGN CRITERIAModules:Max Distributed Load: 3 PSFPOINT LOAD CALCULATION PER ARRAYModule Weight (lbs)# Of Modules41.9Total Module Weight (lbs)Rack Weight (lbs)Optimizers Weight (lbs)Total System Weight (lbs)# Of StandoffsMax Span Between Standoffs (in)Loading Per Standoff (lbs)Total Area (sq.ft.)Loading (PSF)1173.2234.6447.61455.44544826.956162.36RAIL ATTACHMENTMODULES ON ROOFTruss 2 x 4 @ 32" O.C.2828Dakota Electric#:TBDNote: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENT1 Layer of .Plywood & Building FeltSolar Module6"AttachmentMODULES ON ROOFTruss 2 x 4 @ 24" O.C.COMP SHINGLEPrior to the commencement of work, the contractor shall verify the existing roof and framingconditions. Notify New@engineerinc.io of any Discrepancies prior to starting construction.Prior to the commencement of work, the contractor shall inspect framing for any damagesuch as water damage, cracked framing, etc. and These Plans are stamped for structuralcode compliance of the roof framing supporting the proposed PV installation reference only.These plans are not stamped for water leakage. PV modules, racking, and attachmentcomponents must follow manufacturer guidelines and requirements. Attachments to beinstalled in a staggered orientation to properly distribute loads.2x4PurlinDrawn by:New@engineerinc.io09/29/2021DATE:1.86"3.05"0.25"Ø2.24"2.58"1"0.17"3.20"1.37"0.38"0.30"1.08"2.78"1.78"1.50"1.99"1.21"R 1.12"Ø0.33"R 0.82"12345SNAPNRACK, SPEEDSEAL FOOT, BASE, SEALING, SILVER/BLACKBOLT, FLANGE, SERRATED, 5/16IN-18 X 2IN, SSSNAPNRACK, RL UNIVERSAL, MOUNT SPRING, SSSNAPNRACK, ULTRA RAIL MOUNT THRU PRC, CLEAR/BLACKSNAPNRACK, ULTRA RAIL MOUNT TAPPED PRC, CLEAR/BLACK12345DESCRIPTIONITEMQTI11111MATERIALS:DESIGN LOAD (LBS):ULTIMATE LOAD (LBS):TORQUE SPECIFICATION:CERTIFICATION:WEIGHT (LBS):DIE CAST A380 ALUMINUM, 6000 SERIES ALUMINUM, STAINESS STEEL802 UP, 1333 DOWN, 357 SIDE2118 UP, 4006 DOWN, 1331 SIDE12 LB-FTUL 2703, FILE E359313; WIND-DRIVEN RAIN TEST FROM SUBJECT UL 25820.45OPTIONS:CLEAR/BLACKPARTS LISTSNAPNRACK, ULTRA RAIL SPEEDSEAL TM FOOT7/20/2021Date Certified andSigned: 10/1/2021
PV 5.2PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044ATTACHMENT DETAILCONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io09/29/2021DATE:
INVERTERDATA SHEETINVERTERDATA SHEETD 6.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io09/29/2021DATE:
POWER OPTIMIZERDATA SHEETD 7.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io09/29/2021DATE:
MODULEDATA SHEETD 8.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io09/29/2021DATE:
RACKINGDATA SHEETD 9.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io09/29/2021DATE:
ATTACHMENTDATA SHEETD 10.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io09/29/2021DATE:
D 11.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORSURGE PROTECTIONWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDATE:Drawn by:New@engineerinc.io09/29/2021DATE:
D 12.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORINVERTERCERTIFICATIONWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io09/29/2021DATE:
D13.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comINVERTERCERTIFICATIONDrawn by:New@engineerinc.io09/29/2021DATE:
D 14.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Al & Sigrid Iversen20676 Jaguar AveLakeville, MN 55044PV INSPECTIONCHECKLISTCONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comWolf RIver ElectricLakeville, MN 5504420676 Jaguar AveDrawn by:New@engineerinc.io09/29/2021DATE: