HomeMy WebLinkAboutLA201713-Approved Ali Mahbub - ENG CAD-min Everlight Solar Construction , , Subject: Structural Certification for Installation of Residential Solar re job:Ali Mahbub, 16957 Evening Terrace, Lakeville, MN 55044 Attn.: To Whom It May Concern ROOF 1: 115 mph Ground Snow:50 psf C Min Roof Snow:NA psf ROOF 1: Current Renewables Engineering Inc. Professional Engineer projects@creng.solar Code:2018 IBC (ASCE 7-16) Ult Wind Speed: Exposure Cat: After review of the field observation report and based on our structural capacity calculations in accordance with applicable building codes, the existing roof framing supporting the proposed solar panel layout has been determined to be: adequate to support the imposed loads. Therefore, no structural upgrades are required. 4/12/2022 A field observation was performed to document the existing framing of the above mentioned address. From the field observation, the existing roof structure was observed as: Shingle roofing supported by 2x4 Truss @ 24 in. OC spacing. The roof is sloped at approximately 39 degrees and has a max beam span of 6 ft between supports. Design Criteria: ϰͬϭϮͬϮϬϮϮ Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric AERIAL VIEW: DATE: April 8, 2022 PV01 COVER PAGE PV02 SITE PLAN PV03 ROOF ATTACHMENTS PV04 MOUNTING DETAIL PV05 LINE DIAGRAM PV06 ELECTRICAL CALCS PV07 LABELS PV08 PLACARD PV09 SITE PHOTOS COVER PAGE - PV01 DRAWN BY: SoloCAD 1.INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE 690, AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING. 2.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110. 3.ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250 4.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER UL 1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES. 5.ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.8] 6.DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.31] 7.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE. PHOTOVOLTAIC (PV) SYSTEM SPECIFICATIONS AERIAL VIEW: SHEET INDEX: OCCUPANCY: R-3 ZONING: RESIDENTIAL STREET VIEW: GENERAL NOTES APPLICABLE GOVERNING CODES SITE SPECIFICATIONS 2020 NEC 2020 MRC 2020 MFC 2020 MBC EQUIPMENT: AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) RACKING: Quickbolt 2 (QB2) - 48" O.C. AC MSP M PV C JB JB Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 EQUIPMENT LEGEND: INVERTERVISIBLE, LOCKABLE, LABELED AC DISCONNECT METER SOCKET (FOR UTILITY PV METER) UTILITY METER MAIN SERVICE PANEL LC LOAD CENTER FIRE ACCESS PATHWAY (3' TYP) C INV PV AC MSP M COMBINER BOX PROPERTY LINE BATT BATTERY(IES) VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED WITHIN 10' OF UTILITY METER SUB SUB PANEL SITE PLAN - PV02 DRAWN BY: SoloCAD MP1 MP2 ARRAY DETAILS: MOUNTING PLANE:AZIMUTH:TILT: MP1 180°39° MP2 180°39° 16957 Evening Terrace FRONT OF HOME 176'-2" 88'-11" 173'-4" ϰͬϭϮͬϮϬϮϮ AC MSP M PV C JB JB EQUIPMENT INFORMATION:ROOF INFO:PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: RAIL MANUFACTURER:IronRidge ROOF TYPE:Asphalt Shingle PV MODULE COUNT:23 RAIL PART NUMBER:XR-10 ROOF FRAMING:Manufactured Truss ARRAY AREA:MODULE COUNT * 19.83 ft² = 456.09 ATTACHMENTS Quickbolt 2 (QB2)RAFTER/TOP CHORD SIZE:2x4 ROOF AREA:2562.84 ft² ATTACHMENT QTY:58 RAFTER/TOP CHORD SPACING:24"PERCENT OF ROOF COVERED:18% SPLICE QTY:2 ATTACHMENT SPACING:48''ARRAY WEIGHT:MODULE COUNT * 45 lbs = 1035 lbs MIDCLAMP QTY:30 DISTRIBUTED LOAD:ARRAY LBS/ATTACHMENTS = 17.84 ENDCLAMP QTY:32 POINT LOAD: (lbs/ft²)(ARRAY) WEIGHT/AREA = 2.27 lbs/ft² Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 ROOF ATTACHMENTS - PV03 DRAWN BY: SoloCAD 18" TYP ),5(3$7+:$<$&&(66 ϰͬϭϮͬϮϬϮϮ ,5215,'*(;55$,/ /)227$77$&+0(17%5$&.