Loading...
HomeMy WebLinkAboutLA198330 Approved Solar PlansEXISTINGSNAPNRACKSITE MAP & PV LAYOUTELECTRICAL 1-LINE DIAGRAM ATTACHMENT LAYOUTSYSTEM LABELING DETAILINVERTER DATA SHEETSHEET INDEXPROPERTY PLANMODULE DATA SHEETRACKING DATA SHEETATTACHMENT DATA SHEETPV 1.0PV 2.0PV 4.0PV 5.1PV 6.0D 8.0D 9.0D 10.0SYSTEM RATINGEQUIPMENT SUMMARYELECTRICAL INFORMATIONMAIN SERVICE PANEL BUS SIZE:MAIN SERVICE BREAKER SIZE:MOUNTING SYSTEM:BUILDING INFORMATIONCONSTRUCTION TYPE: V-BOCCUPANCY: R3ROOF:Truss 2 x 4 @ 24" O.C.Comp ShingleVICINITY MAP (SCALE: NTS)SATELLITE VIEW (SCALE: NTS)GENERAL NOTES1.All electrical materials shall be new and listed by recognizedelectrical testing laboratory Custom made equipment shall have complete test data submittedby the manufacturer attesting to its safety2.Outdoor equipment shall be NEMA 3R rated or equivalent3.All metallic equipment shall be grounded4.Contractor shall obtain electrical permits prior to installation andshall coordinate all inspections, testing commissioning andacceptance with the client, utility co. and city inspectors as needed.5.The electrical contractor shall verify the exact locations of servicepoints and service sizes with the serving utility company andcomply with all utility companies requirements.6.Drawings are diagrammatic only, routing of raceways shall beoption of the contractor unless otherwise noted and shall becoordinated with other trades.7.If the roof material or the roof structure not adequate for PVinstallation, call the engineer of record print to installation. Thecontractor is responsible to verify that the roof is capable ofwithstanding the extra weight.8.If the distances for cable runs are different than shown, thecontractor shall notify the electrical engineer to validate the wiresize. Final drawings will be red-lined and updated as appropriate.9.Whenever a discrepancy in quality of equipment arises on thedrawing or specifications, the contractor shall be responsible forproviding and installing all materials and services required by thestrictest conditions noted on the drawings or in the specificationsto ensure complete compliance and longevity of the operablesystem required by the engineer of record.PHOTOVOLTAIC NOTES:1.Rooftop mounted photovoltaic panels and modules shall be tested,listed and identified by recognized testing laboratory2.Solar system shall not cover any plumbing or mechanical vents3.Modules and support structures shall be grounded unless racking has integrated ground.4.Removal of an interactive inverter or other equipment shall notdisconnect the bonding connection between the groundingelectrode conductor and the photovoltaic source and/or outputcircuit grounded conductors.5.All PV modules and associated equipment and wiring shall beprotected from physical damage.6.Live parts of PV source circuits and PV output circuits over 150v toground shall not be accessible to other than qualified persons while energized.7.Inverter is equipped with integrated DC disconnect, thus providingground fault protection8.All conductors shall be copper and 75 deg rated9.A single conductor shall be permitted to be used to perform themultiple functions of dc grounding, AC grounding and bondingbetween AC and DC systems.10.Non-current carrying metal parts of equipment shall be effectivelybonded together. Bond both ends of raceways.200A200A 10/15/2021Property Address:Owner:Nathan LykeProperty Type:Single Family ResidenceDrawn by:New@engineerinc.ioDate:DC 18.62 KW STCAC 15.20 KW STC19792 Itea Ave Lakeville, MN 55044CONTRACTORAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comTHE INSTALLATION OF SOLAR ARRAYS ANDPHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITHTHE FOLLOWING CODES:·2020 National Electrical Code·2018 International Building Code·2018 International Residential Code·2020 Minnesota Residential Code·2020 Minnesota Building Code·2020 Minnesota Energy Code·2020 Minnesota Accessibility Code·2020 Minnesota State Fire Code·2018 International Fire Code·2018 International Energy Conservation Code·2018 Mechanical CodeAS ADOPTED BY THE STATE OF MINNESOTAALL OTHER ORDINANCE ADOPTED BY THELOCAL GOVERNING AGENCIESGOVERNING CODESPV 3.1Xcel Energy Application#:0466491149 SILFAB 380 WATT MODULES WITH P400POWEROPTIMIZERS, 2 SOLAREDGE ENERGY HUB WITH PRISMTECHNOLOGY 7.6KW INVERTERSOPTIMIZER DATA SHEETPV 7.0D 11.0SURGE PROTECTIOND 12.0D 13.0INVERTER CERTIFICATIOND 16.0WITNESS TEST REPORTINVERTER CERTIFICATION ATTACHMENT DETAILPV 5.2PLACARDPV 3.2D 17.0PV INSPECTION CHECKLISTD 14.0BACKUP INTERFACE DATA SHEETD 15.0BATTERY DATA SHEETDate Certified andSigned: 10/252021 SOLAR MODULES___SILFAB 380WattModel #SIL-380 BKEMT type ConduitSolar Module(N) Junction BoxJB.........................................................49MSP(E) Main Service Panel200AINDEX(N) Backup InterfaceBI..............AC...................(N) 2x60A Utility AC(N) OptimizerNOTE: Conduit in attic shallbe minimum 18 inches from roof sheatingSITE MAP & PVLAYOUTPV 1.0PV SYSTEMAS INDICATEDScale:Project:Drawn by:New@engineerinc.ioProject Name:Property Adress: 10/15/2021Nathan Lyke19792 Itea AveLakeville, MN 55044DATE:CONTRACTORIN2x(N) Inverter.........................Wolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comNOTE: No clearance issue Distance between all equipments is maximum 10"(E) Main MeterMM........................FMT type Conduit..............SECONDARY INTERCONNECTIONXcel Energy Application#:04664911Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENT..........................BT.............................(N) BatteryINVERTERINVERTER TYPE: Central:Solar Edge Single Phase HD Wave7.6 kW PrismTechnology InverterModel #SE 7600H-US(240V)Xcel Energy Application#:04664911EQUIPMENT ELEVATIONMainServicePanel ACDisconnect10"4'MainMeterOutside Outside Inside Inside From roofSolar EdgeEnergyHubBackupInterfaceLGLG BatteryFrom roofAC...................(N) 200A Utility ACUtility ACDisconnectUtility ACDisconnectSolar EdgeEnergyHubOutside Insideaaaaaaaaaaaaabbbbbbb bbbcccccbbcccccccdddddddddddd Itea AveHazel Nut AveSolar PV Array 120- Silfab 380W Modules20 - P400 Power OptimizersPitch: 25 DegOrientation:91 DegSolar PV Array 24- Silfab 380W Modules4 - P400 Power OptimizersPitch: 25 DegOrientation:1 DegSolar PV Array 318- Silfab 380W Modules18 - P400 Power OptimizersPitch: 25 DegOrientation:271 DegSolar PV Array 54- Silfab 380W Modules4 - P400 Power OptimizersPitch: 25 DegOrientation:181 DegSolar PV Array 44- Silfab 380W Modules4 - P400 Power OptimizersPitch: 25 DegOrientation:1 DegMSPMMACBIINJB2JB118" fire setback18" fire setback18" fire setback18" fire setback18" fire setback18" f i r e s e t b a c kACINACBT SCALE:1/16" = 1'-0" 180° 90° 270°0°SWNE (4) #10 AWG THWN/THWN-2(1) #8 AWG GND3/4" FMT, 15 FEET1J BOX2NEMA3R12STRING - D2 PV 2.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044ELECTRICAL 1-LINE DIAGRAMCONTRACTOR32AWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comEXISTING______ MAINSERVICEPANEL120/240V,1P, 3WGEC(E) GROUNDINGELECTRODE SYSTEM200ANOTE: Service Panel does not contain center fed Main Breaker:SECONDARY INTERCONNECTIONATT:PLEASE REFER TO WH NETMEETERING GUIDE:APPENDIX GThe lockable visible disconnect must be located within 5 feet from the GeneralService Meter and must be located onthe exterior of the buildingMeter Socket must be 200A ratedand must have lever BypassXcel Energy Application#:04664911Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTDesign meet National Electric Code(NEC codes)For smaller DERs, using the PoC as the Reference Point of Applicability allows the DERequipment type testing certification to be utilized as the main method by whichcompliancewith the Standard is verified. The PoC might be the terminals of an inverter, for example,and utilizing a UL 1741 certified and listed inverter would be sufficient to demonstrateStandard compliance. In locations where there is no local Public Authority, the customer is exempt frominspection, and/or the service has been shut off or disconnected for more than 365 days (1 year),the licensed electrician or wireman shall submit a signed and dated Xcel Energy ElectricalInspection Certificate to the Company’s Builders Call Line attesting that the electrical installationhas been completed and installed according to the current National Electrical Code®, the Xcel EnergyStandard for Electric Installation and Use, and any other applicable codes that apply beforeelectric service is energized.AtticWall MAIN METER120/240V,1P, 3W(4) #10 AWG THWN/THWN-2(1) #8 AWG GND3/4" EMT, 5 FEETNOTE:UTILITY HAS 24 HOURUNRESTRICTED ACCESS TO ALL PVSYSTEM COMPONENTS LOCATED ATSERVICE ENTRANCE.If there is cold water bonding and UFER , no additionalsupplementary rod is requiredIf there is no UFER new ground rod shall be installedIf existing ground rod is more than 25-OHM than a new ground rodshall be installedEXISTINGNON CENTER _____MAIN C/B200A(4) #10 AWG THWN/THWN-2(1) #8 AWG GND3/4" FMT, 20 FEET1J BOX1NEMA3R12STRING - B2 32AAtticWall (4) #10 AWG THWN/THWN-2(1) #8 AWG GND3/4" EMT, 5 FEETSILFAB 380W WATT MODULES24P400 POWER OPTIMIZER24(3) #8AWG THWN/THWN-2(1) #8 AWG GND3/4" EMT, 2 FEET(3) #8AWG THWN/THWN-2(1) #8 AWG GND3/4" EMT, 2 FEET(2) #10 AWG PV WIRE,(1) #10 AWG EGCFREE IN THE AIRSurge ProtectionMNSPD-300-ACREFERENCE POIN OF APPLICABILITY112STRING - C2 (2) #10 AWG PV WIRE,(1) #10 AWG EGCFREE IN THE AIR113STRING - A2 6000SolarEdge Power OptimizerRated DC Input Power -Maximum Input Voltage - 80 VdcMPPT Range - 8 to 80 VdcMaximum Input Current - 12.5 AdcMaximum Output Current - 15 AdcString Limitations - 8 to 25Optimizers, watts STC per string maximum.Solaredge optimizers have integratedrapid shut downP400400 watts(3) #3/0AWG THWN/THWN-2(1) #4 AWG GND2" EMT, 2 FEETDrawn by:New@engineerinc.io 10/15/2021DATE:6000SolarEdge Power OptimizerRated DC Input Power -Maximum Input Voltage - 80 VdcMPPT Range - 8 to 80 VdcMaximum Input Current - 12.5 AdcMaximum Output Current - 15 AdcString Limitations - 8 to 25Optimizers, watts STC per string maximum.Solaredge optimizers have integratedrapid shut downP400400 wattsSILFAB 380W WATT MODULES25P400 POWER OPTIMIZER25DC 18.62 KW STCAC 15.20 KW STCINVERTERSOLAR EDGE ENERGY HUB 7.6 kWMODEL #SE 7600H-US(240V) 