76 North Meadowbrook Drive
Scott E. Wyssling, PE Alpine, UT 84004
Jon P. Ward, SE, PE office (201) 874-3483
Gregory T. Elvestad, PE swyssling@wysslingconsulting.com
March 17, 2022
DBM Solar Design and Consulting
2650 Washington Boulevard Ogden, UT 84412 Re: Engineering Services Klecker Residence 20070 Harness Avenue, Lakeville MN 6.120 kW System To Whom It May Concern: We have received information regarding solar panel installation on the roof of the above referenced structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability
to support the additional loads imposed by the proposed solar system. A. Site Assessment Information
1. Site visit documentation identifying attic information including size and spacing of framing for the existing roof structure. 2. Design drawings of the proposed system including a site plan, roof plan and connection details for the solar panels. This information will be utilized for approval and construction
of the proposed system. B. Description of Structure:
Roof Framing: Prefabricated wood trusses at 24” on center. All truss members are constructed of 2x4 dimensional lumber. Roof Material: Composite Asphalt Shingles Roof Slope: 23 degrees
Attic Access: Accessible Foundation: Permanent C. Loading Criteria Used
• Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 PSF
• Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 psf
• Live Load = 20 psf (reducible) – 0 psf at locations of solar panels
• Ground Snow Load = 50 psf
• Wind Load based on ASCE 7-16
o Ultimate Wind Speed = 115 mph (based on Risk Category II)
o Exposure Category C
Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance with the 2020 Minnesota Residential Code, including provisions allowing existing structures to not
require strengthening if the new loads do not exceed existing design loads by 105% for gravity elements and 110% for seismic elements. This analysis indicates that the existing framing will support the additional panel loading without damage, if installed correctly.
Page 2 of 2
D. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent Ironridge installation manual. If during solar panel installation, the roof framing members appear unstable or deflect non-uniformly, our office should be notified before proceeding with the installation. 2. The maximum allowable withdrawal force for a 5/16” lag screw is 235 lbs per inch of penetration as
identified in the National Design Standards (NDS) of timber construction specifications. Based on a minimum penetration depth of 2½”, the allowable capacity per connection is greater than the design withdrawal force (demand). Considering the variable factors for the existing roof framing and installation tolerances, the connection using one 5/16” diameter lag screw with a minimum of 2½” embedment will be adequate and will include a sufficient factor of safety. 3. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of the roof, the panel supports shall be placed no greater than 48” on centers. 4. Panel supports connections shall be staggered to distribute load to adjacent framing members.
Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing roof system will adequately support the additional loading imposed by the solar system. This evaluation is in conformance with the 2020 Minnesota Residential Code, current industry standards, and is based on information supplied to us at the time of this report. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Very truly yours, Scott E. Wyssling Minnesota License No. 57927
VICINITY MAPAERIAL VIEW
SYSTEM SUMMARY
DESIGN CRITERIA
SCOPE OF WORK
GENERAL NOTES
OCCUPANCY & CONSTRUCTION TYPE
OCCUPANCY - R3
CONSTRUCTION - V-B
SHEET INDEX
PAGE NUMBER PAGE TITLE
PV01 TITLE PAGE
PV02 SITE PLAN
PV03 ONE LINE & ELECTRICAL
PV04 ARRAY & STRINGING DETAIL
PV05 LABEL PLAN
SPECS SPECSHEETS AND DOCUMENTS
APPLICABLE CODES
Set Reviewed By:
PV-041115-011207
RACKING:
WIND SPEED: 115 MPH
EXPOSURE CATEGORY: C
Roof Type: Asphalt/Composite Shingle
INVERTER: (1) SOLAREDGE SE6000H-US String Inverter 240VAC
MODULE: (17) Hanwha Q.PEAK DUO BLK G10+ 360W PV Module
OPTIMIZER: (17) SOLAREDGE P370 DC Optimizers
IRONRIDGE Roof Mounted PV System
A.ALL WORK SHALL COMPLY WITH STATE AND LOCAL CODES.