(7 ( 522))5$0,1* 48,&.%2/7 4% )/$6+,1* 3902'8/( ( &2036+,1*/(522) /$<(5 ,5215,'*(;55$,/ (1'&/$03 3902'8/( 0,'&/$03 3902'8/(  0,1 '(37+ ,5215,'*(;55$,/ ,5215,'*(;55$,/ )/$6+,1* 48,&.%2/7 4% 2'-8" MIN - 3'-10" MAX  ,5215,'*(;55$,/ 3902'8/( 48" MAX1'-8" MAX.  FRONT VIEW 10" MIN - 1'-4" MAX2'-8" MIN - 3'-10" MAX 10" MIN - 1'-4" MAX SIDE VIEW ( 5$)7(5723&+25'6 ( 5$)7(5723&+25' DETAIL, MOUNTING AND FLASHING END CLAMP DETAILS MID CLAMP DETAILS   EQUIPMENT INFORMATION:ROOF INFO:PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA: RAIL MANUFACTURER:IronRidge ROOF TYPE:Asphalt Shingle PV MODULE COUNT:23 RAIL PART NUMBER:XR-10 ROOF FRAMING:Manufactured Truss ARRAY AREA:MODULE COUNT * 19.83 ft² = 456.09 ATTACHMENTS Quickbolt 2 (QB2)RAFTER/TOP CHORD SIZE:2x4 ROOF AREA:2562.84 ft² ATTACHMENT QTY:58 RAFTER/TOP CHORD SPACING:24"PERCENT OF ROOF COVERED:18% SPLICE QTY:2 ATTACHMENT SPACING:48''ARRAY WEIGHT:MODULE COUNT * 45 lbs = 1035 lbs MIDCLAMP QTY:30 DISTRIBUTED LOAD:ARRAY LBS/ATTACHMENTS = 17.84 ENDCLAMP QTY:32 POINT LOAD: (lbs/ft²)(ARRAY) WEIGHT/AREA = 2.27 lbs/ft² Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12)AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 MOUNTING DETAIL - PV04 DRAWN BY: SoloCAD ϰͬϭϮͬϮϬϮϮ J-BOX STRING (1): 15.96 A AC, 14 MODULES STRING (2): 11.40 A AC, 9 MODULES N G 3 AC COMBINER BOX SOLAR LOADS ONLYUL 1741 COMPLIANT AC DC AC DC5 INVERTERS AC DC AC DC7 INVERTERS J-BOX (N) 100A (2) 20A-2P J-BOX1 2 1 2 4 (E) LOADS N G (E)GROUNDING ELECTRODE SUPPLY SIDE CONNECTION: NEC 230.46, NEC 230.79, NEC 705.12(A). .,170,/%$1. /8*.,772%($''(' (E) 200A-2P (E) 225A MAIN SERVICE PANEL (E) (E)UTILITY METER 120/240 VAC TO UTILITY GRID UTILITY PV PRODUCTION METER BASE 4 4 (N) 40A FUSES PV AC DISCONNECT 60A FUSED, VISIBLE, LOCKABLE, LABELED, OPEN 240V, 2-POLE Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 LINE DIAGRAM - PV05 DRAWN BY: SoloCAD AP Systems YC600 Specs MAX INPUT VOLTAGE:55 V MAX DC SHORT CIRCUIT CURRENT:12 A MAXIMUM OUTPUT POWER:548 W MAXIMUM OUTPUT CURRENT:2.28 A NOM. OUTPUT VOLTAGE:240 V MAX UNITS PER 20A CIRCUIT:7 1-Phase, 60 HZ, UL 1741 Listed Mission Solar MSE345SX5T Specs POWER MAX (PMAX):345W OPEN CIRCUIT VOLTAGE (VOC):41V MAX POWER-POINT CURRENT (IMP):10.34A MAX POWER-POINT VOLTAGE (VMP):33.37V SHORT CIRCUIT CURRENT (ISC):10.92A SERIES FUSE RATING:20A VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED WITHIN 10' OF UTILITY METER Conduit & Conductor Schedule TAG QTY WIRE GAUGE DESCRIPTION CONDUIT SIZE 1 (2)12-2 TC-ER, THWN-2, COPPER (L1, L2)N/A - FREE AIR(1)6 AWG THWN-2 COPPER - (GROUND) 2 (2)10 AWG THHN/THWN-2, COPPER - (L1, L2)3/4" EMT(1)10 AWG THWN-2 COPPER - (GROUND) 3 (4)10 AWG THHN/THWN-2, COPPER - (L1, L2)3/4" EMT(1)10 AWG THWN-2 COPPER - (GROUND) 4 (3)6 AWG THWN-2 COPPER - (L1, L2, NEUTRAL)3/4" EMT(1)8 AWG THWN-2 COPPER - (GROUND) Equipment Schedule TYPE:QTY:DESCRIPTION:RATING: MODULES:(23)Mission Solar MSE345SX5T 345 W INVERTERS:(12)AP Systems YC600 548 W AC DISCONNECTS:(1)PV AC Disconnect, 240V, 2-Pole 60 A LOAD SIDE LINE SIDE ,17(5&211(&7,21127(6 1. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9] & [NEC 230.95] 2. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC705.12(A)] WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH [NEC 240.21(B)] ',6&211(&7127(6 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH. 3. FUSED AC DISCONNECT TO BE USED. *5281',1* *(1(5$/127(6 1. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE. 2. DC GEC AND AC EGC TO BE SPLICED TO EXISTING ELECTRODE 3. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. 4. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD - JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS. 5. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT. STRING CALCULATIONS MAX AC CURRENT: MICRO INVERTERS IN SERIES NOMINAL STRING VOLTAGE: MAX AC OUTPUT POWER ARRAY DC POWER: TOTAL MAX AC CURRENT: STRING #1 15.96A 7 240V 3836W 7935W 27.36A STRING #2 11.40A 5 240V 2740W AP Systems YC600 Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 ELECTRICAL CALCS - PV06 DRAWN BY: SoloCAD Conduit & Conductor Schedule TAG QTY WIRE GAUGE DESCRIPTION CONDUIT SIZE CONDUCTOR RATING CONDUCTOR TEMP. RATE AMBIENT TEMP TEMP. DERATE # OF CONDUCTORS DERATE CONDUCTOR RATING W/DERATES CONDUIT FILL 1 (2)12-2 TC-ER, THWN-2, COPPER (L1, L2)N/A - FREE AIR 30A 90°C 32°C 0.96 N/A - FREE AIR 28.8A N/A - FREE AIR(1)6 AWG THWN-2 COPPER - (GROUND) 2 (2)10 AWG THHN/THWN-2, COPPER - (L1, L2)3/4" EMT 40A 90°C 32°C 0.96 1 38.4A 11.9%(1)10 AWG THWN-2 COPPER - (GROUND) 3 (4)10 AWG THHN/THWN-2, COPPER - (L1, L2)3/4" EMT 40A 90°C 32°C 0.96 0.8 30.72A 19.8%(1)10 AWG THWN-2 COPPER - (GROUND) 4 (3)6 AWG THWN-2 COPPER - (L1, L2, NEUTRAL)3/4" EMT 65A 75°C 32°C 0.96 1 62.4A 35.5%(1)8 AWG THWN-2 COPPER - (GROUND) SYSTEM OCPD CALCULATIONS INVERTER MODEL(S):AP Systems YC600 # OF INVERTERS:12 MAX OUTPUT CURRENT:2.28A (# OF INVERTERS) X (MAX OUTPUT CURRENT) X 125% <= OCPD RATING (12 X 2.28A X 1.25) = 34.2A <= 40A, OK SUPPLY SIDE INTERCONNECTION MAIN BUSBAR RATING:225A MAIN DISCONNECT RATING:200A PV OCPD RATING:40A SERVICE RATING >= PV OCPD 225A >= 40A, OK NUMBER OF CURRENT CARRYING CONDUCTORS PERCENT OF VALUES 4-6 .80 7-9 .70 10-20 .50 Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 LABELS - PV07 DRAWN BY: SoloCAD LABEL 6 MARKED AT AC DISCONNECTING MEANS. [NEC 690.54] LABEL 5 EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUSBAR OR CONDUCTOR SUPPLIED FROM MULTIPLE SOURCES SHALL BE MARKED TO INDICATE THE PRESENCE OF ALL SOURCES.[NEC 705.12(B)(2)(3)(c)] LABEL 3 PLACED ADJACENT TO THE BACK-FED BREAKER FROM THE INVERTER IF TIE IN CONSISTS OF LOAD SIDE CONNECTION TO BUSBAR. [NEC 705.12(B)(2)(3)(c)] *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON THE ELECTRICAL DIAGRAM PAGE. JUNCTION BOX OR COMBINER BOX MAIN SERVICE PANEL AC DISCONNECT EXISTING SUB PANEL (IF WHERE POINT OF INTERCONNECTION IS MADE) PV COMBINER SUBPANEL - IF USED TO COMBINE PV OUTPUT CIRCUITS AC DC INVERTER (S) INTEGRATED DC DISCONNECT 2 8 6 9 5 (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) 7 1 1 1 5 (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) 7 3 LABELING DIAGRAM: LABEL 7 AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND ENCLOSURES OF JUNCTION BOXES, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(D)(2)] LABEL 9 SIGN LOCATED ON OR NO MORE THAN 3FT FROM INITIATION DEVICE [NEC 690.56(C)(2)]. LABEL 8 FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND CONDUCTORS LEAVING THE ARRAY: SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [NEC 690.56(C)(1)(A)] LABEL 1 PLACED ON THE MAIN DISCONNECTING MEANS FOR THE PV SYSTEM. [NEC 690.13(B)] LABELING NOTES: 1.LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. 