1P, 3WSolar Edge single phaseEnergy HUB 7.6 kW Prism TechnologyInverter have IntegratedDC Disconnect safety switchand Arc Fault ProtectionXcel Energy Application#:04664911PV ARRAY RATINGWIRE SIZE CALCULATIONPV ARRAYFROM JUNCTION BOX TO INVERTERNumber Modules49TypeSIL-380 BKSILFAB 380 WATTMaximum Current (A)13 * 380 / 400 = 12.35Number Inverters2Solar Edge 7.6kW Inverter with OptimizersSE7600H-US (240V)Considers Continuous (A)12.35 * 1.25 = 15.44Short Circuit Current (A)15.44 * 1.25 = 19.3LocationWatts STC, (Watts/Module) 49 * 380 = 18620Raceway Height From Roof (Temp 39+22=61C)3 1/2"Array CurrentsI-SC10.49AI-MP9.92ATemp. Derate Factor (A)19.3 / 0.71 = 27.18Module VoltageV-OC45.69VV-MP38.32V#of wire(#of Strings*2)4SYSTEM POWERMore Than 3 CCC Adjist. Factor0.8Number Of Strings4Max Number of Modules Per String13Adjusted Conductor Ampacity(A)27.18 / 0.8 = 33.98Max DC Wattage In Strings13 * 380 = 4940 < 6000 (Watts)Max AC Voltage 120/240VWire Size from NEC Table 310.15(b)1610 AWGFROM INVERTER 1 TO PVBACKUP INTERFACEAmbiend Tem Factor Per NEC Table 310.15(b)(2)(a)0.71Total Current (A)32Total AC Wattage (Watts)7600Consider Continuous (A)32 * 1.25 = 40Temperature Adjustment40 / 0.91 = 43.96Conductor Size From NEC Table 310.168 AWGTotal Current (A)32Total AC Wattage (Watts)7600Consider Continuous (A)32 * 1.25 = 40Temperature Adjustment40 / 0.91 = 43.96Conductor Size From NEC Table 310.168 AWG40ABackup InterfaceBI-NUSGN-01200A40ALG(2) #10 AWG THWN/THWN-2(1) #8 AWG GND3/4" EMT, 5 FEETLG CHEM RESU10H BATTERYEV CHARGERSE-EV-KIT-25K40-1Solar Edge single phaseEnergy HUB 7.6 kW Prism TechnologyInverter have IntegratedDC Disconnect safety switchand Arc Fault ProtectionINVERTERSOLAR EDGE ENERGY HUB 7.6 kWMODEL #SE 7600H-US(240V) 1P, 3W(3) #8AWG THWN/THWN-2(1) #8 AWG GND3/4" EMT, 2 FEET60A FUSED AC DISCONNECT,WITH 40A FUSESUTILITY AC DISCONNECT VISIBLE-OPENLOCKABLE, READILY ACCESSIBLENEMA3R120 / 240V60A FUSED AC DISCONNECT,WITH 40A FUSESUTILITY AC DISCONNECT VISIBLE-OPENLOCKABLE, READILY ACCESSIBLENEMA3R120 / 240V(3) #8AWG THWN/THWN-2(1) #8 AWG GND3/4" EMT, 2 FEET(3) #8AWG THWN/THWN-2(1) #8 AWG GND3/4" EMT, 2 FEET(3) #3/0AWG THWN/THWN-2(1) #4 AWG GND2" EMT, 2 FEET32A32AFROM INVERTER 2 TO PVBACKUP INTERFACE200A FUSED AC DISCONNECT,WITH 200A FUSESSERVICE AC DISCONNECT VISIBLE-OPENLOCKABLE, READILY ACCESSIBLENEMA3R120 / 240VNOTE:Battery Configuration: DC Coupled Battery #3BHybrid Inverter with a Transfer SwitchBattery Charging: Utility + Renewable GenerationOperation Mode: Backup Only*Battery Set to Non-Export SYSTEM LABELING DETAILPV 3.1PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044PV ARRAYJ BOXPV SUB-PANELACDISCONNECTMAIN SERVICEPANELMETER122221516207124Note: LABELS SHALL COMPLY WITH NEC 690“Labels shall be weatherproof, durable and permanently mounted”64APhotovoltaic Power SourceLABEL 1CAUTION: SOLAR CIRCUITLABEL 2WARNINGELECTRIC SHOCK HAZARDTHE DC CONDUCTORS OF THISPHOTOVOLTAIC SYSTEM AREUNDERGROUND AND MAY BE ENERGIZEDLABEL 3WARNINGELECTRIC SHOCK HAZARDIF GROUND FAULT IS INDICATEDNORMALLY GROUNDED CONDUCTORSMAY BE UNDERGROUND AND ENERGIZEDLABEL 4WARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE AND LOADSIDES MAY BE ENERGIZED IN THE OPENPOSITIONLABEL 5WARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE AND LOADSIDES MAY BE ENERGIZED IN THE OPENPOSITIONDC VOLTAGE IS ALWAYS PRESENTWHEN SOLAR MODULESARE EXPOSED TO SUNLIGHTLABEL 