HomeMy WebLinkAboutLA198289 18138 Garland Path App & FormsRESIDENTIAL BUILDING PERMIT APPLICATION
PAGE 2
OFFICE USE ONLY
BUILDING PERMIT TYPE REQUIRED INSPECTIONS
SINGLE FAMILY DWELLING BUILDING
DUPLEX AS BUILT
TOWNHOUSE UNITS BUILDING FINAL
DETACHED TOWN HOUSE UNIT DECK FOOTING
CONDO FIREPLACE
ACESSORY BUILDING FOOTING
REROOF FOUNDATION
RESIDE FRAMING
PORCH FRAMING
GARAGES
INSULATION
RES ADDN/REPAIR/RMDL
DECK
PORCH
GARAGES LATH
LOWER LEVEL FINISH LOWER LEVEL FINAL
ADDITION OTHER
FOUNDATION ONLY PORCH FOOTING
MISCELLANEOUS POURED WALL
DEMO SEPTIC TANK REMOVAL
MOVED SITE
MECHANICAL
CITY BUILDING VALUATION: $AIR TEST
FINAL
BUILDING PERMIT FEES ROUGH-IN
$PERMIT FEE PLUMBING
$PLAN CHECK FINAL
$SURCHARGE ROUGH-IN
$METRO SAC METER SIZE
$CITY WATER HOOKUP UNIT PRESSURE REDUCING VALVE
$CITY SEWER HOOKUP UNIT SEWER/WATER
$LANDSCAPE ESCROW SEWER/WATER
$TREE ESCROW FINAL
$MISC ESCROW STREET DRAINTILE
$PLUMBING BUILDING INFORMATION
$MECHANICAL TYPE OF CONSTRUCTION
$SEWER WATER ZONING
$OTHER CODE EDITION
$TOTAL FIRE SUPPRESSION SYSTEM
OCCUPANCY GROUP
APPROVED BY:
BUILDING INSPECTOR: Date:
PLUMBING/MECHANICAL
INSPECTOR: Date:
COMMENTS:
20195 Holyoke Avenue, Lakeville, MN 55044
952-985-4400 952-985-4499 fax
www.lakevillemn.gov
Sewer & Water Tie Card
Address:________________________________________
Contractor:______________________________________
Permit Number:__________________________________
Final Date:________________
Street Drain-Tile:______
Size of Water Service: 1”
Comments: AIRTEST SANITARY OVER 20’/2 FITTINGS
THIS CARD MUST BE COMPLETED AND ON-SITE AT TIME
OF SEWER & WATER INSPECTION
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Pronto Heating and AC Sable
Eden Prairie, MN 55344 Page 1
Project Report
General Project Information
Project Title:Sable
Designed By:Doug Dormanen
Project Date:7-12-2021
Client Name:Brandl Anderson
Company Name:Heating & Cooling Two Inc
Company Representative:Doug Dormanen
Design Data
Reference City:Minneapolis/St. Paul AP, Minnesota
Building Orientation:Front door faces East
Daily Temperature Range:Medium
Latitude:44 Degrees
Elevation:834 ft.
Altitude Factor:0.970
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter:-15 -12.38 n/a n/a 70 n/a
Summer:92 73 41%50%72 35
Check Figures
Total Building Supply CFM:926 CFM Per Square ft.:0.405
Square ft. of Room Area:2,289 Square ft. Per Ton:943
Volume (ft³):18,425
Building Loads
Total Heating Required Including Ventilation Air:54,503 Btuh 54.503 MBH
Total Sensible Gain:23,051 Btuh 79 %
Total Latent Gain:6,072 Btuh 21 %
Total Cooling Required Including Ventilation Air:29,123 Btuh 2.43 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\ ...\Brandl Anderson- Sable.rh9 Wednesday, November 24, 2021, 11:18 AM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Pronto Heating and AC Sable
Eden Prairie, MN 55344 Page 2
Miscellaneous Report
System 1 Lower Level
Input Data
Outdoor
Dry Bulb
Outdoor
Wet Bulb
Outdoor
Rel.Hum
Indoor
Rel.Hum
Indoor
Dry Bulb
Grains
Difference
Winter:-15 -12.38 100%n/a 70 n/a
Summer:92 73 41%50%72 35.16
Duct Sizing Inputs
Main Trunk Runouts
Calculate:Yes Yes
Use Schedule:Yes Yes
Roughness Factor:0.00300 0.01000
Pressure Drop:0.1000 in.wg./100 ft.0.1000 in.wg./100 ft.
