HomeMy WebLinkAboutLA200293-Approved Raway_Plans_V2. Engineer StampedN123'-4"84'-2"
85'-4"123'-7"15'-2"36'-11"18'-7"38'-0"RevRAWAY RESIDENCE
DateDescriptionREVISIONSSignature with SealProject Name &AddressSheet SizeSheet NumberANSI B11" X 17"PV 0.0Sheet NameDRAWN BY2010 E HENNEPIN AVE, BLDG 6 BOX 7
MINNEAPOLIS, MINNESOTA, 55413
(509)304-4658
LICENSE #BC708267/EA714757
20501 GRANVILLE LN , LAKEVILLE, MINNESOTA 55044
PHONE: 424-285-5369
EMAIL: pm33@greensoltech.com
APN: 224540004290 SHEET INDEX:PV 0.0: COVER SHEETPV 1.0: SITE PLANS 1.1: MOUNT DETAILSE 1.1: 3-LINE DIAGRAME 1.2: NOTESE 1.3: WARNING LABELS-EQUIPMENT SPEC SHEETCOVER SHEETSCALE: NTS2SATELLITE VIEWPV 0.0SCALE: NTS3VICINITY MAPPV 0.0SCALE: 1/16" = 1'-0"1PLOT PLANPV 0.0GENERAL NOTES:a. INSTALLATION OF SOLAR PHOTOVOLTAICSYSTEM SHALL BE IN ACCORDANCE WITH NECARTICLE 690, AND ALL OTHER APPLICABLE NECCODES WHERE NOTED OR EXISTING.b. PROPER ACCESS AND WORKING CLEARANCEAROUND EXISTING AND PROPOSED ELECTRICALEQUIPMENT WILL COMPLY WITH NEC ARTICLE110.c. ALL CONDUCTORS, INCLUDING THE GROUNDINGELECTRODE CONDUCTOR SHALL BE PROTECTEDFROM PHYSICAL DAMAGE IN ACCORDANCE WITHNEC ARTICLE 250.d. ALL DC WIRES SHALL BE SIZED ACCORDING TO[NEC 690.8]e. DC CONDUCTORS SHALL BE WITHIN PROTECTEDRACEWAYS IN ACCORDANCE WITH [NEC 690.31]f. ALL SIGNAGE TO BE PLACED IN ACCORDANCEWITH LOCAL JURISDICTIONAL BUILDING CODE.g. PV MODULES TO BE RATED UL 1703 CLASS C FIRERATING OR BETTER.h. ALL EQUIPMENT TO BE CERTIFIED BY ANATIONALLY RECOGNIZED TESTINGLABORATORY.PROTECTION OF EMERGENCY RESPONDERSALL SHARP EDGES AND FASTENER TIPS SHALL BECOVERED OR CRIMPED OVER TO ELIMINATE SHARPEDGES, TO MINIMIZE RISK OF INJURY TO EMERGENCYRESPONDERS.ALL ROOF MOUNTED CONDUITS, BOXES, ANDEQUIPMENT CROSSING PATHWAYS ARE TO BECLEARLY IDENTIFIED BY A RED/WHITE REFLECTIVETAPE OR OTHER APPROVED MATERIAL. ROOF ACCESS POINTROOF ACCESS POINT SHALL NOT BE LOCATED IN AREASTHAT REQUIRE THE PLACEMENT OF GROUND LADDERSOVER OPENINGS SUCH AS WINDOWS OR DOORS, ANDLOCATED AT STRONG POINTS OF BUILDINGCONSTRUCTION IN LOCATIONS WHERE THE ACCESSPOINT DOES NOT CONFLICT WITH OVERHEADOBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS.SYSTEM SIZE: 9.855 kW DC7.600 kW ACMODULE TYPE & AMOUNT: (27)LG LG365N1K-A6MODULE DIMENSIONS:(L/W/H) 68.5"/41.02"/1.57"INVERTER:(01)SOLAREDGE ENERGY HUB SE7600H-US [240V]INTERCONNECTION METHOD: LOAD BREAKERPHOTOVOLTAIC SYSTEM SPECIFICATIONS:PHOTOVOLTAIC ROOF MOUNT SYSTEM27 MODULES-ROOF MOUNTED - 9.855 kW DC, 7.600 kW AC, 20501 GRANVILLE LN , LAKEVILLE, MINNESOTA 55044 (LAT. 44.65172, LONG. -93.2259)GOVERNING CODESALL WORK SHALL CONFORM TO THE FOLLOWING CODES·2018 INTERNATIONAL BUILDING CODE·2018 INTERNATIONAL RESIDENTIAL CODE·2018 INTERNATIONAL EXISTING BUILDING CODE·2018 INTERNATIONAL FIRE CODE·2018 INTERNATIONAL MECHANICAL CODE·2018 INTERNATIONAL FUEL GAS CODE 2018·2018 INTERNATIONAL ENERGY CONSERVATION CODE·2020 NATIONAL ELECTRICAL CODEANY OTHER LOCAL AMENDMENTSGRANVILLE LN
FRONT OF HOUSEPROPERTY LINEPROPERTY LINEPROPERTY LINE
PROPERTY LINE MEXISTING INTERIOR MAINSERVICE PANEL TIED TOEXTERIOR UTILITY METER#BI-DIRECTIONALROOF ACCESS POINTDRIVEWAYGARAGE MAIN HOUSEROOF #1(16)LG LG365N1K-A6SLOPE: 24°AZIM.: 270°ROOF #2(11)LG LG365N1K-A6SLOPE: 24°AZIM.: 90°GROUND SNOW LOAD 50 PSFWIND SPEED115 MPHEXPOSURE CATEGORY CRISK CATEGORY IINOTES:·SOLAR PV SHALL BE USED AS A SECONDARYINTERCONNECTION.·NO POSITION, DISTANCE AND CLEARANCE CONCERNS OFOVERHEAD ELECTRIC SERVICE LINES AND/OR OTHERUTILITIES IN RELATION TO THE PV PANELS.NOTES: 24/7 UNESCORTED KEYLESSACCESS TO THE METERS AND ACDISCONNECTI hereby certify that this plan, specification or reportwas prepared by me or under my direct supervisionand that I am a duly Licensed Professional Engineerunder the laws of the State of Minnesota,Brett D. Veazie, License No. 56392,Expiration Date: 30-June-202203/17/2022VSE Project Number: U1922.1366.221Vector Structural Engineering has reviewed the existingstructure with loading from the solar array and screwconnections to the existing framing. The design of theracking system, racking connections, and all otherstructural is by others. Mechanical, architectural, and allother nonstructural aspects of the design are by others.Electrical is by others, unless stamped by Dean Levorsen.
4'-8"27'-11"7'-4"
3'-6"20'-11"15'-7"
NEW PV ATTACHMENTSAT 4'-0" O.C.NRevRAWAY RESIDENCE
DateDescriptionREVISIONSSignature with SealProject Name &AddressSheet SizeSheet NumberANSI B11" X 17"PV 1.0Sheet NameDRAWN BY2010 E HENNEPIN AVE, BLDG 6 BOX 7
MINNEAPOLIS, MINNESOTA, 55413
(509)304-4658
LICENSE #BC708267/EA714757
20501 GRANVILLE LN , LAKEVILLE, MINNESOTA 55044
PHONE: 424-285-5369
EMAIL: pm33@greensoltech.com
APN: 224540004290EQUIPMENTLAYOUT & SITEPLANSCALE: 1/8"=1'-0"1SITE PLANPV 1.0STRING #2 - 13 MODULESSTRING #1 - 14 MODULESSTRING(S)ROOF SECTION(S)MODULE, ARRAY WEIGHT (LOAD CALC'S)Number of Modules27Module Weight41 LBSTotal Module (Array) Weight1107.00 LBSNumber of Attachment point56Mounting System Weight(Per Module)1.5LBSMounting System Weight84.00LBSTotal System Weight(Module Weight + Mounting System Weight)1191.00LBSWeight at Each Attachment Point(Array Weight / Number of Attachment Point)19.77 LBSModule Area (68.5"x41.02")19.51SqFtTotal Array Area526.85SqFtDistributed Load(Total System Weight / Total Array Area)2.18Per SqFtTotal Roof Area2319SqFtTotal Percentage or Roof CoveredTotal Array Area / Total Roof Area)*10022.72%SYSTEM LEGENDEXISTING INTERIOR MAIN SERVICE PANEL & POINTOF INTERCONNECTION. TIED TO EXTERIOR UTILITYMETER #BI-DIRECTIONAL.NEW PHOTOVOLTAIC UTILITY DISCONNECT SWITCH.LOCATED WITHIN 10' OF MSP.MACNEW 01 - SOLAREDGE ENERGY HUB SE7600H-US[240V] INVERTER.I= EXTERIOR RUN= CONDUIT ROOF TOP JUNCTION BOX= ATTACHMENT POINTS= RAFTER= ROOF OBSTRUCTIONS= FIRE PATHWAY= RACKING SYSTEM27 NEW LG LG365N1K-A6 MODULES WITHSOLAREDGE OPTIMIZER MOUNTED ON THEBACK OF EACH MODULES.SYSTEM SIZE: 9.855 kW DC7.600 kW ACMODULE TYPE & AMOUNT: (27)LG LG365N1K-A6MODULE DIMENSIONS:(L/W/H) 68.5"/41.02"/1.57"INVERTER:(01)SOLAREDGE ENERGY HUB SE7600H-US [240V]PHOTOVOLTAIC SYSTEM SPECIFICATIONS:MODULE - 11SLOPE - 24°AZIMUTH - 90°MATERIAL - COMP SHINGLETRUSS SIZE & SPACING - 2"X4" @ 24" O.C.MODULE - 16SLOPE - 24°AZIMUTH - 270°MATERIAL - COMP SHINGLETRUSS SIZE & SPACING - 2"X4" @ 24" O.C.ROOF #01ROOF #02NOTE: -1. ALL TESTING SHALL BE PERFORMED BY QUALIFIEDPERSONNEL, WITH PROPER PERSONAL PROTECTIVEEQUIPMENT.2. INSTALLATION SHALL COMPLY WITH NEC 690 AND ALLAPPLICABLE LOCAL, STATE, AND NATIONAL CODES ANDSTANDARDS.3. EQUIPMENT LABELS SHALL BE IN ACCORDANCE WITHNEC 690 AND XCEL ENERGY STANDARDS.4. 24/7 UNESCORTED KEYLESS ACCESS SHALL BEPROVIDED FOR THE METERS AND AC DISCONNECT.5. EQUIPMENT PAD SHALL CONTAIN INVERTER,GROUNDING TRANSFORMER, AND STEP STEP-UPTRANSFORMER PER PROJECT SINGLE LINE DIAGRAM.6. SHOW ALL THE SYSTEMS INCLUDING STORAGE,EXISTING AND NEW (IF APPLICABLE).7. PROVIDE FUSED, VISIBLE, LOCKABLE DISCONNECTMOUNTED ON DISCONNECT POLE. CLEARLY LABELDISCONNECT PER XCEL ENERGY GUIDELINES.NOTES:·SOLAR PV SHALL BE USED AS A SECONDARYINTERCONNECTION.·PRODUCTION METER SHALL BE WIRED SUCH THATTHE DER SYSTEM IS THE SOURCE.·THE DESIGNED INTERCONNECTION MEETS NATIONALELECTRIC CODE (NEC) REQUIREMENTS.MACIEXISTING INTERIOR MAIN SERVICE PANEL & POINT OFINTERCONNECTION. TIED TO EXTERIOR#BI-DIRECTIONALUTILITY METERNEW PV AC DISCONNECT GROUPED WITHSERVICE EQUIPMENT (VISIBLE,LOCKABLE, LABELED)NEW SOLAREDGE ENERGY HUB SE7600H-US [240V] INVERTEREQUIPPED WITH RAPIDSHUTDOWN36" FIRE SETBACK36" FIRE SETBACK36" FIRE SETBACK36" FIRE SETBACK36" FIRE SETBACK18" FIRE SETBACK18" FIRE SETBACK
FRONT OF HOUSE
GRANVILLE LN39'-1"ROOF #01ROOF #02
NOTE: -PLUMBING OR PVC VENT BENEATH MODULESWILL BE RELOCATED OR REMOVED PRIOR TOINSTALLATION.NO POSITION, DISTANCE AND CLEARANCE CONCERNS OFOVERHEAD ELECTRIC SERVICE LINES AND/OR OTHERUTILITIES IN RELATION TO THE PV PANELS.NOTES:I hereby certify that this plan,specification or report was prepared byme or under my direct supervision andthat I am a duly Licensed ProfessionalEngineer under the laws of the State ofMinnesota,Brett D. Veazie, License No. 56392,Expiration Date: 30-June-202203/17/2022VSE Project Number: U1922.1366.221Vector Structural Engineering has reviewed the existingstructure with loading from the solar array and screwconnections to the existing framing. The design of theracking system, racking connections, and all otherstructural is by others. Mechanical, architectural, and allother nonstructural aspects of the design are by others.Electrical is by others, unless stamped by Dean Levorsen.
RevRAWAY RESIDENCE
DateDescriptionREVISIONSSignature with SealProject Name &AddressSheet SizeSheet NumberANSI B11" X 17"S 1.1Sheet NameDRAWN BY2010 E HENNEPIN AVE, BLDG 6 BOX 7
MINNEAPOLIS, MINNESOTA, 55413
(509)304-4658
LICENSE #BC708267/EA714757
20501 GRANVILLE LN , LAKEVILLE, MINNESOTA 55044
PHONE: 424-285-5369
EMAIL: pm33@greensoltech.com
APN: 224540004290MOUNT DETAILPV MODULE(E)COMP SHINGLE ROOF2"X4
"
TRUSS
@
24"
OCPV MODULESUNIRAC SM LIGHT RAILLAG BOLT, 5/16"UNIRAC FLASH LOC ATTACHMENTUNIRAC END / MID CLAMP2"X4" TRUSS @ 24" OCSEE (2/S 1.1) FORENLARGED VIEWSCALE: NTS2ATTACHMENT DETAIL ENLARGED VIEWS 1.1SCALE: NTS1ATTACHMENT DETAIL (SIDE VIEW)S 1.1GENERAL STRUCTURAL NOTES:1. THE SOLAR PANELS ARE TO BE MOUNTED TO THEROOF FRAMING USING THE UNIRAC SM LIGHTRAIL WITH FLASH LOC ATTACHMENTS. THEMOUNTING FEET ARE TO BE SPACED AS SHOWNIN THE DETAILS, AND MUST BE STAGGERED TOADJACENT FRAMING MEMBERS TO SPREAD OUTTHE ADDITIONAL LOAD.2. UNLESS NOTED OTHERWISE, MOUNTINGANCHORS SHALL BE 5/16" LAG SCREWS WITH AMINIMUM OF 2-1/2" PENETRATION INTO ROOFFRAMING.3. THE PROPOSED PV SYSTEM ADDS 2.6 PSF TO THEROOF FRAMING SYSTEM.4. ROOF LIVE LOAD = 20 PSF TYPICAL, 0 PSF UNDERNEW PV SYSTEM.5. GROUND SNOW LOAD = 50 PSF6. WIND SPEED = 115 MPH7. EXPOSURE CATEGORY = C8. RISK CATEGORY = IINOTE: - CONTRACTOR/INSTALLER TO VERIFY COMPATIBILITYOF ANY BRANDS OR PRODUCTS SUBSTITUTED OR USED ASALTERNATES WITHIN ANY BRAND-SPECIFIC SYSTEMS.CONTRACTOR SHALL SUPPLY AND PRESENT CERTIFICATESOF COMPATIBILITY TO THE BUILDING OFFICIAL UPONINSPECTION.I hereby certify that this plan, specification or reportwas prepared by me or under my direct supervisionand that I am a duly Licensed Professional Engineerunder the laws of the State of Minnesota,Brett D. Veazie, License No. 56392,Expiration Date: 30-June-202203/17/2022VSE Project Number: U1922.1366.221Vector Structural Engineering has reviewed the existingstructure with loading from the solar array and screwconnections to the existing framing. The design of theracking system, racking connections, and all otherstructural is by others. Mechanical, architectural, and allother nonstructural aspects of the design are by others.Electrical is by others, unless stamped by Dean Levorsen.
RevRAWAY RESIDENCE
DateDescriptionREVISIONSSignature with SealProject Name &AddressSheet SizeSheet NumberANSI B11" X 17"E 1.1Sheet NameDRAWN BY2010 E HENNEPIN AVE, BLDG 6 BOX 7
MINNEAPOLIS, MINNESOTA, 55413
(509)304-4658
LICENSE #BC708267/EA714757
20501 GRANVILLE LN , LAKEVILLE, MINNESOTA 55044
PHONE: 424-285-5369
EMAIL: pm33@greensoltech.com
APN: 2245400042903-LINEDIAGRAMGN200AM40A(E) LOADSGN3EXISTING GROUNDINGELECTRODE SYSTEM(N) LOCKABLE BLADETYPE NON-FUSIBLE ACDISCONNECT NEMA 3R60A-2P 120/240VAC3EXISTING 240V/200A BUS BAR RATING,MAIN SERVICE PANEL, SINGLE PHASE,WITH A 200A MAIN DISCONNECTUTILITY COMPANY - XCEL ENERGY BI-DIRECTIONAL UTILITY METER(N) PV BREAKERPOINT OF INTERCONNECT, LOAD SIDE1=ACDC2- ++- +++---======- +2131- ++- +++---======- +2141(N) JUNCTION BOX600 V, NEMA 3RUL LISTED(N)SOLAREDGE ENERGY HUB SE7600H-US [240V] INVERTEROUTPUT: 240VAC, 32A, RATED POWER 7600W99% CEC WEIGHTED EFFICIENCYNEMA 3R, UL LISTED, INTERNAL GFDIWITH INTEGRATED DC DISCONNECT(N) SOLAREDGE P401OPTIMIZER(S)27 NEW LG LG365N1K-A6 MODULES (UL LISTED) WITHSOLAREDGE OPTIMIZER MOUNTED ON THE BACK OFEACH MODULES.Rooftop conductor ampacities designed in compliance withart. 690.8, Tables 310.15(B)(2)(a), 310.15(B)(3)(a),310.15(B)(3)(c), 310.15(B)(16), Chapter 9 Table 4, 5, & 9.Location specific temperature obtained from ASHRAE 2017data tablesAMBIENT TEMP (HIGH TEMP 2%)RECORD LOW TEMP-26°C32°CCONDUIT HEIGHT0.5"ROOF TOP TEMP54°CCONDUCTOR TEMPERATURE RATE90°CMANUFACTURERDC INPUT POWER400 WSOLAREDGE P401DC MAX INPUT VOLTAGEDC MAX INPUT CURRENTDC MAX OUTPUT CURRENT60V14.65A15AOPTIMIZER SPECIFICATIONSPV MODULE RATING @ STCMANUFACTURERMAX. POWER-POINT CURRENT (IMP)MAX. POWER-POINT VOLTAGE (VMP)OPEN-CIRCUIT VOLTAGE (VOC)SHORT-CIRCUIT CURRENT (ISC)10.41 AMPS35.1 VOLTS41.8 VOLTS10.92 AMPSNOM. MAX. POWER AT STC (PMAX)MAX. SYSTEM VOLTAGEVOC TEMPERATURE COEFFICIENT365 WATTPHOTOVOLTAIC SYSTEMDC SYSTEM SIZE (WATTS)NOMINAL AC VOLTAGE240V9855WAC SYSTEM SIZE (WATTS)7600WTOTAL NUMBER OF MODULES27120% RULEBUS BAR RATING X 120%) - MAIN BREAKER RATING= MAX. PV OCPD(200A x 120%) - 200 = 40AWIREQTYWIRETAG #CONDUITWIRE TYPECONDUITFILL:TEMPRATING:WIREAMPTEMPDE-RATE:WIREOCP:MAX SYSTEMVOLTAGEGRNDSIZEWIREGAUGE:TERMINAL75°C RATING:NEC:MAXAMPSxx=x=1.2518.75A38.40A 35A90°C35Ax=1.2518.75Axx=24.32A90°C50Ax=1.2540.00Axx=47.00A75°C40A#1040A#1050A#83/4" EMT3/4" EMTWIRE FROM - -JUNCTION BOX TOINVERTERINVERTER TO MSPARRAY TOJUNCTION BOX123PV WIRETHWN-2THWN-240.8031.00IN AIRx=GRND WIRETYPE480V480V240V#6#8#8SBCTHWN-2THWN-20.960.760.94SYSTEM SIZE: 9.855 kW DC7.600 kW ACMODULE: (27)LG LG365N1K-A6INVERTER: (01)SOLAREDGE ENERGY HUB SE7600H-US [240V]LG LG365N1K-A64NA1000V-0.26° %/°CINVERTER CHARACTERISTICS - SOLAREDGE ENERGY HUB SE7600H-USMAX OUTPUT POWER7600WSYSTEM OPERATING VOLTAGE400VMAX CONTINOUS OUTPUT CURRENT32AMAX INPUT VOLTAGE480VSYSTEM SHORT CIRCUIT CURRENT15AMAX EFFICIENCY99%OPTIMIZEROUTPUT C\N15A15A32ANOTES:·SOLAR PV SHALL BE USED AS A SECONDARYINTERCONNECTION.·PRODUCTION METER SHALL BE WIRED SUCHTHAT THE DER SYSTEM IS THE SOURCE.·THE DESIGNED INTERCONNECTION MEETSNATIONAL ELECTRIC CODE (NEC)REQUIREMENTS.NOTE: -1. ALL TESTING SHALL BE PERFORMED BY QUALIFIED PERSONNEL,WITH PROPER PERSONAL PROTECTIVE EQUIPMENT.2. THE PRODUCTION METER AND AC DISCONNECT SHOULD BE LOCATEDTOGETHER IN A READILY ACCESSIBLE LOCATION WITHIN 10' OF THEMAIN SERVICE METER.3. 24/7 UNESCORTED KEYLESS ACCESS SHALL BE PROVIDED FOR THEMETERS AND AC DISCONNECT.4. UTILITY AC DISCONNECT SHOULD BE LOCATED WITHIN 10 FEET OFTHE MAIN SERVICE METER.5. NOTE ALL THE APPLICABLE NEC CODES.6. SHOW ALL THE SYSTEMS INCLUDING STORAGE, EXISTING AND NEW(IF APPLICABLE).7. SERVICES <320A WILL USE SELF CONTAINED MAIN SERVICE METERS.320A SERVICES MUST INDICATE WHETEHER THE METERING WILL BESELF CONTAINED OR TRANSFORMER METERED. ALL SERVICES 400AOR GREATER MUST BE TRANSFORMER METERED.PoC/RPA*NOTE:-WIRES LOCATED IN READILY ACCESSIBLE LOCATIONSSHALL BE GUARDED PER NEC 690.31(A)
RevRAWAY RESIDENCE
DateDescriptionREVISIONSSignature with SealProject Name &AddressSheet SizeSheet NumberANSI B11" X 17"E 1.2Sheet NameDRAWN BY2010 E HENNEPIN AVE, BLDG 6 BOX 7
MINNEAPOLIS, MINNESOTA, 55413
(509)304-4658
LICENSE #BC708267/EA714757
20501 GRANVILLE LN , LAKEVILLE, MINNESOTA 55044
PHONE: 424-285-5369
EMAIL: pm33@greensoltech.com
APN: 224540004290NOTES SITE NOTES:1.A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHAREGULATIONS.2.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AUTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.3.THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL,OR BUILDING ROOF VENTS.4.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSEDELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.5.ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED INACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'SINSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THEBUILDING OR STRUCTURE.EQUIPMENT LOCATIONS:1.ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.2.WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTEDOPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLES310.15 (B)(2)(A) AND 310.15 (B)(3)(C).3.JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULESACCORDING TO NEC 690.34.4.ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOTWITHIN SIGHT OF THE AC SERVICING DISCONNECT. 2.2.6 ALL EQUIPMENT SHALL BEINSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NECAPPLICABLE CODES.5.ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOORUSAGE WHEN APPROPRIATE.STRUCTURAL NOTES:1.RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TOCODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATEDSPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCEBEYOND EITHER EDGE OF THE ARRAY / SUBARRAY, ACCORDING TO RAIMANUFACTURER’S INSTRUCTIONS.2.JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IFROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCALREQUIREMENTS.3.ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.4.ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THESPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 2.3.6 WHENPOSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGEREDAMONGST THE ROOF FRAMING MEMBERS.WIRING & CONDUIT NOTES:1.ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODEREQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.2.CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.3.VOLTAGE DROP LIMITED TO 1.5%.4.DC WIRING LIMITED TO MODULE FOOTPRINT. MICRO INVERTER WIRINGSYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLEWIRING CLIPS.5.AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACKPHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3-BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GREYIN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TOBE MARKED ORANGE [NEC 110.15].GROUNDING NOTES:1.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, ANDGROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCHUSE.2.PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUMNEC TABLE 250.122.3.METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURESCONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).4.EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC690.45 AND MICRO INVERTER MANUFACTURERS’ INSTRUCTIONS.5.EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN INMANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARENOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIEDGROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATIONREQUIREMENTS.6.THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THATTHE REMOVAL OFA MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TOANOTHER MODULE.7.GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLOREDGREEN OR MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]8.THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, AGROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47AND AHJ.9.GROUND-FAULT DETECTION SHALL COMPLY WITH NEC 690.41(B)(1) AND (2) TOREDUCE FIRE HAZARDSDISCONNECTION AND OVER-CURRENT PROTECTION NOTES:1.DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH ISOPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THETERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS).2.DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BELOCKABLE, AND BE A VISIBLE-BREAK SWITCH3.PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPIDSHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCYRESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D).4.ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND240.5.MICRO INVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPEDFUSES IN ACCORDANCE WITH NEC 110.3(B).6.IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTIONACCORDING TO NEC 690.11 AND UL1699B.INTERCONNECTION NOTES:1.LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12 (B)]2.THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS OUTPUT MAY NOTEXCEED 120% OF BUS BAR RATING [NEC 705.12(D)(2)(3)].3.THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENTAND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUS BARSHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUS BAR, PVDEDICATED BACKFEED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUSFROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(2)(3)].4.AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTALRATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OFBUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE EXCLUDEDACCORDING TO NEC 705.12 (B)(2)(3)(C).5.FEEDER TAP INTERCONNECTION (LOADSIDE) ACCORDING TO NEC 705.12 (B)(2)(1)6.SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.12 (A) WITHSERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230.422.7.8BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPTFROM ADDITIONAL FASTENING [NEC 705.12 (B)(5)].
NRevRAWAY RESIDENCE
DateDescriptionREVISIONSSignature with SealProject Name &AddressSheet SizeSheet NumberANSI B11" X 17"E 1.3Sheet NameDRAWN BY2010 E HENNEPIN AVE, BLDG 6 BOX 7
MINNEAPOLIS, MINNESOTA, 55413
(509)304-4658
LICENSE #BC708267/EA714757
20501 GRANVILLE LN , LAKEVILLE, MINNESOTA 55044
PHONE: 424-285-5369
EMAIL: pm33@greensoltech.com
APN: 224540004290WARNINGLABELS CAUTION:POWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWNGRANVILLE LNSOLAR PHOTOVOLTAICSYSTEMS(PER CODE: NEC 690)ASOLAR PV SYSTEMEQUIPPED WITH RAPIDSHUTDOWNTURN RAPIDSHUTDOWNSWITCH TO THE"OFF" POSITION TOSHUTDOWN PVSYSTEM ANDREDUCESHOCK HAZARDIN THE ARRAYSOLARELECTRICPV PANELSAT INVERTER [IFC 605.11.3.1(1) & 690.56(C)]PER CODE: NEC 2020ELECTRICAL SHOCK HAZARDTERMINALS ON BOTH LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONWARNING!LABEL LOCATION:WHERE ALL TERMINALS OF THE DISCONNECTING MEANS MAY BEENERGIZED IN THE OPEN POSITION, A WARNING SIGN SHALL BEMOUNTED ON OR ADJACENT TO THE DISCONNECTING MEANS.PER CODE(S): NEC 2020:NEC 706.15(C)(4) and NEC 690.13(B)WARNING!DUAL POWER SOURCESECOND SOURCE IS PHOTOVOLTAIC SYSTEMLABEL LOCATION:PRODUCTION / NET METER (BI-DIRECTIONAL)NEC: 2020NEC 690.59, 705.12(D)(3)WARNING: PHOTOVOLTAICPOWER SOURCEMAIN PHOTOVOLTAICSYSTEM DISCONNECTLABEL LOCATION: MAIN SERVICE DISCONNECT, NEC 2020, 690.13(B)POWER SOURCE OUTPUTCONNECTION. DO NOT RELOCATETHIS OVERCURRENT DEVICE.WARNING!LABEL LOCATION:MAIN SERVICE DISCONNECTNEC: 2020, 705.12(B)(3)(2)LABEL LOCATION:PERMANENT WARNING LABELS SHALL BE APPLIEDTO DISTRIBUTION EQUIPMENT, AC DISCONNECTNEC: 2020, PER CODE: 705.12(B)(3)(3) PHOTOVOLTAICAC DISCONNECTLABEL LOCATION:AC DISCONNECT, NEC: 2020, (NEC 690.13(B) PHOTOVOLTAICDC DISCONNECTLABEL LOCATION:DC DISCONNECT(NEC 690.13(B)MACINVERTERJ/BPV ARRAYWARNING: PHOTOVOLTAICPOWER SOURCELABEL LOCATION :EXPOSED RACEWAY, CABLE TRAYS, JUNCTION BOXNEC: 2020, PER CODE: NEC 690.31(D)(2)LABEL LOCATION:AC DISCONNECT, POINT OF INTERCONNECTIONNEC: 2020(PER CODE: NEC 690.54)PHOTOVOLTAIC SYSTEM AC DISCONNECTRATED AC OPERATING CURRENT 32 AMPSAC NOMINAL OPERATING VOLTAGE 240 VOLTSPHOTOVOLTAIC SYSTEMEQUIPPED WITHRAPID SHUTDOWNLABEL LOCATION:UTILITY SERVICE ENTRANCE/METER, INVERTER/DC DISCONNECT IF REQUIRED BYLOCAL AHJ, OR OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ.PER CODE(S): NEC 2020: ARTICLE 690.56(C)SOLAR PHOTOVOLTAICSYSTEMS(PER CODE: NEC 690)PHOTOVOLTAIC DC DISCONNECTMAXIMUM SYSTEM VOLTAGE:MAXIMUM CIRCUIT CURRENT:MAX RATED OUTPUT CURRENT OF THE CHARGECONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED):VDCADCADC4802015INVERTER #1 (SOLAREDGE ENERGY HUBSE7600H-US [240V])LABEL LOCATION:INVERTER(S), DC DISCONNECT(S).PER CODE(S): NEC 2020,PER CODE: 690.53THIS EQUIPMENT FED BY MULTIPLESOURCES, TOTAL RATING OF ALLOVERCURRENT DEVICES,EXCLUDING MAIN SUPPLYOVERCURRENT DEVICE, SHALL NOTEXCEED AMPACITY OF BUSBAR.WARNING!ACMIINVERTERAC DISCONNECTUTILITY METERMAIN SERVICEPANEL(27) PV MODULES