HomeMy WebLinkAboutLA200437-Approved Klecker_Design_20220318 76 North Meadowbrook Drive Scott E. Wyssling, PE Alpine, UT 84004 Jon P. Ward, SE, PE office (201) 874-3483 Gregory T. Elvestad, PE swyssling@wysslingconsulting.com March 17, 2022 DBM Solar Design and Consulting 2650 Washington Boulevard Ogden, UT 84412 Re: Engineering Services Klecker Residence 20070 Harness Avenue, Lakeville MN 6.120 kW System To Whom It May Concern: We have received information regarding solar panel installation on the roof of the above referenced structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability to support the additional loads imposed by the proposed solar system. A. Site Assessment Information 1. Site visit documentation identifying attic information including size and spacing of framing for the existing roof structure. 2. Design drawings of the proposed system including a site plan, roof plan and connection details for the solar panels. This information will be utilized for approval and construction of the proposed system. B. Description of Structure: Roof Framing: Prefabricated wood trusses at 24” on center. All truss members are constructed of 2x4 dimensional lumber. Roof Material: Composite Asphalt Shingles Roof Slope: 23 degrees Attic Access: Accessible Foundation: Permanent C. Loading Criteria Used • Dead Load o Existing Roofing and framing = 7 psf o New Solar Panels and Racking = 3 psf o TOTAL = 10 PSF • Dead Load o Existing Roofing and framing = 7 psf o New Solar Panels and Racking = 3 psf o TOTAL = 10 psf • Live Load = 20 psf (reducible) – 0 psf at locations of solar panels • Ground Snow Load = 50 psf • Wind Load based on ASCE 7-16 o Ultimate Wind Speed = 115 mph (based on Risk Category II) o Exposure Category C Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance with the 2020 Minnesota Residential Code, including provisions allowing existing structures to not require strengthening if the new loads do not exceed existing design loads by 105% for gravity elements and 110% for seismic elements. This analysis indicates that the existing framing will support the additional panel loading without damage, if installed correctly. Page 2 of 2 D. Solar Panel Anchorage 1. The solar panels shall be mounted in accordance with the most recent Ironridge installation manual. If during solar panel installation, the roof framing members appear unstable or deflect non-uniformly, our office should be notified before proceeding with the installation. 2. The maximum allowable withdrawal force for a 5/16” lag screw is 235 lbs per inch of penetration as identified in the National Design Standards (NDS) of timber construction specifications. Based on a minimum penetration depth of 2½”, the allowable capacity per connection is greater than the design withdrawal force (demand). Considering the variable factors for the existing roof framing and installation tolerances, the connection using one 5/16” diameter lag screw with a minimum of 2½” embedment will be adequate and will include a sufficient factor of safety. 3. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of the roof, the panel supports shall be placed no greater than 48” on centers. 4. Panel supports connections shall be staggered to distribute load to adjacent framing members. Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing roof system will adequately support the additional loading imposed by the solar system. This evaluation is in conformance with the 2020 Minnesota Residential Code, current industry standards, and is based on information supplied to us at the time of this report. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Very truly yours, Scott E. Wyssling Minnesota License No. 57927 VICINITY MAPAERIAL VIEW SYSTEM SUMMARY DESIGN CRITERIA SCOPE OF WORK GENERAL NOTES OCCUPANCY & CONSTRUCTION TYPE OCCUPANCY - R3 CONSTRUCTION - V-B SHEET INDEX PAGE NUMBER PAGE TITLE PV01 TITLE PAGE PV02 SITE PLAN PV03 ONE LINE & ELECTRICAL PV04 ARRAY & STRINGING DETAIL PV05 LABEL PLAN SPECS SPECSHEETS AND DOCUMENTS APPLICABLE CODES Set Reviewed By: PV-041115-011207 RACKING: WIND SPEED: 115 MPH EXPOSURE CATEGORY: C Roof Type: Asphalt/Composite Shingle INVERTER: (1) SOLAREDGE SE6000H-US String Inverter 240VAC MODULE: (17) Hanwha Q.PEAK DUO BLK G10+ 360W PV Module OPTIMIZER: (17) SOLAREDGE P370 DC Optimizers IRONRIDGE Roof Mounted PV System A.ALL WORK SHALL COMPLY WITH STATE AND LOCAL CODES. B.DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS. C.PRIOR TO COMMENCMENT OF WORK, CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND NOTIFY DBM OF ANY INCONSISTENCIES. D.ALL EQUIPMENT SHALL BE INSTALLED AS SHOWN. E.WARNINGS PER NEC 690. F.WIRING SHALL NOT BE INSTALLED WITHIN 10 INCHES OF ROOF DECKING EXCEPT WHERE DIRECTLY BELOW PV EQUIPMENT DC System Size: 6.12kW Roof Pitch: 5/12 Anchored on 48" centers using UL listed racking system UV Resistant cable ties (not zip ties) used for permanent wire management in accordance with NEC 110.2, 110.3(A-B), 300.4 Junction boxes mounted flush with racking. 2020 NATIONAL ELECTRICAL CODE (NEC) 2020 MINNESOATA FIRE CODE (MFC) 2020 MINNESOTA BUILDING CODE (MBC) 2020 MINNESOTA RESIDENTIAL CODE (MRC) CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 PV01 COVER PAGE Signed 3/17/2022 3' 18" 40" 67.6" ARRAY DETAIL A B C D AZIMUTH 180°90° TILT ANGLE 23°23° MODULE COUNT 2 15 ROOF SUPPORTS TRUSS = 2X4 @ 24" O.C. SITE INDEX #' PHOTOVOLTAIC MODULES FIRECODE SETBACKS APPROXIMATE DISTANCE TO PROPERTY LINES **PV Modules cannot be installed over vents -WIRES LOCATED IN READILY ACCESSIBLE LOCATIONS SHALL BE GUARDED PER NEC 690.31(A) -24/7 unescorted keyless access is required for ALL UTILITY EQUIPMENT Secondary Method of Interconnecting is: Supply Side Tap in MSP box -The Production Meter and AC Disconnect Should be Located Together in a Readily Accessible Location Within 10' of the Main Service Meter UNDERGROUND Service to home from the NORTH WEST Main Service Panel Located INTERIOR N *No clearance issue of over head power lines MAIN SERVICE SHALL BE EQUIPPED WITH A LABEL READING "GENERATION SYSTEM CONNECT". AC Inv 12" M MP 12" 6" (E) WALL Panels 10' *Distance between equipment not to Scale Installer's Contact: POWERFULLY GREEN 612-208-5628 2380 Watertown Rd. Long Lake, MN 55356 Contractor ID: BC773271 UTILITY METERINVERTER/DC DISCONNECT VISIBLE, LOCKABLE, LABELED AC DISCONNECT MSP (INTERIOR) TRANSFORMER LIGHT POLE UNDERGROUND SERVICE ENTRANCE No Clearance Issues CLOSEST CROSS STREET 60' 100' 145' 86' 145' DRIVEWAY CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 PV02 PROPERTY DETAIL Signed 3/17/2022 +- JUNCTION BOX +- ELECTRICAL NOTES #10 PV WIRE #6 BARE COPPER EGC 1 2 3 A.ALL COMPONENTS SHALL COMPLY WITH NECAS AMENDED.B.PHASE CONDUCTORS SHALL BE IDENTIFIED C.ALL WIRES SHALL BE PROVIDED WITH STRAIN RELIEF UPON ENTRY INTO BOXES, REFER TO MANUFACTURERS INSTALLATION MANUAL FOR REQUIRED TORQUE VALUES D.THE DC GEC, IF USED, SHALL BE CONTINUOUS FROM THE INVERTER GROUND BUS TO THE MAIN SERVICE GROUNDING ELECTRODE SYSTEME.ATTACHMENT TO GROUND ELECTRODE SHALL USE IRREVERSIBLE CLAMP. F.ALL EXPOSED METAL PARTS SHALL BE GROUNDED USING TIN PLATED COPPER LAY IN LUGS OR GROUNDING CLIPS LISTED FOR THE PURPOSE G.MIN #10 BARE COPPER EGC AT SOURCE CIRCUITS SHALL BE ROUTED SECURELY TO MOUNTING HARDWARE THAT PROTECTS FROM PHYSICAL DAMAGE H.