LA202008 - Approved plans 17542 Five Oaks Drive PermitPlanSet
1.1.1PROJECT NOTES:1.1.2THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THENATIONAL ELECTRIC CODE (NEC) ARTICLE 690, ALLMANUFACTURERS’S LISTING AND INSTALLATION INSTRUCTIONS, ANDTHE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVINGJURISDICTION’S (AHJ) APPLICABLE CODES.1.1.3THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVEDAND PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION1.1.4ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVEINVERTERS, AND SOURCE CIRCUIT COMBINER BOXES AREIDENTIFIED AND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS ASREQUIRED BY NEC 690.4: PV MODULES: UL1703, IEC61730, ANDIEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL1741 ACCESSORY1.1.5MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDEDTEMP COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGECALCULATED ACCORDING TO NEC 690.7.1.1.6ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS,AND SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN APHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTEDFOR THE APPLICATION PER 690.4 (D). SHALL BE INSTALLEDACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING[NEC 110.3].1.1.7ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDINGCODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALLPLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THENEC AND AHJ.1.2.1 SCOPE OF WORK:1.2.2PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN ANDSPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEMRETROFIT. PRIME CONTRACTOR WILL BE RESPONSIBLE FORCOLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN, SPECIFY,AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THEPHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.1.3.1 WORK INCLUDES:1.3.2PV ROOF ATTACHMENTS - SNAP-N-RACK ULTRA RAIL SPEEDSEALFOOT1.3.3PV RACKING SYSTEM INSTALLATION - SNAPNRACK UR-601.3.4PV MODULE AND INVERTER INSTALLATION - JINKO EAGLE 72HM G2JKM400M-72HL-V / SOLAR EDGE SE11400H-US (240V)1.3.5PV EQUIPMENT GROUNDING1.3.6PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX1.3.7PV LOAD CENTERS (IF INCLUDED)1.3.8PV METERING/MONITORING (IF INCLUDED)1.3.9PV DISCONNECTS1.3.10PV FINAL COMMISSIONING1.3.11(E) ELECTRICAL EQUIPMENT RETROFIT FOR PV1.3.12SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODEGENERAL NOTESN2017CSCOPE OF WORKSYSTEM SIZE:STC: 28 X 400W = 11.200KWPTC: 28 X 367.7W = 10.296KW DC(28) JINKO EAGLE 72HM G2 JKM400M-72HL-V(1) SOLAR EDGE SE11400H-US (240V)ATTACHMENT TYPE: SNAP-N-RACK ULTRA RAIL SPEEDSEAL FOOTMSP UPGRADE: NOOWNERNAME:TIM ROCHEPROJECT MANAGERNAME:MUSA KEITAPHONE:763-226-4768CONTRACTORNAME:SOLAR ANGELS LLCPHONE: 763-226-4768AUTHORITIES HAVING JURISDICTIONBUILDING: CITY OF LAKEVILLE, MNZONING: CITY OF LAKEVILLE, MNUTILITY: DAKOTA ELECTRICDESIGN SPECIFICATIONSOCCUPANCY: IICONSTRUCTION: SINGLE-FAMILYZONING:RESIDENTIALGROUND SNOW LOAD: 50 PSFWIND EXPOSURE: BWIND SPEED: 115 MPHAPPLICABLE CODES & STANDARDSBUILDING: MSBC 2020,MSRC 2020ELECTRICAL: NEC 2020FIRE:MSFC 2020PROJECT INFORMATIONNEW PV SYSTEM: 11.200 kWpROCHE RESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024ASSESSOR'S #: 222087804060BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604T-001.00COVER PAGE(SHEET 1)01AERIAL PHOTONOT TO SCALENEWS02PLAT MAPNOT TO SCALESHEET LIST TABLESHEET NUMBERSHEET TITLET-001COVER PAGEG-001NOTESA-101SITE PLANA-102ELECTRICAL PLANA-103SOLAR ATTACHMENT PLANS-501ASSEMBLY DETAILSE-601LINE DIAGRAME-602DESIGN TABLESE-603PLACARDSR-001RESOURCE DOCUMENTR-002RESOURCE DOCUMENTR-003RESOURCE DOCUMENTR-004RESOURCE DOCUMENTR-005RESOURCE DOCUMENTR-006RESOURCE DOCUMENTR-007RESOURCE DOCUMENT5 OAKS DR NEC2019S2.1.1SITE NOTES:2.1.2A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHAREGULATIONS.2.1.3THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AUTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.2.1.4THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, ORBUILDING ROOF VENTS.2.1.5PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSEDELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.2.1.6ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED INACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'SINSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THEBUILDING OR STRUCTURE.2.2.1EQUIPMENT LOCATIONS2.2.2ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.2.2.3WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTEDOPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLES310.15 (B)(2)(A) AND 310.15 (B)(3)(C).2.2.3JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULESACCORDING TO NEC 690.34.2.2.4ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOTWITHIN SIGHT OF THE AC SERVICING DISCONNECT.2.2.5ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNELACCORDING TO NEC APPLICABLE CODES.2.2.6ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOORUSAGE WHEN APPROPRIATE.2.3.1STRUCTURAL NOTES:2.3.2RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TOCODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE ADESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND AMINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY,ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.2.3.3JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS.IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCALREQUIREMENTS.2.3.4ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED ANDSEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY A LICENSEDCONTRACTOR.2.3.5ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THESPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.2.3.6WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BESTAGGERED AMONGST THE ROOF FRAMING MEMBERS.2.4.1GROUNDING NOTES:2.4.2GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, ANDGROUNDING DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCHUSE.2.4.3PV SYSTEMS REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. ALL METALELECTRICAL EQUIPMENT AND STRUCTURAL COMPONENTS BONDED TO GROUND, INACCORDANCE WITH 250.134 OR 250.136(A). ONLY THE DC CONDUCTORS AREUNGROUNDED.2.4.4PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NECTABLE 250.122.2.4.5METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURECONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).2.4.6EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN INMANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOTUSED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIEDGROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATIONREQUIREMENTS.2.4.7THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THEREMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TOANOTHER MODULE.2.4.8GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREENOR MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]2.4.9THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, AGROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47AND AHJ.2.4.10DC PV ARRAYS SHALL BE PROVIDED WITH DC GROUND-FAULT PROTECTION MEETINGTHE REQUIREMENTS OF 690.41(B)(1) AND (2) TO REDUCE FIRE HAZARDS2.5.1INTERCONNECTION NOTES:2.5.2LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC705.12 (B)]2.5.3THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS OUTPUT MAYNOT EXCEED 120% OF BUSBAR RATING [NEC 705.12(B)(2)(3)].2.5.4THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUITCURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THEBUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THEBUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE LOCATED OPPOSITEEND OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(2)(3)].2.5.5AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTALRATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OFBUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BEEXCLUDED ACCORDING TO NEC 705.12 (B)(2)(3)(C).2.5.6FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12(B)(2)(1)2.5.7SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.12 (A) WITHSERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230.422.5.8BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPTFROM ADDITIONAL FASTENING [NEC 705.12 (B)(5)].2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:2.6.2DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCHIS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TOTHE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS).2.6.3DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BELOCKABLE, AND BE A VISIBLE-BREAK SWITCH.2.6.4BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED.THEREFORE BOTH MUST OPEN WHERE A DISCONNECT IS REQUIRED,ACCORDING TO NEC 690.13.2.6.5ISOLATING DEVICES OR EQUIPMENT DISCONNECTING MEANS SHALL BEINSTALLED IN CIRCUITS CONNECTED TO EQUIPMENT AT A LOCATION WITHINTHE EQUIPMENT, OR WITHIN SIGHT AND WITHIN 10 FT. OF THE EQUIPMENT. ANEQUIPMENT DISCONNECTING MEANS SHALL BE PERMITTED TO BE REMOTEFROM THE EQUIPMENT WHERE THE EQUIPMENT DISCONNECTING MEANS CANBE REMOTELY OPERATED FROM WITHIN 10 FT. OF THE EQUIPMENT,ACCORDING TO NEC 690.15 (A).2.6.6PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE ARAPID SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCYRESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D)2.6.7ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9,AND 240.2.6.8BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED,THEREFORE BOTH REQUIRE OVER-CURRENT PROTECTION, ACCORDING TONEC 240.21. (SEE EXCEPTION IN NEC 690.9)2.6.9IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTIONACCORDING TO NEC 690.11 AND UL1699B.2.7.1WIRING & CONDUIT NOTES:2.7.2ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODEREQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.2.7.3ALL CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.2.7.4EXPOSED PV SOURCE CIRCUITS AND OUTPUT CIRCUITS SHALL USE WIRELISTED AND IDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.31 (C)]. PVMODULES WIRE LEADS SHALL BE LISTED FOR USE ON PV ARRAYS,ACCORDING TO NEC 690.31 (A).2.7.5PV WIRE BLACK WIRE MAY BE FIELD-MARKED WHITE [NEC 200.6 (A)(6)].2.7.6MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY.2.7.7ACCORDING TO NEC 200.7, UNGROUNDED SYSTEMS DC CONDUCTORSCOLORED OR MARKED AS FOLLOWS: DC POSITIVE-RED, OR OTHER COLOR EXCLUDING WHITE, GRAY ANDGREENDC NEGATIVE- BLACK, OR OTHER COLOR EXCLUDING WHITE, GRAY ANDGREEN2.7.8AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTION NEUTRAL- WHITE OR GRAY* IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGETO BE MARKED ORANGE [NEC 110.15].N2017C N2017C BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604G-001.00NOTES(SHEET 2) GENERAL NOTES1.FIELD VERIFY ALL MEASUREMENTS2.ITEMS BELOW MAY NOT BE ON THIS PAGEPROPERTY LINEBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604A-101.00(SHEET 3)AREA OF WORKENTRANCESITE PLAN5 OAKS DRNEWS01/24" = 1'-0"SITE PLAN0112'24'PV METERAC DISCONNECTUTILITY METERINVERTER46'-7"25'-6"42'-0"34'-10" MODULE:JINKO EAGLE72HM G2 JKM400M-72HL-V400 WATTS39.45"79.06"GENERAL NOTES1.FIELD VERIFY ALL MEASUREMENTS2.ITEMS BELOW MAY NOT BE ON THIS PAGEFIRE CLEARANCEMODULE STRINGINGMODULE STRINGINGBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604A-102.00(SHEET 4)A(N) (1) JUNCTION BOXELECTRICAL PLAN01/8"=1'-0"ELECTRICAL PLAN014'8'ARRAY 1 - 6.400 kW[x16] (N) MODULESTILT: 28 DEGREESROOF PITCH: 6:12AZIMUTH: 25 DEGREESNEWSEXTERIOR PV EQUIPMENTINTERIOR PV EQUIPMENT(E) (1) UTILITY METER(N) (1) AC DISCONNECT(E) (1) MAIN ELECTRICAL PANEL(N) (1) INVERTER(N) (1) PV METERВARRAY 2 - 4.800 kW[x12] (N) MODULESTILT: 28 DEGREESROOF PITCH: 6:12AZIMUTH: 205 DEGREES3' FIRE ACCESS PATH3' FIRE ACCESS PATH3' FIRE ACCESS PATH3' FIRE ACCESS PATHВВВВВВВВВВВВВВAAAAAAAAAAAAAA GENERAL NOTES1.FIELD VERIFY ALL MEASUREMENTS2.ITEMS BELOW MAY NOT BE ON THIS PAGEROOF TRUSSESMODULE:JINKO EAGLE72HM G2 JKM400M-72HL-V400 WATTS39.45"79.06"BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604NEWS01/8"=1'-0"SOLAR ATTACHMENT PLAN014'8'FLUSH MOUNT SOLAR MODULESATTACHED TO ROOF SURFACE (SEESHEET S-501 FOR MOUNTING DETAILS)A-103.00(SHEET 5)SOLAR ATTACHMENT PLANROOF MATERIAL IS ASPHALT SHINGLE26'-5"26'-5" SHEET KEYNOTES1.ROOF MATERIAL: ASPHALT SHINGLE2.ROOF STRUCTURE: TRUSS3.ATTACHMENT TYPE: SNAP-N-RACK ULTRA RAIL SPEEDSEALFOOT4.MODULE MANUFACTURER: JINKO 5.MODULE MODEL: EAGLE 72HM G2 JKM400M-72HL-V6.MODULE LENGTH: 79.06''7.MODULE WIDTH: 39.45''8.MODULE WEIGHT: 49.6 LBS.9.SEE SHEET A-103 FOR DIMENSION(S)10.MIN. FIRE OFFSET: 3' FROM RIDGE/RAKE, 18" FROMHIPS/VALLEYS11.TRUSS SPACING: 24 IN. O.C.12.TRUSS SIZE: 2Х4 IN. NOMINAL13.LAG BOLT DIAMETER: 5/16 IN.14.LAG BOLT EMBEDMENT: 2-1/2 IN.15.TOTAL # OF ATTACHMENTS: 5516.TOTAL AREA: 606.46 SQ. FT.17.TOTAL WEIGHT: 1541.26 LBS.18.WEIGHT PER ATTACHMENT: 29.08 LBS.19.DISTRIBUTED LOAD: 2.54 PSF20.MAX. HORIZONTAL STANDOFF: 48 IN.21.MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH MODULEMANUFACTURER'S INSTRUCTIONS22.STANDOFF STAGGERING: YES23.RAIL MANUFACTURER (OR EQUIV.): SNAPNRACK24.RAIL MODEL (OR EQUIVALENT): UR-6025.RAIL WEIGHT: 0.6 PLF.26.MAX. TRUSS SPAN: N/A.27.MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.S-501D52011121413151822ROOF SLOPE 910106217S-501D43154252423827121.FIELD VERIFY ALL MEASUREMENTSGENERAL NOTESBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604S-501.00ASSEMBLY DETAILS(SHEET 6)D4DETAIL (TRANSVERSE)NOT TO SCALED5DETAIL (LONGITUDINAL)NOT TO SCALED1RACKING DETAIL (TRANSVERSE)NOT TO SCALED3RACKING DETAIL (TOP)NOT TO SCALED2RACKING DETAIL (LONGITUDINAL)NOT TO SCALE EQUIPMENT LEFTLINE IS (N) NEWEQUIPMENT RIGHTLINE IS (E) EXISTINGUNLESS OTHERWISENOTED.54(E) MAIN ELECTRICAL PANEL240/120 V 1Ø, 3WMAIN BUSS: 150 ATO UTILITYGRID (UG)L1L2NNNL2L1NGTO (E)LOADS150 A(E) MAIN(E) GROUNDINGELECTRODEGROUNDROD(E)UTILITYMETERF1-2GSW1ТАРV PV METERM13SOLAR EDGESE11400H-US (240V)JUNCTION BOX(28) SOLAR EDGE S440(28) JINKO EAGLE 72HMG2 JKM400M-72HL-VG2IN BRANCH1IN BRANCH 14BL1L2NGG1.PV SYSTEM EQUIPEED WITH RAPIDSHUTDOWN DISCONNECT PER NEC 690.122.SYSTEM COMPLIANT WITH NEC 690.1314AAC DISCONNECT, 60AFUSE, 60ACONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONSIDTYPICALCONDUCTORCONDUITCURRENT-CARRYINGCONDUCTORS IN CONDUITOCPDEGCTEMP. CORR.FACTORCONDUIT FILLFACTORCONT.CURRENTMAX. CURRENT(125%)BASE AMP.DERATEDAMP.TERM. TEMP. RATINGAMP. @ TERMINAL1210 AWG PV WIRE, COPPERFREE AIR2N/A10 AWG BARE, COPPER0.96 (32.1 °C)115A18.75A55A52.8A75°C50A2110 AWG THWN-2, COPPER0.75'' DIA EMT4N/A10 AWG THWN-2, COPPER0.96 (32.1 °C)0.815A18.75A40A30.72A75°C35A316 AWG THWN-2, COPPER0.75'' DIA EMT260A6 AWG THWN-2, COPPER0.96 (32.1 °C)147.5A59.38A75A72A75°C65A416 AWG THWN-2, COPPER0.75'' DIA EMT2N/A6 AWG THWN-2, COPPER0.96 (32.1 °C)147.5A59.38A75A72A75°C65A516 AWG THWN-2, COPPER0.75'' DIA EMT2N/A6 AWG THWN-2, COPPER0.96 (32.1 °C)147.5A59.38A75A72A75°C65AE-601.00(SHEET 7)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604LINE DIAGRAMAMODULE STRINGINGВMODULE STRINGING DISCONNECTSINVERTERSOCPDSPOWER OPTIMIZERSMODULESASHRAE EXTREME LOW-35.2°C (-31.4°F), SOURCE: AIRLAKE (44.63°; -93.22°)ASHRAE 2% HIGH32.1°C (89.8°F), SOURCE: AIRLAKE (44.63°; -93.22°)REF.QTY.RATED CURRENTMAX VOLTAGEF1-2260A240VACREF.QTY.MAKE AND MODELRATED CURRENTMAX RATED VOLTAGESW11SQUARE D D222NRB OR EQUIV.60A240VACREF.QTY.MAKE AND MODELPMAXPTCISCIMPVOCVMPTEMP. COEFF. OF VOCFUSE RATINGPM1-2828JINKO EAGLE 72HM G2 JKM400M-72HL-V400W367.7W10.61A9.96A49.1V40.16V-0.142V/°C (-0.29%/°C)20AREF.QTY.MODELRATED INPUT POWERMAX OUTPUT CURRENTMAX INPUT ISCMAX DC VOLTAGEWEIGHTED EFFICIENCYPO1-2828SOLAR EDGE S440440W15A14.5A60V98.6%REF.QTY.MAKE AND MODELACVOLTAGEGROUNDOCPDRATINGRATEDPOWERMAX OUTPUTCURRENTMAX INPUTCURRENTMAX INPUTVOLTAGECEC WEIGHTEDEFFICIENCYI11SOLAR EDGE SE11400H-US (240V)240VFLOATING60A11400W47.5A30.5A480V99.0%SYSTEM SUMMARYINVERTER #1STRING #1STRING #2POWERBOX MAX OUTPUT CURRENT15A15AOPTIMIZERS IN SERIES1414NOMINAL STRING VOLTAGE400V400VARRAY OPERATING CURRENT14A14AARRAY STC POWER11,200WARRAY PTC POWER10,296WMAX AC CURRENT47.5AMAX AC POWER11,400WDERATED (CEC) AC POWER10,050WBILL OF MATERIALSCATEGORYMAKEMODEL NUMBERREFQTYUNITQTY/UNITDESCRIPTIONMODULEJINKOEAGLE 72HM G2 JKM400M-72HL-VPM1-2828PIECES1JINKO EAGLE 72HM G2 JKM400M-72HL-V 400W 144 HALF-CELLS, MONOCRYSTALLINE SILICONINVERTERSOLAR EDGESE11400H-US (240V)I11PIECE1SOLAR EDGE SE11400H-US (240V) 11400W INVERTERMODULE OPTIMIZERSOLAR EDGES440PO1-2828PIECES1SOLAR EDGE S440 OPTIMIZER (REQUIRED PART OF INVERTER'S DISTRIBUTED DC ARCHITECTURE)DISCONNECTSQUARE DD222NRBSW11PIECE1SQUARE D D222NRB, FUSED, 2-POLE, 60A, 240VAC OR EQUIVALENTPRODUCTION METERGENERIC MANUFACTURERGEN-METER-80AM11PIECE1ELECTRICAL METER, OWNER APPROVEDWIRINGGEN-10-AWG-PV-WIRE-CUWR1180FEET110 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)WIRINGGEN-10-AWG-BARE-CUWR190FEET110 AWG BARE, COPPER (GROUND)WIRINGGEN-10-AWG-THWN-2-CU-RDWR240FEET110 AWG THWN-2, COPPER, RED (POSITIVE)WIRINGGEN-10-AWG-THWN-2-CU-BLKWR240FEET110 AWG THWN-2, COPPER, BLACK (NEGATIVE)WIRINGGEN-10-AWG-THWN-2-CU-GRWR220FEET110 AWG THWN-2, COPPER, GREEN (GROUND)WIRINGGEN-6-AWG-THWN-2-CU-RDWR3-530FEET16 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-6-AWG-THWN-2-CU-BLKWR3-530FEET16 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-6-AWG-THWN-2-CU-WHWR3-530FEET16 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIRINGGEN-6-AWG-THWN-2-CU-GRWR3-530FEET16 AWG THWN-2, COPPER, GREEN (GROUND)WIREWAYGEN-EMT-0.75'' DIAWW2-550FEET1EMT CONDUIT, 0.75'' DIAOCPDGENERIC MANUFACTURERGEN-FU-60A-240VACF1-22PIECES1FUSE, 60A, 240VACTRANSITION BOXGENERIC MANUFACTURERGEN-AWB-TB-4-4XJB11PIECE1TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKSE-602.00(SHEET 8)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604DESIGN TABLES MAIN DISTRIBUTIONUTILITY DISCONNECTFRONTBACK!CAUTION!POWER TO THIS BUILDING IS ALSO SUPPLIEDFROM ROOF MOUNTED SOLAR ARRAYS WITHSAFETY DISCONNECTS AS SHOWN:E-603.00(SHEET 9)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604NEWSPV ARRAYPLACARDSELECTRICAL SHOCK HAZARDTERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONWARNINGLABEL 1AT EACH DISCONNECTING MEANS FORPHOTOVOLTAIC EQUIPMENT (2" X 4").[NEC 690.13].POWER SOURCEOUTPUT CONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICEWARNINGLABEL 2AT POINT OF INTERCONNECTIONOVERCURRENT DEVICE (2" X 4").[NEC 705.12(B)(2)(3)(B)].WARNING: PHOTOVOLTAICPOWER SOURCELABEL 4AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRINGMETHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERESEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,OR FLOORS (5 3/4" X 1 1/8").[NEC 690.31(G)]LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;REFLECTIVE[IFC 605.11.1.1]RAPID SHUTDOWNSWITCH FORSOLAR PV SYSTEMLABEL 5AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2").[NEC 690.56(C)(3)].LABEL 9AT EACH AC DISCONNECTING MEANS(4" X 1").[NEC 690.13(B)].LABEL 10AT EACH DC DISCONNECTING MEANS(4" X 1").[NEC 690.13(B)].SOLAR PV SYSTEMEQUIPPED WITHRAPID SHUTDOWNTURN RAPID SHUTDOWN SWICH TOTHE "OFF" POSITION TO SHUT DOWNPV SYSTEM AND REDUCE SHOCKHAZARD IN ARRAYSOLAR ELECTRICPV PANELSLABEL 3AT RAPID SHUTDOWN SYSTEM(3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)].LABELING NOTES1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE,INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z5351.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVINGJURISDICTION.1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENTINVOLVED.1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE REDBACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVEYELLOW BACKGROUND. [ANSI Z535]1.6 ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHERRESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B)PHOTOVOLTAIC SYSTEMAC DISCONNECTRATED AC OUTPUT CURRENTNOMINAL OPERATING AC VOLTAGELABEL 11AT POINT OF INTERCONNECTION, MARKEDAT DISCONNECTING MEANS (4" X 2").[NEC 690.54]INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTEDPHOTOVOLTAIC SYSTEM DISCONNECT LOCATEDSE SIDE OF THE HOUSEDIRECTORYPERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICEDISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTINGMEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").[NEC 690.56(B)]WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, ADIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PVSYSTEM DISCONNECTING MEANS.PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED INBATHROOMS[NEC 690.4(D),(E)]PHOTOVOLTAIC SOLARAC DISCONNECTCAUTIONSOLAR ELECTRIC SYSTEM CONNECTEDLABEL 6AT UTILITY METER (5 3/4" X 1 1/8")[NEC 690.56(B)]LABEL 12AT EACH DC DISCONNECTINGMEANS (3" X 4").[NEC 690.53].WARNINGDUAL POWER SUPPLYSOURCES: UTILITY GRIDAND PV SOLARELECTRIC SYSTEMLABEL 7AT POINT OF INTERCONNECTION(2 3/4" X 1 5/8").[NEC 705.12(B)(3)]WARNINGSOLAR ELECTRICCIRCUIT BREAKERIS BACKFEDLABEL 8AT POINT OF INTERCONNECTION(2" X 1").[NEC 705.12(B)(3)]PHOTOVOLTAIC SOLARDC DISCONNECT47.5AV240MAXIMUM VOLTAGE: V DCMAXIMUM CIRCUIT CURRENT: A DCMAX RATED OUTPUT CURRENT OFTHE CHARGE CONTROLLEROR DC-TO-DC CONVERTER A DC3028480DIRECT CURRENTPHOTOVOLTAIC POWER SOURCE BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604R-001.00(SHEET 10)RESOURCE DOCUMENT BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604R-002.00(SHEET 11)RESOURCE DOCUMENT G:\Work\Sadovenko group\292009\264548_R1\CAD\PDF Images\(2) Documentf0542aff.pngSingle Phase Inverter with HD-Wave Technologyfor North AmericaSE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/SE7600H-US / SE10000H-US / SE11400H-USMODEL NUMBERADDITIONAL FEATURESSupported Communication InterfacesRevenue Grade Metering, ANSI C12.20Consumption meteringInverter CommissioningRapid Shutdown - NEC 2014, NEC2017 and NEC 2020, 690.12STANDARD COMPLIANCESafetyGrid Connection StandardsEmissionsINSTALLATION SPECIFICATIONSAC Output Conduit Size / AWG RangeDC Input Conduit Size / # of Strings /AWG RangeDimensions with Safety Switch (HxWxD)Weight with Safety SwitchNoiseCoolingOperating Temperature RangeProtection Rating22 / 10< 25Natural Convection-40 to +140 / -40 to +60(4)NEMA 4X (Inverter with Safety Switch)(3) Inverter with Revenue Grade Meter P/N: SExxxxH-US000BNC4; Inverter with Revenue Grade Production and Consumption Meter P/N: SExxxxH-US000BNI4 . For consumption metering, current transformersshould be ordered separately: SEACT0750-200NA-20 or SEACT0750-400NA-20. 20 units per box(4) Full power up to at least 50˚C / 122˚F; for power de-rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-derating-note-na.pdfHow to Enable Consumption MonitoringBy simply wiring current transformers through the inverter's existing AC conduits and connecting them to the servicepanel, homeowners will gain full insight into their household energy usage helping them to avoid high electricity bills˚F / ˚CSE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-USRS485, Ethernet, ZigBee (optional), Cellular (optional)Optional(3)With the SetApp mobile application using Built-in Wi-Fi Access Point for Local ConnectionAutomatic Rapid Shutdown upon AC Grid DisconnectUL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07IEEE1547, Rule 21, Rule 14 (HI)FCC Part 15 Class B1'' Maximum / 14-6 AWG1'' Maximum / 1-2 strings / 14-6 AWG17.7 x 14.6 x 6.8 / 450 x 370 x 17425.1 / 11.426.2 / 11.91'' Maximum /14-4 AWG1'' Maximum / 1-3 strings / 14-6 AWG21.3 x 14.6 x 7.3 / 540 x 370 x 185 in / mmlb / kg38.8 / 17.6<50dBA© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo , OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. Allother trademarks mentioned herein are trademarks of their respective owners. Date: 12/2020/V01/ENG NAM. Subject to change without notice.BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604R-003.00(SHEET 12)RESOURCE DOCUMENT BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604R-004.00(SHEET 13)RESOURCE DOCUMENT BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604R-005.00(SHEET 14)RESOURCE DOCUMENT BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604R-006.00(SHEET 15)RESOURCE DOCUMENT TIM ROCHE (2.1.4)2022-05-06T17:47:52-0400Ultra Rail Configuration Tool ReportCompany Name: Solar Angels, LLCProject Name: TIM ROCHEProposed Bill of Materials:Part Number232-02540242-01270242-02070242-02072232-02484242-01220242-92266232-01375242-02101Create Date: 2022-05-06T17:47:52-0400Bill of Materials #197468DescriptionSNAPNRACK, UR-60 RAIL, 172IN, SILVERSNAPNRACK, UR-60 SPLICE, SILVERSNAPNRACK, ULTRA RAIL MID CLAMP, SILVERSNAPNRACK, ULTRA RAIL END CLAMP, SILVERSNAPNRACK, UR-60 END CAPSNAPNRACK, ULTRA RAIL UMBRELLA L FOOT, BLACKSNAPNRACK, UMBRELLA LAG, TYPE 3, 4IN, SSSNAPNRACK, COMP FLASHING, 9IN X 12IN, BLACK ALUMSNAPNRACK, GROUND LUG ASSEMBLY, 6-12 AWGSystem Total Weight:Qty14844161652525241464.37 lbsBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM: 11.200 kWpRATED AC POWER OUTPUT :11400 @ 240VENGINEER OF RECORD05.02.2022DESIGN BY:T.M.M.M.ROCHERESIDENCE17542 5 OAKS DR FARMINGTON, MN 55024APN: 222087804060PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORSOLAR ANGELS LLCPHONE:LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:763-226-4768140 124TH LN NWCOON RAPIDS, MN 55448EA791604R-007.00(SHEET 16)RESOURCE DOCUMENT