6WARNINGLABEL 7TURN OF PHOTOVOLTAICAC DISCONNECT PRIOR TOWORKING INSIDE PANELDO NOT DISCONNECTUNDER LOADLABEL 8MAIN PV SYSTEMDISCONNECTLABEL 9MAIN PV SYSTEMAC DISCONNECTLABEL 10LABEL 11CAUTIONLABEL 12SOLAR ELECTRIC SYSTEMCONNECTEDWARNING-LABEL 13 DUAL POWER SOURCESECOND SOURCE IS PV SYSTEMCAUTIONLABEL 14PHOTOVOLTAIC SYSTEM CIRCUITIS BACKFEDLABEL 15PHOTOVOLTAIC AC DISCONNECTMAXIMUM AC OPERATING CURRENTMAXIMUM AC OPERATING CURRENTPHOTOVOLTAICLABEL 16UTILITY AC DISCONNECTPHOTOVOLTAICLABEL 17DC DISCONNECTNOMINAL OPERATING AC VOLTAGENOMINAL OPERATING AC FREQUANCYMAXIMUM AC POWERMAXIMUM AC CURRENTMAX OCERCURRENT DEVICE RATINGFOR AC MODULE PROTECTIONLABEL 18LABEL 19PV SYSTEM DC DISCONNECTOPERATING CURRENTOPERATING VOLTAGEMAXIMUM SYSTEM VOLTAGESHORT CIRCUIT CURRENTCAUTIONLABEL 20PHOTOVOLTAIC SOURCECONNECTED***ALL LABELS = RED THERMOPLASTIC/REFLECTIVE , Permanently mounted240VSOLAR DISCONNECT20CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comSOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNTURN RAPID SHUTDOWNSWITCH TO THE"OFF" POSITION TOSHUT DOWN PV SYSTEMAND REDUCESHOCK HAZARDIN THE ARRAYSOLAR ELECTRICPV PANELSDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911 PV 3.2PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044PLACARDCONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comINSTALL 40A PVINSTALL 20A PVCAUTIONPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:SERVICE 1 OF 219792 Itea Ave Lakeville, MN 55044CAUTIONPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:SERVICE 2 OF 219792 Itea Ave Lakeville, MN 55044NWESNWESDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911PV SYSTEM DISCONNECTFOR UTILITY OPERATIONSOLAR INVERTERBACKUP INTERFACESERVICE POINT &UTILITY METERINGSOLAR PV ARRAYPV SYSTEM DISCONNECTFOR UTILITY OPERATIONBATTERYPV SYSTEM DISCONNECTFOR UTILITY OPERATIONSOLAR INVERTERBACKUP INTERFACESERVICE POINT &UTILITY METERINGSOLAR PV ARRAYPV SYSTEM DISCONNECTFOR UTILITY OPERATIONBATTERY PROPERTY PLANLEGENDMSPMain Service Panel................ Production MeterPM.................. AC DisconnectAC.........................PV 4.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044CONTRACTOR2xInverterIN....................................Wolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comMMMain Meter............................Xcel Energy Application#:04664911Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911BT..................................... BatteryBI...................... Backup InterfaceDRIVEWAY18'-5"99'-10"121'-5"112'-6"110'-4"35'-7"11'-11"23'-7"46'Hazel Nut Ave Itea AvePROPERTY LINEMSPMMACBIINACINACBTSCALE:1/32" = 1'-0" 180° 90° 270°0°SWNEDate Certified andSigned: 10/252021 ATTACHMENTLAYOUTPV 5.1PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDESIGN CRITERIAModules:Max Distributed Load: 3 PSFPOINT LOAD CALCULATION PER ARRAYModule Weight (lbs)# Of Modules41.9Total Module Weight (lbs)Rack Weight (lbs)Optimizers Weight (lbs)Total System Weight (lbs)# Of StandoffsMax Span Between Standoffs (in)Loading Per Standoff (lbs)Total Area (sq.ft.)Loading (PSF)2053.1410.6283.32547.021104823.1510782.36RAIL ATTACHMENTMODULES ON ROOFTruss 2 x 4 @ 24" O.C.4949Xcel Energy Application#:04664911Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENT1 Layer of .Plywood & Building FeltSolar Module6"AttachmentMODULES ON ROOFTruss 2 x 4 @ 24" O.C.COMPSHINGLEPrior to the commencement of work, the