B.DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING
REQUIREMENTS.
C.PRIOR TO COMMENCMENT OF WORK, CONTRACTOR SHALL VERIFY EXISTING
CONDITIONS AND NOTIFY DBM OF ANY INCONSISTENCIES.
D.ALL EQUIPMENT SHALL BE INSTALLED AS SHOWN.
E.WARNINGS PER NEC 690.
F.WIRING SHALL NOT BE INSTALLED WITHIN 10 INCHES OF ROOF DECKING
EXCEPT WHERE DIRECTLY BELOW PV EQUIPMENT
DC System Size: 6.12kW
Roof Pitch: 5/12
Anchored on 48" centers using UL listed racking system
UV Resistant cable ties (not zip ties) used for permanent wire management in accordance
with NEC 110.2, 110.3(A-B), 300.4
Junction boxes mounted flush with racking.
2020 NATIONAL ELECTRICAL CODE (NEC)
2020 MINNESOATA FIRE CODE (MFC)
2020 MINNESOTA BUILDING CODE (MBC)
2020 MINNESOTA RESIDENTIAL CODE (MRC)
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
PV01
COVER PAGE
Signed 3/17/2022
3'
18"
40"
67.6"
ARRAY DETAIL
A B C D
AZIMUTH 180°90°
TILT ANGLE 23°23°
MODULE COUNT 2 15
ROOF SUPPORTS TRUSS = 2X4 @ 24" O.C.
SITE INDEX
#'
PHOTOVOLTAIC
MODULES
FIRECODE
SETBACKS
APPROXIMATE
DISTANCE TO
PROPERTY LINES
**PV Modules cannot be installed over vents
-WIRES LOCATED IN READILY ACCESSIBLE
LOCATIONS SHALL BE GUARDED PER NEC
690.31(A)
-24/7 unescorted keyless access is required
for ALL UTILITY EQUIPMENT
Secondary Method of Interconnecting is:
Supply Side Tap in MSP box
-The Production Meter and AC
Disconnect Should be Located Together
in a Readily Accessible Location Within
10' of the Main Service Meter
UNDERGROUND Service to home
from the NORTH WEST
Main Service Panel Located INTERIOR
N
*No clearance issue of over head power lines
MAIN SERVICE SHALL BE EQUIPPED
WITH A LABEL READING "GENERATION
SYSTEM CONNECT".
AC Inv
12"
M
MP
12"
6"
(E) WALL
Panels
10'
*Distance between equipment not to Scale
Installer's Contact:
POWERFULLY GREEN
612-208-5628
2380 Watertown Rd.
Long Lake, MN 55356
Contractor ID: BC773271
UTILITY METERINVERTER/DC DISCONNECT
VISIBLE, LOCKABLE,
LABELED AC DISCONNECT
MSP (INTERIOR)
TRANSFORMER
LIGHT POLE
UNDERGROUND SERVICE ENTRANCE
No Clearance Issues
CLOSEST CROSS STREET
60'
100'
145'
86'
145'
DRIVEWAY
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
PV02
PROPERTY DETAIL
Signed 3/17/2022
+-
JUNCTION BOX
+-
ELECTRICAL NOTES
#10 PV WIRE #6 BARE COPPER EGC
1 2
3
A.ALL COMPONENTS SHALL COMPLY WITH NECAS AMENDED.B.PHASE CONDUCTORS SHALL BE IDENTIFIED
C.ALL WIRES SHALL BE PROVIDED WITH STRAIN RELIEF UPON ENTRY INTO BOXES, REFER TO MANUFACTURERS INSTALLATION MANUAL FOR REQUIRED TORQUE VALUES
D.THE DC GEC, IF USED, SHALL BE CONTINUOUS FROM THE INVERTER GROUND BUS TO THE MAIN SERVICE GROUNDING ELECTRODE SYSTEME.ATTACHMENT TO GROUND ELECTRODE SHALL USE IRREVERSIBLE CLAMP.