Minimum Velocity:0 ft./min 0 ft./min
Maximum Velocity:900 ft./min 750 ft./min
Minimum Height:8 in.6 in.
Maximum Height:10 in.0 in.
Outside Air Data
Winter Summer
Infiltration Specified:0.220 AC/hr 0.110 AC/hr
68 CFM 34 CFM
Infiltration Actual:0.000 AC/hr 0.000 AC/hr
Above Grade Volume:Cu.ft.Cu.ft.X 18,425 X 18,425
0 Cu.ft./hr 0 Cu.ft./hr
X 0.0167 X 0.0167
Total Building Infiltration:0 CFM 0 CFM
Total Building Ventilation:154 CFM 154 CFM
---System 1---
Infiltration & Ventilation Sensible Gain Multiplier: 21.35 = (1.10 X 0.970 X 20.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier: 23.19 = (0.68 X 0.970 X 35.16 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 90.72 = (1.10 X 0.970 X 85.00 Winter Temp. Difference)
Winter Infiltration Specified:0.220 AC/hr (68 CFM), Construction: Semi-Tight
Summer Infiltration Specified:0.110 AC/hr (34 CFM), Construction: Semi-Tight
C:\ ...\Brandl Anderson- Sable.rh9 Wednesday, November 24, 2021, 11:18 AM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Pronto Heating and AC Sable
Eden Prairie, MN 55344 Page 3
Load Preview Report
Scope
Net
Ton
ft.²
/Ton Area
Sen
Gain
Lat
Gain
Net
Gain
Sen
Loss
Sys
Htg
CFM
Sys
Clg
CFM
Sys
Act
CFM
Duct
Size
Building 2.43 943 2,289 23,051 6,072 29,123 54,503 543 926 926
System 1 2.43 943 2,289 23,051 6,072 29,123 54,503 543 926 926 18x10
Ventilation 3,287 3,572 6,859 13,970
Zone 1 - Clg.: 19%, Htg.: 26%808 4,563 700 5,263 10,683 143 214 214 6x9
1-Lower Level 808 4,563 700 5,263 10,683 143 214 214 4--6
Zone 2 - Clg.: 51%, Htg.: 45%800 12,162 600 12,762 18,427 247 570 570 12x10
2-Main Level 160 1,329 0 1,329 4,486 60 62 62 1--6
4-Great Room/ Dining/ Kitchen 640 10,833 600 11,433 13,941 187 507 507 8--6
Zone 3 - Clg.: 30%, Htg.: 28%681 7,240 1,200 8,440 11,423 153 339 339 8x10
3-Upper Level 681 7,240 1,200 8,440 11,423 153 339 339 5--6
Sum of room airflows may be greater than system airflow because Sum of room airflows may be greater than system airflow because
system has multiple zones.