2.LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRIC CODE, OSHA STANDARD 19010.145, ANSI Z535. 3.MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 4.LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC 110.21] 5.LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLY AFFIXED [IFC 605.11.1.1] 3 4 1 LABEL 4 PLACED ON EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUITS SUPPLYING POWER TO A BUSBAR OR CONDUCTOR SUPPLIED FROM MULTIPLE SOURCES [NEC 705.10(C)] 2 3 4 1 LABEL 2 FOR PV DISCONNECTING MEANS WHERE THE LINE AND LOAD TERMINALS MAY BE ENERGIZED IN THE OPEN POSITION. [NEC 690.13(B)] :$51,1*! 7(50,1$/6217+(/,1($1' /2$'6,'(60$<%((1(5*,=(' ,17+(23(1326,7,21 !:$51,1* 7+,6(48,30(17,6)('%<08/7,3/( 6285&(6727$/5$7,1*2)$// 29(5&855(17'(9,&(6(;&/8',1* 0$,16833/<29(5&855(17 '(9,&(6+$//127(;&((' $03$&,7<2)%86%$5 3+27292/7$,&$&',6&211(&7 5$7('$&287387&855(17 120,1$/23(5$7,1*$&92/7$*( (/(&75,&6+2&.+$=$5' 0$,13+27292/7$,& 6<67(0',6&211(&7 :$51,1*! 32:(56285&(287387&211(&7,21 '21275(/2&$7(7+,629(5&855(17'(9,&( :$51,1*!'8$/32:(56285&( 6(&21'6285&(,63+27292/7$,&6<67(0 3+27292/7$,&32:(56285&( TURN RAPID SHUTDOWN SWICH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY 62/$5396<67(0(48,33(' :,7+5$3,'6+87'2:1 62/$5(/(&75,& 393$1(/6 5$3,'6+87'2:1 6:,7&+)25 62/$5396<67(0 27 240 AC MSP M PV C JB JB Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: CAUTION DIRECTORY PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM. (ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED WITHIN: NEC 690.56(B)&(C), [NEC 705.10]) RAPID SHUTDOWN AC DISCONNECT SWITCH 16957 Evening Terrace, Lakeville MN 55044 FRONT OF HOME PLACARD - PV08 DRAWN BY: SoloCAD COMBINER MAIN DISTRIBUTION UTILITY DISCONNECT PV ARRAY SYSTEM UTILIZES MICROINVERTERS LOCATED UNDER EACH MODULE Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 SITE PHOTOS: SITE PHOTOS - PV09 DRAWN BY: SoloCAD Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 SITE PHOTOS: FRONT/BACK VIEWS - PV09.1 DRAWN BY: SoloCAD Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 SITE PHOTOS: SIDE VIEWS - PV09.2 DRAWN BY: SoloCAD Everlight Solar Construction 7369 HIGHWAY 13 W SAVAGE, MN 55378 License# BC 771658 833.786.4387 ext. 701 CONTRACTOR INFORMATION: SITE INFORMATION Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 AC SYSTEM SIZE: 6.576 kW AC DC SYSTEM SIZE: 7.935 kW DC Lat, 44.7035051 Long, -93.1845951999999 (23) Mission Solar MSE345SX5T PV MODULES (12) AP Systems YC600 INVERTER(S) Dakota Electric DATE: April 8, 2022 SITE PHOTOS: METER/OPEN MSP - PV09.3 DRAWN BY: SoloCAD Brand Name:Milbank Type:Wire Connector Kit Application:Metering Accessory Standard:UL Listed Connection:Mechanical Conductor Range:12 to 1/0 Awg Number Of Conductors: 0 Material:Aluminum Insulation:None Temperature Rating:75 Degrees Celsius Mounting:Slide Nut Consist Of:Slide Nut, Set Screw, Connector