F.ALL EXPOSED METAL PARTS SHALL BE GROUNDED USING TIN PLATED COPPER LAY IN LUGS OR GROUNDING CLIPS LISTED FOR THE PURPOSE
G.MIN #10 BARE COPPER EGC AT SOURCE CIRCUITS SHALL BE ROUTED SECURELY TO MOUNTING HARDWARE THAT PROTECTS FROM PHYSICAL DAMAGE
H.#6 FOR AREAS THAT MAY BE SUBJECT TO DAMAGE
I.BOTH ENDS OF ALL METALLIC CONDUIT SHALL BE BONDED PER NEC250J.INTERCONNECTION PER NEC690
K.ALL WIRES WILL BE RATED AT THHN/THWN-2
L.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONSM.PV PRODUCTION TERMINATED IN LOAD SIDES OF ALL AC DISCONNECTS
4
RAPID
SHUTDOWN
DEVICE
DC DISCONNECT
MODULES & OPTIMIZERS IN A SERIES STRING8
MODULES & OPTIMIZERS IN A SERIES STRING9
*DC OPTIMIZERS OUTPUT 1Voc PER MODULE & LIMIT VOLTAGE
TO MAX POWER POINT VOLTAGE OF THE INVERTER*
INTEGRATED ARC FAULT
PROTECTION AND RAPID
SHUTDOWN FOR NEC 2011, 2014,
2017 AND 2020 690.11 AND 690.12
·All Exposed PV rooftop conductors that are not located under the array modules, shall be installed in a listed raceway, and shall include listed junction
boxes at both ends of the raceway to transition from exposed conductors to the listed raceways. In Accordance with NEC 690.31(A) & (B)**
·ROMEX AMPACITY LIMITED TO 60° VALUES. IF USED, SIZE ACCORDING TO NEC TABLE 310.15
·DC Conduit must be marked in accordance with NEC 690.31. Labeling must be every 10' and must comply with NEC 690.31. See PV05 for Label plan
·ALL DC Conductors must be protected with metal conduit
FUSED AC DISCONNECT60A 120/240V
40A FUSES
PHOTOVOLTAIC AC OUTPUT LABEL
AC OUTPUT CURRENT 25A
NOMINAL AC VOLTAGE 240V
CONDUCTOR SCHEDULE WITH NEC ELECTRICAL CALCULATIONS
ID CONDUCTOR CONDUIT NO. OF CNDRS.
IN CNDT.
RATED
AMPS EGC TEMP. CORR.
FACTOR
FILL ADJ.
FACTOR
CONT.
CURRENT
MAX.
CURRENT
BASE
AMPACITY
DERATED
AMPACITY
WIRE RUN
DISTANCE
1 PV WIRE FREE AIR N/A 15.00A #6 BARE COPPER 0.96 N/A 15.00A 18.75A 35A 33.60A 20ft
2 10 AWG THWN-2 CU 3/4" DIA EMT 4 15.00A 10 AWG THWN-2 CU 0.96 0.8 15.00A 18.75A 35A 26.88A 20ft
3 8 AWG THWN-2 CU 3/4" DIA EMT 3 25A 10 AWG THWN-2 CU 0.96 1.0 25.00A 31.25A 50A 48.00A 5ft
4 6 AWG THWN-2 CU 3/4" DIA EMT 3 25A 8 AWG THWN-2 CU 0.96 1.0 25.00A 31.25A 65A 62.40A 5ft
INVERTER SPECIFICATIONS
MANUFACTURER SolarEdge
MODEL SE6000H-US (240V)
MAX DC INPUT VOLTAGE 480 V
MAX OUTPUT POWER 6000 W
NOMINAL AC OUTPUT VOLTAGE 240 V
NOMINAL AC OUTPUT CURRENT 25 AMAX FUSE (OCPD)35 A
SE6000H-US
MAX DC VOLTAGE =
MAX DC CIRCUIT CURRENT =
MAXIMUM RATED DC OUTPUT CURRENT OF DC TO DC
CONVERTER (IF INSTALLED) =
DC DISCONNECT CALCS
480V
15A
PV LOAD CALCULATIONS: SUPPLY SIDE TIE-IN
200A RATED FEEDER WIRES
200A ÷ 1.25 =160A
160A (FEEDER WIRES ALLOWABLE SOLAR)
160A AVAILABLE FOR PV
705.12(A) & 690.59
TYPICAL SUPPLY SIDE
CONNECTION (TAP)
NEC 705.12 (A)TO EXISTING LOADS
UTILITY METER
#6 CU GEC
#XX XXX XXX
G
MAINOCPD
MAIN SERVICE PANEL
200A MAIN BUS
200A MAIN OCPD
200A
30A
Installer's Contact:
