HomeMy WebLinkAboutLA205318-APPROVED - Josh VanDeraa Permitplans 08052022 stampedUM
AC
BG
PM
AC
CB
CL
BT
SITE PLAN-1
PV-1.0
JOSHUA VANDERAA - 9.600kW DC, 6.960kW AC, 13.500kWH STORAGE SYSTEM
SITE PLAN-1
PV-1.0
A SITE PLAN-1
SCALE: 3/32" = 1'-0"
INDEX
INDEX NO.DESCRIPTION
SITE PLAN-1
SITE PLAN-2
GENERAL NOTES
MOUNTING DETAILS
STRUCTURAL DETAILS
SINGLE LINE DIAGRAM
ELECTRICAL CALCULATION
WARNING PLACARDS
SPEC SHEET(S)
PV-1.0
PV-1.1
PV-2.0
PV-3.0
PV-3.1
PV-4.0
PV-4.1
PV-5.0
SS
ELECTRIC CODE NEC 2020
FIRE CODE MFC 2020
RESIDENTIAL CODE MRC 2020
BUILDING CODE MBC 2020
WIND SPEED 115 MPH
SNOW LOAD 50 PSF
GENERAL INFORMATION
PHOTOVOLTAIC ARRAY ON THE ROOF
PV-1.0
A1 VICINITY MAP
SCALE: NTS
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
NOTE:
1.NO CLEARANCE ISSUES WITH EXISTING OVERHEAD LINES
2.UTILITY PV PRODUCTION METER AND PV UTILITY DISCONNECTS ARE
·LOCATED WITHIN 10' OF MAIN SERVICE/BILLING METER
·VISIBLE,LOCKABLE,READILY ACCESSIBLE AND 24/7 ACCESS
3.DESIGN COMPLY WITH NEC AND NEC690
4.LABELS SHALL BE WEATHERPROOF,DURABLE,AND PERMANENTLY MOUNTED
5.24/7 UNESCORTED KEYLESS ACCESS TO METERS AND UTILITY AC
DISCONNECTS.
6..SECONDARY INTERCONNECTION.
ACCOUNT #200005557756
METER #1ND93994758
NOTE:
1. MICRO INVERTERS ARE UL 1741 RATED.
2. MODULES ARE UL1703 RATED.
NOTE:
CONDUIT RUN IN ATTIC.
(N) ENPHASE IQ COMBINER 4(EXTERIOR)
(N) UTILITY PV PRODUCTION METER(EXTERIOR)
1'-6" FIRE SETBACK
(N)TESLA BACKUP GATEWAY 2 (EXTERIOR)
(N) UTILITY AC DISCONNECT(EXTERIOR)
(E) MAIN SERVICE METER WITH
DISCONNECT(EXTERIOR)
3'-0" FIRE SETBACK
1' MIN
CLEARANCE
(N)CRITICAL LOAD PANEL(INTERIOR)
(N) UTILITY BATTERY DISCONNECT(EXTERIOR)
(N) TESLA POWERWAL II (INTERIOR)
44'22'-10"DISTANCE BETWEEN EQUIPMENT
FROM TO DISTANCE(FT)
MODULE ENPHASE IQ
COMBINER 4 30
ENPHASE IQ COMBINER
4
UTILITY AC
DISCONNECT 1
UTILITY AC
DISCONNECT
UTILITY PV
PRODUCTION
METER
1
UTILITY PV
PRODUCTION METER
TESLA BACKUP
GATEWAY 2 1
TESLA BACKUP
GATEWAY 2
MAIN SERVICE
METER WITH
DISCONNECT
2
TESLA POWERWALL
II
UTILITY BATTERY
DISCONNECT 1
UTILITY BATTERY
DISCONNECT
TESLA BACKUP
GATEWAY 2 1
TESLA BACKUP
GATEWAY 2
CRITICAL LOAD
PANEL 1
UM
AC
BG
PM
AC
CB
CL
BT
SITE PLAN-2
PV-1.1
JOSHUA VANDERAA - 9.600kW DC, 6.960kW AC, 13.500kWH STORAGE SYSTEM
SITE PLAN-2
PV-1.1
A SITE PLAN-2
SCALE: 1/16" = 1'-0"
PHOTOVOLTAIC ARRAY ON THE ROOF
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
PROPERTY LINEDRIVE WAY182N
D
S
T
W
WALK
W
A
Y104'-10"66'-1
0
"104'-10"18'-1"6'-2"6'-7"36'-11"
GENERAL NOTES
PV-2.0
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
GENERAL NOTES
GENERAL NOTES
1.MODULES ARE LISTED UNDER UL 1703 AND CONFORM TO THE STANDARDS.