contractor shall verify the existing roof and framingconditions. Notify New@engineerinc.io.com of any Discrepancies prior to startingconstruction. Prior to the commencement of work, the contractor shall inspect framing forany damage such as water damage, cracked framing, etc. and These Plans are stampedfor structural code compliance of the roof framing supporting the proposed PV installationreference only. These plans are not stamped for water leakage. PV modules, racking, andattachment components must follow manufacturer guidelines and requirements.Attachments to be installed in a staggered orientation to properly distribute loads.1.86"3.05"0.25"Ø2.24"2.58"1"0.17"3.20"1.37"0.38"0.30"1.08"2.78"1.78"1.50"1.99"1.21"R 1.12"Ø0.33"R 0.82"12345SNAPNRACK, SPEEDSEAL FOOT, BASE, SEALING, SILVER/BLACKBOLT, FLANGE, SERRATED, 5/16IN-18 X 2IN, SSSNAPNRACK, RL UNIVERSAL, MOUNT SPRING, SSSNAPNRACK, ULTRA RAIL MOUNT THRU PRC, CLEAR/BLACKSNAPNRACK, ULTRA RAIL MOUNT TAPPED PRC, CLEAR/BLACK12345DESCRIPTIONITEMQTI11111MATERIALS:DESIGN LOAD (LBS):ULTIMATE LOAD (LBS):TORQUE SPECIFICATION:CERTIFICATION:WEIGHT (LBS):DIE CAST A380 ALUMINUM, 6000 SERIES ALUMINUM, STAINESS STEEL802 UP, 1333 DOWN, 357 SIDE2118 UP, 4006 DOWN, 1331 SIDE12 LB-FTUL 2703, FILE E359313; WIND-DRIVEN RAIN TEST FROM SUBJECT UL 25820.45OPTIONS:CLEAR/BLACKPARTS LISTSNAPNRACK, ULTRA RAIL SPEEDSEAL TM FOOTDrawn by:New@engineerinc.io 10/15/2021DATE:2x4PurlinXcel Energy Application#:04664911Date Certified andSigned: 10/252021 PV 5.2PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044ATTACHMENT DETAILCONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911 INVERTERDATA SHEETINVERTERDATA SHEETD 6.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911 POWER OPTIMIZERDATA SHEETD 7.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911 MODULEDATA SHEETD 8.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911 RACKINGDATA SHEETD 9.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911 ATTACHMENTDATA SHEETD 10.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911 D 11.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044CONTRACTORSURGE PROTECTIONWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911 D 12.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044CONTRACTORINVERTERCERTIFICATIONWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911 D 13.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comINVERTERCERTIFICATIONDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911 D 15.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044BATTERYDATA SHEETCONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application#:04664911Drawn by:New@engineerinc.io 10/15/2021DATE: D 14.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044BACKUP INTERFACEDATA SHEETCONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application#:04664911Drawn by:New@engineerinc.io 10/15/2021DATE: D 16.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044WITNESSTEST REPORTCONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application#:04664911Drawn by:New@engineerinc.io 10/15/2021DATE: D 17.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Nathan Lyke19792 Itea AveLakeville, MN 55044PV INSPECTIONCHECKLISTCONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comWolf RIver ElectricLakeville, MN 5504419792 Itea AveDrawn by:New@engineerinc.io 10/15/2021DATE:Xcel Energy Application#:04664911