C:\ ...\Brandl Anderson- Sable.rh9 Wednesday, November 24, 2021, 11:18 AM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Pronto Heating and AC Sable
Eden Prairie, MN 55344 Page 4
System 1 Lower Level Summary Loads
Component
Description
Area
Quan
Sen
Loss
Lat
Gain
Sen
Gain
Total
Gain
4A-6-d: Glazing-Double pane low-e (e = 0.20 or less),
high performance, sliding glass door, e=0.05 on
surface 2, any frame, U-value 0.33, SHGC 0.33
249 6,985 0 8,944 8,944
11N: Door-Metal - Polystyrene Core, U-value 0.35 39 1,161 0 423 423
12E-0bm: Wall-Frame, R-19 insulation in 2 x 6 stud
cavity, no board insulation, brick finish, metal studs,
U-value 0.103
2456.8 21,509 0 4,150 4,150
15B0-10sf-8: Wall-Basement, , R-10 board insulation to
floor, no interior finish, 8' floor depth, U-value 0.05,
above grade U-value 0.083
1040 5,004 0 283 283
16CR-44: Roof/Ceiling-Under Attic with Insulation on Attic
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic with Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane, R-44 insulation, U-value 0.022
1321 2,470 0 1,308 1,308
21A-20: Floor-Basement, Concrete slab, any thickness, 2
or more feet below grade, no insulation below floor,
any floor cover, shortest side of floor slab is 20' wide,
U-value 0.027
808 1,854 0 0 0
20P-30: Floor-Over open crawl space or garage, Passive,
R-30 blanket insulation, any cover, U-value 0.035
521 1,550 0 274 274
Subtotals for structure:40,533 0 15,382 15,382
People:8 1,600 2,400 4,000
Equipment:900 1,200 2,100
Lighting:0 0 0
Ductwork:0 0 0 0
Infiltration: Winter CFM: 0, Summer CFM: 0 0 0 0 0
Ventilation: Winter CFM: 154, Summer CFM: 154 13,970 3,572 3,287 6,859
Exhaust: Winter CFM: 60, Summer CFM: 60
AED Excursion:0 0 782 782
System 1 Lower Level Load Totals:54,503 6,072 23,051 29,123
Check Figures
Supply CFM:926 CFM Per Square ft.:0.405
Square ft. of Room Area:2,289 Square ft. Per Ton:943
Volume (ft³):18,425
System Loads
Total Heating Required Including Ventilation Air:54,503 Btuh 54.503 MBH
Total Sensible Gain:23,051 Btuh 79 %
Total Latent Gain:6,072 Btuh 21 %
Total Cooling Required Including Ventilation Air:29,123 Btuh 2.43 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\ ...\Brandl Anderson- Sable.rh9 Wednesday, November 24, 2021, 11:18 AM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Pronto Heating and AC Sable
Eden Prairie, MN 55344 Page 5
System 1 Room Load Summary
No
Room
Name
Area
SF
Htg
Sens
Btuh
Min
Htg
CFM
Run
Duct
Size
Run
Duct
Vel
Clg
Sens
Btuh
Clg
Lat
Btuh
Min
Clg
CFM
Act
Sys
CFM
---Zone 1---
1 Lower Level 808 10,683 143 4-6 272 4,563 700 214 214
Zone 1 subtotal 808 10,683 143 4,563 700 214 214
---Zone 2---
2 Main Level 160 4,486 60 1-6 317 1,329 0 62 62
4 Great Room/
Dining/ Kitchen
640 13,941 187 8-6 323 10,833 600 507 507
Zone 2 subtotal 800 18,427 247 12,162 600 570 570
---Zone 3---
3 Upper Level 681 11,423 153 5-6 346 7,240 1,200 339 339
Zone 3 subtotal 681 11,423 153 7,240 1,200 339 339
Ventilation 13,970 3,287 3,572
System 1 total 2,289 54,503 543 23,051 6,072 926 926
System 1 Main Trunk Size:18x10 in.
Velocity:741 ft./min
Loss per 100 ft.:0.087 in.wg
Note: Since the system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains
at the room and zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended
to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which
the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the "Average Load
Procedure + Excursion" method.
Cooling System Summary
Cooling
Tons
Sensible/Latent
Split
Sensible
Btuh
Latent
Btuh
Total
Btuh
Net Required:2.43 79% / 21%23,051 6,072 29,123
Equipment Data
Heating System Cooling System
Type:Natural Gas Furnace Standard Air Conditioner
Model:
Indoor Model:
Brand:
Efficiency:0 AFUE 0 SEER
Sound:0 0
Capacity:0 Btuh 0 Btuh
Sensible Capacity:n/a 0 Btuh
Latent Capacity:n/a 0 Btuh
C:\ ...\Brandl Anderson- Sable.rh9 Wednesday, November 24, 2021, 11:18 AM