POWERFULLY GREEN
612-208-5628
2380 Watertown Rd.
Long Lake, MN 55356
Contractor ID: BC773271
DER RATING:
6.12 kW DC
6.0 kW AC
Secondary Method of Interconnecting is:
Supply Side Tap in MSP
Solar Edge SE6000H-US
1-ph Utility Interactive Inverter
UL 1741 SA Certified and readily accessible
UTILITY AC DISCONNECTShall be Visible-Open Type, Lockable
UTILITY METERBi-Directional by Xcel Energy1-ph 120/240v - 200A self contained
PV MODULE SPECIFICATIONSMANUFACTURERHanwha Q-Cells
MODEL Q.PEAK DUO BLK G10+
360WMAX POWER-POINT CURRENT (Imp)10.27AMAX POWER-POINT VOLTAGE (Vmp)34.31VOPEN CIRCUIT VOLTAGE (Voc)41.18VSHORT CIRCUIT CURRENT (Isc)11.04AMAX SERIES FUSE (OCPD)20AMAX POWER (Pmax)360WMAX VOLTAGE (Vdc)1000V
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
PV03
1LD/ ELECTRICAL DETAIL
ATTACHMENT SPAN AND SUPPORT PLACEMENT ACCORDING TO MANUFACTURER INSTALLATION MANUAL
+ -+ -+ -+ -
Diagram: Grid-Tied System w/ Optimizers
+ -+ -+ -
PV Source Circuit
To Inverter
Junction Box
#10 PV Wire
Equipment Grounding Conductor
Solar Edge DC Optimizers
48" MAX rail span with staggered attachments to distribute weight across support framing
RAIL MOUNT
TERMINAL BLOCK
HEYCO-TITE UL LISTED/RECOGNIZED AND
CSA CERTIFIED LIQUID TIGHT CORDGRIPS
Photovoltaic Array String Detail
(9) Modules String A
(8) Modules String B
GROUNDING DETAIL
JUNCTION BOX DETAIL
*See Attached Data Sheets For More Information
STRINGING DETAIL
Attachment Diagram
Rail PV Module
Module Overhang Cantilever = 33% of MAX rail span
25%
25%
50%
PV ATTIC DETAIL
ATTACHMENT DETAIL
2.5"
4"ROOF SURFACE FLASHING
5/16" STAINLESS STEEL LAG BOLT
AND FLAT WASHER
SOLAR MODULE
5'5"
4'
4"
4" BETWEEN ROOF
AND PANELS
JUNCTION BOX
ATTACHMENT DETAIL
B
A
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
PV04
ARRAY/STRINGING DETAIL
LOCATION: (1) COMBINER BOX (2) JUNCTION BOX
LOCATION: STRING INVERTER (IF USED)
LOCATION: MAIN SERVICE LOCATION: (1) MAIN SERVICE
(3) BREAKER PANEL (4) DISCONNECT SWITCH LOCATION: DC CONDUIT (EVERY 10 FEET)
(REFLECTIVE CONDUIT LABEL)
PER NEC 690.31(B)(1-4)LOCATION: (1) MAIN SERVICE (5) INVERTER (IF USED)
(2) AC COMBINER PANEL MAIN SERVICE & ALL BACK FED PANEL BOARDS
LOCATION: (1) MAIN SERVICE
(2) AC COMBINER PANEL
(3) ALL BACKFED PANELS
LABEL NOTES
4.5"4.5"4.5"
4.5"
3"
4.5"
B
MAIN SERVICE PANEL
FOR ILLUSTRATION ONLY
(NOT ACTUAL MSP)
PV SUB PANEL
(IF USED)
AC
DISCONNECT
(IF USED)
STRING
INVERTER
(IF USED)
JUNCTION
BOX
(IF USED)
A
A
A AC
D
E
H
G
H
A
F
I
I
J