Utility requirements may vary. Always consult the serving utility for their requirements prior to ordering or installing this equipment. This product must always be installed by a licensed electrician. Installation of this equipment may require local electrical inspector approval. milbankworks.com K4977-INT 100A CONN AND SLIDE 784572274365 Catalog Number: Item Description: UPC Code: Everlight Solar Construction Attn.: To Whom It May Concern re job:Ali Mahbub 16957 Evening Terrace Lakeville, MN 55044 Design Criteria: Code:2018 IBC ASCE 7-16 Live Load:20 psf Ult Wind Speed:115 mph Exposure Cat:C Ground Snow:50 psf Min Roof Snow:NA Current Renewables Engineering Inc. Professional Engineer projects@creng.solar 4/12/2022 The following calculations are for the structural engineering design of the photovoltaic panels and are valid only for the structural info referenced in the stamped plan set. The verification of such info is the responsibility of others. After review, I certify that the roof structure has sufficient structural capacity for the applied PV loads. All mounting equipment shall be designed and installed per manufacturer's approved installation specifications. ϰͬϭϮͬϮϬϮϮ Job Code: Ali Mahbub 2 of 6 Roof Properties: Roof Type = Roof Pitch (deg) = Mean Roof Height (ft) = Attachment Trib Width (ft) = Attachment Spacing (ft) = Framing Type = Framing Size = Framing OC Spacing (in.) = Section Thickness, b (in.) = Section Depth, d (in.) = Section Modulus, Sx (in.^3) = Moment of Inertia, Ix (in.^4) = Framing Span (ft) = Deflection Limit D+L (in.) = Deflection Limit S or W (in.) = Framing Upgrade = Sister Size = Wood Species = Wood Fb (psi) = Wood Fv (psi) = Wood E (psi) = CD (Wind) = CD (Snow) = CM = Ct = CL = Ci = CF = Cfu = Cr = F'b_wind (psi) = F'b_snow (psi) = F'v_wind (psi) = F'v_snow (psi) = M_allowable_wind (lb-ft) = M_allowable_snow (lb-ft) = V_allowable_wind (lbs) = V_allowable_snow (lbs) = E' (psi) = Load Calculation: 725 1600000 456 1008 207 634 1785 288 1.15 2484 1.5 1.00 1.0 1.6 1.15 180 1600000 DF #2 900 Adequate NA 0.80 6 1.2 3.1 5.4 1.5 3.5 2x4 24 4 Truss 13 2.75 Shingle 39 Roof 1 Job Code: Ali Mahbub 3 of 6 Panels Dead Load (psf) = Roofing Weight (psf) = Decking Weight (psf) = Framing Weight (psf) = Misc. Additional Weight (psf) = Existing Dead Load (psf) = Total Dead Load (psf) = Ground Snow Load, pg (psf) = Min Flat Snow, pf_min (psf) = Min Sloped Snow, ps_min (psf) = Snow Importance Factor, Ic = Exposure Factor, Ce = Thermal Factor, Ct = Flat Roof Snow, pf (psf) = Slope Factore, Cs = Sloped Roof Snow, ps (psf) = Ultimate Wind Speed (mph) = Directionality Factor, kd = Topographic Factor, kzt = Velocity Press Exp Factor, kz = Ground Elevation Factor, ke = Velocity Pressure, qz (psf) = Array Edge Factor, ɶE = ^ŽůĂƌƋƵĂůŝnjĂƚŝŽŶ&ĂĐƚŽƌ͕ɶĂс External Pressure Up, GCp_1 = External Pressure Up, GCp_2 = External Pressure Up, GCp_3 = External Pressure Down, GCp = Design Pressure Up, p_1 (psf) = Design Pressure Up, p_2 (psf) = Design Pressure Up, p_3 (psf) = Design Pressure Down, p (psf) =17.1 -38.5 -47.0 0.8 -32.1 -1.8 -2.2 1.25 0.70 -1.5 0.85 1.00 24.4 115 0.85 1.0 Roof 1 35 Wind Load Calculations: 34.65 1.00 Roof 1 1.1 Snow Load Calculations: 50 NA NA 1.0 0.9 6.6 9.6 0.6 1.0 3.0 2.0 Dead Load Calculations: 3.0 Roof 1 Job Code: Ali Mahbub 4 of 6 Hardware