#6 FOR AREAS THAT MAY BE SUBJECT TO DAMAGE I.BOTH ENDS OF ALL METALLIC CONDUIT SHALL BE BONDED PER NEC250J.INTERCONNECTION PER NEC690 K.ALL WIRES WILL BE RATED AT THHN/THWN-2 L.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONSM.PV PRODUCTION TERMINATED IN LOAD SIDES OF ALL AC DISCONNECTS 4 RAPID SHUTDOWN DEVICE DC DISCONNECT MODULES & OPTIMIZERS IN A SERIES STRING8 MODULES & OPTIMIZERS IN A SERIES STRING9 *DC OPTIMIZERS OUTPUT 1Voc PER MODULE & LIMIT VOLTAGE TO MAX POWER POINT VOLTAGE OF THE INVERTER* INTEGRATED ARC FAULT PROTECTION AND RAPID SHUTDOWN FOR NEC 2011, 2014, 2017 AND 2020 690.11 AND 690.12 ·All Exposed PV rooftop conductors that are not located under the array modules, shall be installed in a listed raceway, and shall include listed junction boxes at both ends of the raceway to transition from exposed conductors to the listed raceways. In Accordance with NEC 690.31(A) & (B)** ·ROMEX AMPACITY LIMITED TO 60° VALUES. IF USED, SIZE ACCORDING TO NEC TABLE 310.15 ·DC Conduit must be marked in accordance with NEC 690.31. Labeling must be every 10' and must comply with NEC 690.31. See PV05 for Label plan ·ALL DC Conductors must be protected with metal conduit FUSED AC DISCONNECT60A 120/240V 40A FUSES PHOTOVOLTAIC AC OUTPUT LABEL AC OUTPUT CURRENT 25A NOMINAL AC VOLTAGE 240V CONDUCTOR SCHEDULE WITH NEC ELECTRICAL CALCULATIONS ID CONDUCTOR CONDUIT NO. OF CNDRS. IN CNDT. RATED AMPS EGC TEMP. CORR. FACTOR FILL ADJ. FACTOR CONT. CURRENT MAX. CURRENT BASE AMPACITY DERATED AMPACITY WIRE RUN DISTANCE 1 PV WIRE FREE AIR N/A 15.00A #6 BARE COPPER 0.96 N/A 15.00A 18.75A 35A 33.60A 20ft 2 10 AWG THWN-2 CU 3/4" DIA EMT 4 15.00A 10 AWG THWN-2 CU 0.96 0.8 15.00A 18.75A 35A 26.88A 20ft 3 8 AWG THWN-2 CU 3/4" DIA EMT 3 25A 10 AWG THWN-2 CU 0.96 1.0 25.00A 31.25A 50A 48.00A 5ft 4 6 AWG THWN-2 CU 3/4" DIA EMT 3 25A 8 AWG THWN-2 CU 0.96 1.0 25.00A 31.25A 65A 62.40A 5ft INVERTER SPECIFICATIONS MANUFACTURER SolarEdge MODEL SE6000H-US (240V) MAX DC INPUT VOLTAGE 480 V MAX OUTPUT POWER 6000 W NOMINAL AC OUTPUT VOLTAGE 240 V NOMINAL AC OUTPUT CURRENT 25 AMAX FUSE (OCPD)35 A SE6000H-US MAX DC VOLTAGE = MAX DC CIRCUIT CURRENT = MAXIMUM RATED DC OUTPUT CURRENT OF DC TO DC CONVERTER (IF INSTALLED) = DC DISCONNECT CALCS 480V 15A PV LOAD CALCULATIONS: SUPPLY SIDE TIE-IN 200A RATED FEEDER WIRES 200A ÷ 1.25 =160A 160A (FEEDER WIRES ALLOWABLE SOLAR) 160A AVAILABLE FOR PV 705.12(A) & 690.59 TYPICAL SUPPLY SIDE CONNECTION (TAP) NEC 705.12 (A)TO EXISTING LOADS UTILITY METER #6 CU GEC #XX XXX XXX G MAINOCPD MAIN SERVICE PANEL 200A MAIN BUS 200A MAIN OCPD 200A 30A Installer's Contact: POWERFULLY GREEN 612-208-5628 2380 Watertown Rd. Long Lake, MN 55356 Contractor ID: BC773271 DER RATING: 6.12 kW DC 6.0 kW AC Secondary Method of Interconnecting is: Supply Side Tap in MSP Solar Edge SE6000H-US 1-ph Utility Interactive Inverter UL 1741 SA Certified and readily accessible UTILITY AC DISCONNECTShall be Visible-Open Type, Lockable UTILITY METERBi-Directional by Xcel Energy1-ph 120/240v - 200A self contained PV MODULE SPECIFICATIONSMANUFACTURERHanwha Q-Cells MODEL Q.PEAK DUO BLK G10+ 360WMAX POWER-POINT CURRENT (Imp)10.27AMAX POWER-POINT VOLTAGE (Vmp)34.31VOPEN CIRCUIT VOLTAGE (Voc)41.18VSHORT CIRCUIT CURRENT (Isc)11.04AMAX SERIES FUSE (OCPD)20AMAX POWER (Pmax)360WMAX VOLTAGE (Vdc)1000V CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 PV03 1LD/ ELECTRICAL DETAIL ATTACHMENT SPAN AND SUPPORT PLACEMENT ACCORDING TO MANUFACTURER INSTALLATION MANUAL + -+ -+ -+ - Diagram: Grid-Tied System w/ Optimizers + -+ -+ - PV Source Circuit To Inverter Junction Box #10 PV Wire Equipment Grounding Conductor Solar Edge DC Optimizers 48" MAX rail span with staggered attachments to distribute weight across support framing RAIL MOUNT TERMINAL BLOCK HEYCO-TITE UL LISTED/RECOGNIZED AND CSA CERTIFIED LIQUID TIGHT CORDGRIPS Photovoltaic Array String Detail (9) Modules String A (8) Modules String B GROUNDING DETAIL JUNCTION BOX DETAIL *See Attached Data Sheets For More Information STRINGING DETAIL Attachment Diagram Rail PV Module Module Overhang Cantilever = 33% of MAX rail span 25% 25% 50% PV ATTIC DETAIL ATTACHMENT DETAIL 2.5" 4"ROOF SURFACE FLASHING 5/16" STAINLESS STEEL LAG BOLT AND FLAT WASHER SOLAR MODULE 5'5" 4' 4" 4" BETWEEN ROOF AND PANELS JUNCTION BOX ATTACHMENT DETAIL B A CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 PV04 ARRAY/STRINGING DETAIL LOCATION: (1) COMBINER BOX (2) JUNCTION BOX LOCATION: STRING INVERTER (IF USED) LOCATION: MAIN SERVICE LOCATION: (1) MAIN SERVICE (3) BREAKER PANEL (4) DISCONNECT SWITCH LOCATION: DC CONDUIT (EVERY 10 FEET) (REFLECTIVE CONDUIT LABEL) PER NEC 690.31(B)(1-4)LOCATION: (1) MAIN SERVICE (5) INVERTER (IF USED) (2) AC COMBINER PANEL MAIN SERVICE & ALL BACK FED PANEL BOARDS LOCATION: (1) MAIN SERVICE (2) AC COMBINER PANEL (3) ALL BACKFED PANELS LABEL NOTES 4.5"4.5"4.5" 4.5" 3" 4.5" B MAIN SERVICE PANEL FOR ILLUSTRATION ONLY (NOT ACTUAL MSP) PV SUB PANEL (IF USED) AC DISCONNECT (IF USED) STRING INVERTER (IF USED) JUNCTION BOX (IF USED) A A A AC D E H G H A F I I J FOR MICRO INVERTERS ONLY (NO KNIFE SWITCH DISCONNECT) F 4.5" PHOTOVOLTAIC AC DISCONNECT MAXIMUM AC OPERATING CURRENT: NOMINAL AC OPERATING VOLTAGE:240V K WARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION WARNING: PHOTOVOLTAIC POWER SOURCE WARNING: DUAL POWER SOURCE SECOND SOURCE IS A PHOTOVOLTAIC SYSTEM "RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM" "PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN" WARNING: DO NOT ADD ADDITIONAL CIRCUITS TO PANEL CAUTION: PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED WARNING: INVERTER OUTPUT CONNECTION DO NOT RELOCATE SOLAR BREAKER A.RED BACKGROUND WITH WHITE LETTERING OR YELLOW / ORANGE BACKGROUND WITH BLACK LETTERING B.MINIMUM 3/8" LETTER HEIGHT C.ALL CAPITAL LETTERS D.NON BOLD TEXT E.MATERIAL SUITABLE FOR ENVIRONMENT F.SIGNS MUST BE REFLECTIVE G.SIGNS MUST NOT BE HAND WRITTEN K A C D E F G H I J J J "PHOTOVOLTAIC SYSTEM CONNECTED" LYELLOW BACKGROUND WITH BLACK TEXT L MAX DC VOLTAGE = MAX DC CIRCUIT CURRENT = MAXIMUM RATED DC OUTPUT CURRENT OF DC TO DC CONVERTER (IF INSTALLED) = DC DISCONNECT CALCS 480V 15A 25A 30A TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS (YELLOW WITH BLACK LETTERING)K CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 PV05 LABEL PLAN PHOTOVOLTAIC SYSTEM SITE PLACARD CAUTIONTHIS SERVICE SUPPLIED BY ALTERNATIVE POWER SOURCES WITH DISCONNECTS LOCATED AS SHOWN UTILITY METER INVERTER/DC DISCONNECT VISIBLE, LOCKABLE, LABELED AC DISCONNECT MSP (INTERIOR) UNDERGROUND SERVICE ENTRANCE No Clearance IssuesN CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 PV05-1 SITE-PLACARD PICTURES CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 PICS PICTURES SOLAR MODULE SPECSHEET CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 SPECS SPEC SHEETS INVERTER SPECSHEET CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 SPECS SPEC SHEETS OPTIMIZER SPECSHEET CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 SPECS SPEC SHEETS RACKING SPECSHEET CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BELLO NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC DBM SOLAR DESIGN AND CONSULTING COMPANY, LLC P: (801) 690-4873 E: SUPPORT@DBMSOLAR.COM WWW.DBMSOLAR.COM PROJECT # DATE: DESIGNED BY: N. Flowers SHEET NAME: PAGE #REVISION: 0 2022-AVOLTA 3/17/2022SITE INFORMATION:Patrick Klecker20070 Harness AveLakeville, MN 55044DC SYSTEM SIZE:6.12 kW1640 S State St, Orem, UT 84097 P: (801) 783-5959 SPECS SPEC SHEETS