FOR MICRO INVERTERS ONLY
(NO KNIFE SWITCH DISCONNECT)
F
4.5"
PHOTOVOLTAIC AC DISCONNECT
MAXIMUM AC OPERATING CURRENT:
NOMINAL AC OPERATING VOLTAGE:240V
K
WARNING
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING: DUAL POWER SOURCE
SECOND SOURCE IS A PHOTOVOLTAIC SYSTEM
"RAPID SHUTDOWN
SWITCH FOR SOLAR PV SYSTEM"
"PHOTOVOLTAIC SYSTEM EQUIPPED
WITH RAPID SHUTDOWN"
WARNING:
DO NOT ADD ADDITIONAL CIRCUITS TO PANEL
CAUTION:
PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED
WARNING:
INVERTER OUTPUT CONNECTION
DO NOT RELOCATE SOLAR BREAKER
A.RED BACKGROUND WITH WHITE LETTERING
OR YELLOW / ORANGE BACKGROUND WITH
BLACK LETTERING
B.MINIMUM 3/8" LETTER HEIGHT
C.ALL CAPITAL LETTERS
D.NON BOLD TEXT
E.MATERIAL SUITABLE FOR ENVIRONMENT
F.SIGNS MUST BE REFLECTIVE
G.SIGNS MUST NOT BE HAND WRITTEN
K
A C D
E F G H
I J
J
J
"PHOTOVOLTAIC SYSTEM
CONNECTED"
LYELLOW BACKGROUND WITH BLACK TEXT
L
MAX DC VOLTAGE =
MAX DC CIRCUIT CURRENT =
MAXIMUM RATED DC OUTPUT CURRENT OF DC TO DC
CONVERTER (IF INSTALLED) =
DC DISCONNECT CALCS
480V
15A
25A
30A
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
(YELLOW WITH BLACK LETTERING)K
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
PV05
LABEL PLAN
PHOTOVOLTAIC SYSTEM SITE PLACARD
CAUTIONTHIS SERVICE SUPPLIED BY ALTERNATIVE POWER SOURCES WITH
DISCONNECTS LOCATED AS SHOWN
UTILITY METER
INVERTER/DC DISCONNECT
VISIBLE, LOCKABLE,
LABELED AC DISCONNECT
MSP (INTERIOR)
UNDERGROUND SERVICE ENTRANCE
No Clearance IssuesN
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
PV05-1
SITE-PLACARD
PICTURES
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
PICS
PICTURES
SOLAR MODULE SPECSHEET
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
SPECS
SPEC SHEETS
INVERTER SPECSHEET
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
SPECS
SPEC SHEETS
OPTIMIZER SPECSHEET
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
SPECS
SPEC SHEETS
RACKING SPECSHEET
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BELLO NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
TO OTHERS OUTSIDE RECIPIENTS
ORGANIZATION, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF DBM SOLAR DESIGN
AND CONSULTING COMPANY, LLC
DBM SOLAR DESIGN AND
CONSULTING COMPANY, LLC
P: (801) 690-4873
E: SUPPORT@DBMSOLAR.COM
WWW.DBMSOLAR.COM
PROJECT #
DATE:
DESIGNED BY:
N. Flowers
SHEET NAME:
PAGE #REVISION:
0
2022-AVOLTA
3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St,
Orem, UT 84097
P: (801) 783-5959
SPECS
SPEC SHEETS