Checks: Ref. Widthrawal Value, W (lb/in) = (CM = Ct = Ceg = 1.0) CD = Adjusted Widthrawal Value, W' (lb/in) = Lag Penetration, p (in.) = Allowable Widthrawal Force, W'p (lbs) = Applied Uplift Force (lbs) = Uplift DCR = Ref. Lateral Value, Z (lbs) = (CM = Ct = Cȴ = Ceg = 1.0) CD = Adjusted Lateral Value, Z' (lbs) = Applied Laeral Force (lbs) = Angle of Resultant Force, ɲ;ĚĞŐͿс Adjusted Interaction Lateral Value, Z'ɲ (lbs) = Lateral DCR = Roof Framing Checks: LC1: D+S Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC2: D+0.6W Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC3: D+0.75(S+0.6W) Applied Moment (lb-ft) = Applied Shear (lbs) = 260 260 0.19 0.12 634 1008 119 119 0.58 0.37 456 725 266 Force Checks: Roof 1 266 459 0.57 261 42 1.15 311 0.22 270 1064 -239 426 2.5 266 1.6 Lag Screw Checks: Roof 1 Job Code: Ali Mahbub 5 of 6 Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC4: 0.6D+0.6W Applied Moment (lb-ft) = Applied Shear (lbs) = Allowable Moment (lb-ft) = Allowable Shear (lbs) = Moment DCR = Shear DCR = LC1: D+L Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC2: S Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC3: W (Down) Deflection (in.) = Deflection Limit (in.) = Deflection DCR = LC4: W (Up) Deflection (in.) = Deflection Limit (in.) = Deflection DCR = Seismic Check: Wall Weight (psf) = Tributary Wall Area (ft2) = Total Wall Weight (lbs) = Roof Weight (psf) = Roof Area (ft2) = Total Roof Weight (lbs) = Total Existing Weight (lbs) = 1000 17000 7 2400 15844 32844 0.02 Existing Weight: 17 -0.02 0.80 0.80 0.01 0.06 0.01 0.05 0.80 1.2 0.02 Deflection Checks (Service Level): Roof 1 0.02 0.13 0.08 634 1008 81 81 0.41 0.26 634 1008 Job Code: Ali Mahbub 6 of 6 Total Additional PV Weight (lbs) = (Existing W + Additional W)/(Existing W) =104% The increase in weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. Limits of Scope of Work and Liability: Existing structure is assumed to have been designed and constructed following appropriate codes at time of erection, and assumed to have appropriate permits. The calculations produced are only for the roof framing supporting the proposed PV installation referenced in the stamped planset and were completed according to generally recognized structural analysis standards and procedures, professional engineering and design experience, opinions and judgements. Existing deficiencies which are unknown or were not observable during time of inspection are not included in this scope of work. All PV modules, racking, and mounting equipment shall be designed and installed per manufacturer's approved installation specifications. The Engineer of Record and the engineering consulting firm assume no responsibility for misuse or improper installation. This analysis is not stamped for water leakage. Framing was determined based on information in provided plans and/or photos, along with engineering judgement. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and spans noted in the stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any discrepancies prior to starting construction. Contractor shall also verify that there is no damaged framing that was not addressed in stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any concerns prior to starting construction. Additional PV Weight: 1252 Weight Increase: