HomeMy WebLinkAboutLA200293-Approved Raway Engineering Letter SS (1)VSE Project Number: U1922.1366.221
March 17, 2022
Powerfully Green
2010 E Hennepin Ave
Minneapolis, MN 55413
REFERENCE: Raway Residence: 20501 Granville Lane, Lakeville, MN 55044
Solar Array Installation
To Whom It May Concern:
Per your request,we have reviewed the existing structure at the above referenced site.The purpose of our review was to
determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on
the panel layout plan.
Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation.
Design Parameters
Code: 2020 Minnesota Residential Code (2018 IRC)
Risk Category: II
Design wind speed, Vult: 115 mph (3-sec gust)
Wind exposure category: C
Ground snow load, Pg: 50 psf
Existing Roof Structure
Roof structure: 2x4 manufactured trusses @ 24" o.c.
Roofing material: composite shingles
Roof slope: 24°
Connection to Roof
Mounting connection: (1) 5/16" lag screw w/ min. 2.5" threaded embedment into framing at max. 48" o.c. (portrait and
landscape) along rails
Install (2) rails per row of panels, evenly spaced
Maximum panel dimension: 68.5x41 in
Rail cantilever shall not exceed 33% of connection spacing
Conclusions
Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation.
The gravity loads,and thus the stresses of the structural elements,in the area of the solar array are either decreased or
increased by no more than 5%.Stress decreases or increases of no more than 5%are considered acceptable.Therefore,the
structure is permitted to remain unaltered.
651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com
VSE Project Number: U1922.1366.221
Raway Residence
3/17/2022
The solar array will be flush-mounted (no more than 10"above the roof surface)and parallel to the roof surface.Thus,we
conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible.
The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift),
the governing load case.Increases in lateral forces less than 10%are considered acceptable.Thus the existing lateral force
resisting system is permitted to remain unaltered.
Limitations
Installation of the solar panels must be performed in accordance with manufacturer recommendations.All work performed
must be in accordance with accepted industry-wide methods and applicable safety standards.The contractor must notify
Vector Structural Engineering,LLC should any damage,deterioration or discrepancies between the as-built condition of the
structure and the condition described in this letter be found.Connections to existing roof framing must be staggered,except
at array ends,so as not to overload any existing structural member.The use of solar panel support span tables provided by
others is allowed only where the building type,site conditions,site-specific design parameters,and solar panel configuration
match the description of the span tables.The design of the solar panel racking (mounts,rails,etc.)and electrical engineering
is the responsibility of others.Waterproofing around the roof penetrations is the responsibility of others.Vector Structural
Engineering assumes no responsibility for improper installation of the solar array.Vector Structural Engineering shall be
notified of any changes from the approved layout prior to installation.
VECTOR STRUCTURAL ENGINEERING, LLC
03/17/2022
_______________________________________________________
Brett Veazie, P.E.
Project Engineer
Enclosures
BDV/ryl
I hereby certify that this plan, specification or report was prepared
by me or under my direct supervision and that I am a duly Licensed
Professional Engineer under the laws of the State of Minnesota.
Brett Veazie, License No. 56392,
Expiration Date: 30-June-2022
03/17/2022
651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com
JOB NO.:U1922.1366.221
SUBJECT:WIND PRESSURE
PROJECT:Raway Residence
Label:Note: Calculations per ASCE 7-10
SITE-SPECIFIC WIND PARAMETERS:
Basic Wind Speed [mph]:115 Notes:
Exposure Category:C
Risk Category:II
Importance Factor, I:
ADDITIONAL INPUT & CALCULATIONS:
Height of Roof, h [ft]:25 (Approximate)Hip?
Comp/Cladding Location:No
Enclosure Classification:
Zone 1 GCp:0.9 Figure 30.4-2B (enter negative pressure coefficients)
Zone 2 GCp:1.7
Zone 3 GCp:2.6
α:9.5 Table 26.9-1
zg [ft]:900 Table 26.9-1
Kh:0.95 Table 30.3-1
Kzt:1 Equation 26.8-1
Kd:0.85 Table 26.6-1
Velocity Pressure, qh [psf]:27.2 Equation 30.3-1
GCpi:0 Table 26.11-1
PRESSURES:Equation 30.9-1
Zone 1, p [psf]:24.4 psf (1.0 W, Interior Zones, beyond 'a' from roof edge)
Zone 2, p [psf]:45.5 psf (1.0 W, End Zones, within 'a' from roof edge)
Zone 3, p [psf]:69.8 psf (1.0 W, Corner Zones, within 'a' from roof corner)
(a= 3 ft)
Solar Panel Array
Gable/Hip Roofs 7° < θ ≤ 27°
Enclosed Buildings
Components and Cladding Wind Calculations
()()piphGCGCqp−=
JOB NO.:U1922.1366.221
SUBJECT:CONNECTION
PROJECT:Raway Residence
Calculate Uplift Forces on Connection
Pressure
(0.6 Dead -0.6 Wind)
(psf)
Max Trib. Width1
(ft)
Max Trib.
Area2
(ft2)
Max Uplift
Force
(lbs)
Zone 1 12.8 4.0 11.4 146
Zone 2 25.5 4.0 11.4 291
Zone 3 40.1 4.0 11.4 457
Calculate Connection Capacity
Lag Screw Size [in]:5/16
Cd:1.6 NDS Table 2.3.2
Embedment3 [in]:2.5
Grade:
Nominal Capacity [lbs/in]:205 NDS Table 12.2A
Number of Screws:1
Prying Coefficient:1.4
Total Capacity [lbs]:586
Determine Result
Maximum Demand [lbs]:457
Lag Screw Capacity [lbs]:586
Result:Capacity > Demand, Connection is adequate.
Notes
1. 'Max Trib. Width' is the width along the rails tributary to the connection.
2. 'Max Trib Area' is the product of the 'Max. Trib Width' and 1/2 the panel width/height perpendicular to the
rails. (2) rails per row of panels. Length of panels perpendicular to the rails shall not exceed 69".
SPF (G = 0.42)
3. Embedment is measured from the top of the framing member to the beginning of the tapered tip of the lag
screw. Embedment in sheathing or other material is not effective. The length of the tapered tip is not part of the
embedment length.
VECTOR STRUCTURAL ENGINEERS
JOB NO.:U1922.1366.221
SUBJECT:GRAVITY LOADS
PROJECT:Raway Residence
GRAVITY LOADS Roof Pitch: 5.3 :12
ROOF DEAD LOAD (D)
Increase due to
pitch
Material weight
[psf]
Composite Shingles 1.09 2.0
1/2" Plywood 1.09 1.0
Framing 1.00 3.0
Insulation 1.00 0.5
1/2" Gypsum Clg.1.09 2.0
M, E & Misc 1.00 6.5
Total Existing Roof DL
PV Array DL 1.09 3
DL:1.09
ROOF LIVE LOAD (Lr)
Existing Design Roof Live Load [psf]20 ASCE 7-10 Table 4.3-1
Roof Live Load With PV Array [psf]0
SNOW LOAD (S):w/ Solar Array
Roof Slope [x:12]:5.3
Roof Slope [°]:24
Ground Snow Load, pg [psf]:50 ASCE 7-16, Section 7.2
Terrain Category:C ASCE 7-16, Table 7.3-1
Exposure of Roof:Fully Exposed ASCE 7-16, Table 7.3-1
Exposure Factor, Ce:0.9 ASCE 7-16, Table 7.3-1
Thermal Factor, Ct:1.1 ASCE 7-16, Table 7.3-2
Risk Category:II ASCE 7-16, Table 1.5-1
Importance Factor, Is:1.0 ASCE 7-16, Table 1.5-2
Flat Roof Snow Load, pf [psf]:35 ASCE 7-16, Equation 7.3-1
Minimum Roof Snow Load, pm [psf]:0 ASCE 7-16, Section 7.3.4
Unobstructed Slippery Surface?No ASCE 7-16, Section 7.4
Slope Factor Figure:Figure 7-2b ASCE 7-16, Section 7.4
Roof Slope Factor, Cs:1.00 ASCE 7-16, Figure 7.4-1
Sloped Roof Snow Load, ps [psf]:35 ASCE 7-16, Equation 7.4-1
Design Snow Load, S [psf]:35
1.00
35
Design material
weight [psf]
2.2
1.1
3.0
0.5
2.2
6.5
15.5
3.3
#VALUE!
2020 MRC, Section R324.4.1.1
Existing
35
5.3
24
50
C
Fully Exposed
0.9
1.1
II
1.0
35
0
No
Figure 7-2b
VECTOR STRUCTURAL ENGINEERS
JOB NO.:U1922.1366.221
SUBJECT:MEMBER FORCES
PROJECT:Raway Residence
DESIGN LOADS [PSF]:Load Types:Snow Live Dead
Existing Roof 35 20 15
Proposed PV Array 35 0 19
(Cd = Load Duration Factor = 0.9 for D, 1.15 for S, and 1.25 for Lr)
Label
Length 35.9 Existing Proposed Check
M (ft-lb)14043 13871 99%OK
Existing Proposed Check
V (lb)1565 1528 98%OK
Existing Loads (Distributed)
Cond
Roof
Trib (ft)
Add'l
Live
Load
(plf)
Add'l
Dead
Load
(plf)
Bm wt
(plf)wLL (plf)wDL (plf)
1 2.00 0 0 0 60.3 26.9
Proposed Loads (Distributed)
Cond
Dist to
Load 'a'
(ft)
Length
of Load
'b' (ft)
Δ wLL
(plf)Δ wDL (plf)
2 2.3 5.7 -14.1 5.7
3 11.0 5.7 0.0 5.7
4 24.4 11.4 -14.1 5.7
5 0.0 5.7
6 0.0 5.7
Proposed Loads as Point Loads
Cond
Dist 'a'
(ft)
Point
Live
Load
'PLL' (lb)
Point
Dead
Load
'PDL' (lb)
7 0.0 0.0
8 0.0 0.0
9 0.0 0.0
10 0.0 0.0
11 0.0 0.0
manufactured trusses
The gravity loads, and thus the stresses of the structural elements, in the area of the solar array are either decreased
or increased by no more than 5%. Stress decreases or increases of no more than 5% are considered acceptable.
Therefore, the structure is permitted to remain unaltered.
(D+Lr)/Cd(D+S)/Cd Max Load
28
21
44
46
44
46
0
5000
10000
15000
0 5 10 15 20 25 30 35 40
MOMENT (FT-LB)
EXISTING PROPOSED
-2000
-1000
0
1000
2000
0 10 20 30 40
SHEAR (LB)
EXISTING PROPOSED
0
50
100
0 10 20 30 40
LOAD (LB)
EXISTING PROPOSED