2.INVERTERS ARE LISTED UNDER UL 1741 AND CONFORM TO THE STANDARDS.
3.DRAWINGS ARE DIAGRAMMATIC, INDICATING GENERAL ARRANGEMENT OF THE PV SYSTEM AND THE ACTUAL
SITE CONDITION MIGHT VARY.
4.WORKING CLEARANCES AROUND THE NEW PV ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN
ACCORDANCE WITH NEC CODE.
5.ALL GROUND WIRING CONNECTED TO THE MAIN SERVICE GROUNDING IN MAIN SERVICE PANEL/ SERVICE
EQUIPMENT.
6.ALL CONDUCTORS SHALL BE 600V, 75°C STANDARD COPPER UNLESS OTHERWISE NOTED.
7.WHEN REQUIRED, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA
REGULATIONS.
8.THE SYSTEM WILL NOT BE INTERCONNECTED BY THE CONTRACTOR UNTIL APPROVAL FROM THE LOCAL
JURISDICTION AND/OR THE UTILITY.
9.ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND
LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING
CONSTRUCTION WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS
TREES, WIRES OR SIGNS.
10.PV ARRAY COMBINER/JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING
EQUIPMENT LOCATION:
11.ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC CODE.
12.WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING
TEMPERATURE AS SPECIFIED BY NEC CODE AND NEC TABLES.
13.JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC CODE.
14.ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE
AC SERVICING DISCONNECT.
15.ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC
APPLICABLE CODES.
16.ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE
.
STRUCTURAL NOTES:
17.RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION
MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND
A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL
MANUFACTURER’S INSTRUCTIONS.
18.JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT
SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS.
19.ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED WITH APPROVED CHEMICAL
SEALANT PER CODE BY A LICENSED CONTRACTOR.
20.ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY
THE RACKING MANUFACTURER.
21.WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF
FRAMING MEMBERS.
WIRING & CONDUIT NOTES:
22.ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE
SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.
23.CONDUCTORS SIZED ACCORDING TO NEC CODE.
24.DC WIRING LIMITED TO MODULE FOOTPRINT. MICRO INVERTER WIRING SYSTEMS SHALL BE LOCATED AND
SECURED UNDER THE ARRAY WITH SUITABLE WIRING CLIPS.
25.AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR
OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION
NEUTRAL- WHITE OR GREY IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO
BE MARKED ORANGE [NEC CODE].
INTERCONNECTION NOTES:
26.LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC CODE]
27.THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAY NOT EXCEED 120% OF BUSBAR
RATING [NEC CODE].
28.WHEN SUM OF THE PV SOURCES EQUALS >100% OF BUSBAR RATING, PV DEDICATED BACKFFED BREAKERS
MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC CODE].
29.AT MULTIPLE PV OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVER CURRENT DEVICES SHALL NOT
EXCEED AMPACITY OF BUSBAR. HOWEVER, THE COMBINED OVER CURRENT DEVICE MAY BE EXCLUDED
ACCORDING TO NEC CODE.
30.FEEDER TAP INTER CONNECTION (LOAD SIDE) ACCORDING TO NEC CODE
31.SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC CODE (A) WITH SERVICE ENTRANCE
CONDUCTORS IN ACCORDANCE WITH NEC CODE
32. BACK FEEDING BREAKER FOR UTILITY-INTERACTIVE INVERTER OUTPUT IS EXEMPT FROM ADDITIONAL
FASTENING [NEC CODE].
GROUNDING NOTES:
33.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES
EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE.
34.PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC CODE AND MINIMUM NEC TABLE.
35.METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN
ACCORD.
36.EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC CODE AND MICRO INVERTER
MANUFACTURER'S INSTRUCTIONS.
37.EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER
DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST
BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION
REQUIREMENTS.
38.THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE
DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE.
39.GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR MARKED GREEN IF
#4 AWG OR LARGER [NEC CODE]
40.THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC CODE. IF EXISTING SYSTEM IS INACCESSIBLE,
OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC CODE AND AHJ.
41.GROUND-FAULT DETECTION SHALL COMPLY WITH NEC CODE IN GENERAL AND NEC CODE SPECIFICALLY.
42.DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
43.DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS
REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER
TERMINALS).
44.DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A
VISIBLE-BREAK SWITCH
45.RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 10 FT OF PV ARRAY OR 5 FT INSIDE A BUILDING
WITHIN 10 SECONDS. CONTROLLED CONDUCTORS ≤30V AND ≤240VA [NEC CODE]. LOCATION OF LABEL
ACCORDING TO AHJ.
46.ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC CODE.
47.MICRO INVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN ACCORDANCE WITH
NEC CODE. 2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING
TO NEC CODE AND UL1699B.
MOUNTING DETAILS
PV-3.0
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
PV-3.0
B MOUNTING DETAILS
SCALE:1/8" = 1'-0"
DEAD LOAD CALCULATIONS
BOM QUANTITY LBS/UNIT TOTAL
WEIGHT (LBS)
MODULES 24 45 1080.00
MID-CLAMP 34 0.050 1.70
END-CLAMP 28 0.050 1.40
RAIL LENGTH 171 0.680 116.28
SPLICE BAR 4 0.360 1.44
SNAPNRACK FLASHED L
FOOT 48 1.35 64.80
MICRO-INVERTER 24 2.38 57.12
TOTAL WEIGHT OF THE SYSTEM (LBS)1322.74
TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)478.00
WEIGHT PER SQ. FT.(LBS)2.77
WEIGHT PER PENETRATION (LBS)27.56
MODULES DATA
REC SOLAR REC400AA PURE
MODULE DIMS 71.7"x40"x1.2"
LAG SCREWS 5/16"x3.5":2.5"MIN EMBEDMENT
UPLIFT CALCULATIONS
UPLIFT 14340.0 LBS
PULL OUT STRENGTH 29520 LBS
POINT LOADING 23 LBS
MINIMUM FIRE ACCESS PATHWAYS PER MFC 2020
RIDGE TO ARRAY: 1'-6"
EAVE TO ARRAY : 3'-0"
HIP/VALLEY W/ ADJACENT ARRAY: 1'-6"
EACH SIDE HIP/VALLEY W/O ADJACENT ARRAY: 0'-0"
NOTE: INSTALLER TO VERIFY RAFTER SIZE, SPACING AND SLOPED
SPANS, AND NOTIFY ANY DISCREPANCIES BEFORE PROCEEDING.
FIRE SETBACK
2 X 4 PRE-FABRICATED TRUSSES@2'-0"SPACING
ALUMINIUM RAIL
SITE INFORMATION
SR.NO AZIMUTH PITCH NO. OF
MODULES
ARRAY AREA
(SQ. FT.)ROOF TYPE ATTACHMENT ROOF
EXPOSURE FRAME TYPE FRAME
SIZE
FRAME
SPACING
MAX RAIL
SPAN
OVER
HANG
MP-01 198°26°20 398.3 ASPHALT
SHINGLE
SNAPNRACK
FLASHED L FOOT ATTIC PRE-FABRICATED
TRUSSES 2 X 4 2'-0"4'-0"2'-0"
MP-02 288°33°2 39.8 ASPHALT
SHINGLE
SNAPNRACK
FLASHED L FOOT ATTIC PRE-FABRICATED
TRUSSES 2 X 4 2'-0"4'-0"2'-0"
MP-03 108°33°2 39.8 ASPHALT
SHINGLE
SNAPNRACK
FLASHED L FOOT ATTIC PRE-FABRICATED
TRUSSES 2 X 4 2'-0"4'-0"2'-0"
ARRAY MP-02
ARRAY MP-03ARRAY MP-01
6'1'-6"3'
26'-8"17'-11"9'-4"6'-8"6'-8"6'
STRUCTURAL DETAILS
PV-3.1
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
MID-CLAMP & END CLAMP DETAIL
GROUNDING DETAILS
5/16"-18 SS BOLT
SS SPLIT LOCK WASHER
(TORQUE TO 16FT-LBS)
SNAPNRACK
GROUNDING LUG
BOUNDING
CHANNEL NUT
RAIL
6-12 AWG BARE
COPPER WIRE
NOTES:
·ALL HARDWARE IS INCLUDED FROM MANUFACTURER
·A MINIMUM OF ONE GROUND LUG IS TO BE INSTALLED ON EVERY
CONTINUOUS ROW OF MODULES
·GROUNDING LUG MAY BE INSTALLED IN EITHER RAIL CHANNEL
·GROUNDING LUG MAY BE INSTALLED SO GROUND WIRE IS PARALLEL
OR PERPENDICULAR TO RAIL
·ENSURE SPLIT LOCK WASHER IS INSTALLED ON TOP OF COPPER WIRE.
SCALE:NTS
SS BONDING PIN
MID CLAMP
ASSEMBLY
MODULE
FRAME
RAIL
CHANNEL NUT
SNAPNRACK GROUNDING MID-CLAMP
SCALE: NTS
NTS REMOVAL OF ONE PIECE OF EQUIPMENT SHALL NOT DISCONNECT THE
BONDING CONNECTION BETWEEN ANY OTHER PIECES.
SCALE:NTS
GROUND BONDING
JUMPERRACKING
PV MODULE SELF TAPING SCREW
MODULE TO MODULE & MODULE TO RAIL
SNAPNRACK GROUNDING
RAIL TO RAIL
PV MODULE
RAIL END CLAMP
PV MODULE
RAIL
MID CLAMP
SCALE: NTS
SCALE: NTS
5/16 HEX-BOLT
STAINLESS STEEL 5/16" HANGER
BOLT 2.5" EMBEDMENT
PILOT HOLE REQUIRED
(E)ASPHALT SHINGLE ROOF
SNAPNRACK FLASHED L FOOT
SNAPNRACK ULTRA RAIL
PV MODULE
(E) BUILDING
STRUCTURE
ATTACHMENT DETAIL-SNAPNRACK FLASHED L FOOT
SCALE: NTS
ROOF FRAMING DETAIL
SNAPNRACK
FLASHED L FOOT
SOLAR MODULE
RAIL
6" MAX
2 X 4 PRE-FABRICATED TRUSSES@2'-0" SPACING
LOAD BEARING WALL
13
(N)60A UTILITY
AC DISCONNECT
3
MIN.1'MIN.1'
(N)(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
WITH
(24)REC SOLAR REC400AA PURE MODULES
(1) BRANCH OF (12) MICRO-INVERTERS(12 MODULES),
(1) BRANCH OF (12) MICRO-INVERTERS(12 MODULES),
(N)REC SOLAR REC400AA PURE MODULES
APPROX.5'
(N)SOLADECK
SOLADECK PV
ROOFMOUNT AC
ENCLOSURE BOX
2
APPROX.25'
AC COMBINER WITH ENPHASE
ENVOY-S EN-X-IQ-AM1-240-4
120/240V, 1PH, 3W NEMA 3R
INSTALL (2) 20A 2P PV
BREAKERS(ONLY FOR SOLAR
NO LOAD TO BE ADDED)
LOCATED ON SOUTH-WEST
EXTERIOR WALL OF THE
HOUSE
(N)ENPHASE IQ
COMBINER 4
20A
60A UTILITY AC DISCONNECT
NON FUSED 120/240V, 2P 1-PH,3W
-LOCATED ON SOUTH-WEST EXTERIOR
WALL OF THE HOUSE -DISCONNECT IS
LOCATED WITHIN 1' OF UTILITY PV
PRODUCTION METER-VISIBLE BLADE,
OPEN-TYPE LOCKABLE,AND READILY
ACCESSIBLE
REFERENCE POINT OF
APPLICABILITY
15A
20A
3
MIN.1'
(N) UTILITY PV
PRODUCTION METER
M
LINE/TOP SIDE
LOAD/BOTTOM SIDE
UTILITY PV PRODUCTION METER
200A, 120/240V 1-PH 3W
W/ BYPASS HANDLE MILBANK
U4801-XL-5T9 LOCATED ON
SOUTH-WEST WALL OF THE HOUSE
40A
MAIN SERVICE METER WITH
DISCONNECT 200A
120/240V,1-PHASE, 2P,3W
LOCATED ON THE SOUTH-WEST
EXTERIOR WALL OF THE HOUSE
.
M
EXISTING 200A MAIN
SERVICE METER
120/240V 1PH,2P,3W 60HZ
EPS
UTILITY: DAKOTA ELECTRIC
ASSOCIATION
1ND93994758
3
4
30A
(N)TESLA BACKUP
GATEWAY 2
APPROX.2'
(N)30A UTILITY BATTERY
AC DISCONNECT
(N) TESLA POWERWALL II
13.5KWH,5KW
120/240V,1-PH,3W LOCATED
ON GARAGE INTERIOR
3A
MIN.1'APPROX.3'
3A
UTILITY BATTERY DISCONNECT
NON FUSED 30A, 120/240V, 2P
1-PHASE 3W -LOCATED ON
SOUTH-WEST EXTERIOR WALL OF THE
HOUSE
(N)100A CRITICAL
LOAD PANEL
100A LOAD PANEL 120/240V
1PH, 3W LOCATED ON THE
SOUTH-WEST INTERIOR
WALL OF THE HOUSE
100A
200A
(E)GROUND
ELECTRODE
40A 2P
BREAKER
SINGLE LINE DIAGRAM
PV-4.0
SINGLE LINE DIAGRAM: DC SYSTEM SIZE - 9600W, AC SYSTEM SIZE - 6960W, 13500WH STORAGE SYSTEM
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
CONDUIT SCHEDULE
TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND
1 NONE (4) 12 AWG ENPHASE Q CABLE
PER BRANCH CIRCUIT NONE (1) 6 AWG BARE COPPER
2 3/4"EMT OR EQUIV (4) 10 AWG THHN/THWN-2 NONE (1) 10 AWG THHN/THWN-2
3 3/4"EMT OR EQUIV (2) 8 AWG THHN/THWN-2 (1) 8 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2
3A 3/4"EMT OR EQUIV (2) 10 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2
4 1"EMT OR EQUIV (2) 3 AWG THHN/THWN-2 (1) 3 AWG THHN/THWN-2 (1) 8 AWG THHN/THWN-2
NOTE:
1.EACH MICRO INVERTERS ARE RAPID SHUT COMPLIANT
2.MICROINVERTERS ARE UL 1741 RATED
NOTES:
1. UTILITY PV PRODUCTION METER AND PV UTILITY DISCONNECTS ARE
·LOCATED WITHIN 10' OF MAIN SERVICE/BILLING METER
·VISIBLE,LOCKABLE,READILY ACCESSIBLE AND 24/7 ACCESS
2.SYSTEM PEAK CURRENT 29.04AMPS, 120/240V, 1 PHASE,3-WIRE
3.PV MODULES UL1703
4.MICRO INVERTER UL 1741
5.THE SITE HAS 24/7 KEYLESS ACCESS TO METERS AND UTILITY AC DISCONNECTS.
6.NO CLEARANCE CONCERNS EXISTING WITH UNDERGROUND SERVICE ENTRANCE
CONDUCTORS.
7.SECONDARY INTERCONNECTION
8.DESIGN SHALL MEET NEC 2020
DISTANCE BETWEEN EQUIPMENT
FROM TO DISTANCE(FT)
MODULE ENPHASE IQ
COMBINER 4 30
ENPHASE IQ COMBINER
4
UTILITY AC
DISCONNECT 1
UTILITY AC
DISCONNECT
UTILITY PV
PRODUCTION
METER
1
UTILITY PV
PRODUCTION METER
TESLA BACKUP
GATEWAY 2 1
TESLA BACKUP
GATEWAY 2
MAIN SERVICE
METER WITH
DISCONNECT
2
TESLA POWERWALL
II
UTILITY BATTERY
DISCONNECT 1
UTILITY BATTERY
DISCONNECT
TESLA BACKUP
GATEWAY 2 1
TESLA BACKUP
GATEWAY 2
CRITICAL LOAD
PANEL 1
OCPD CALCULATIONS:
MAIN PANEL RATING:200A,
MAIN BREAKER RATING:200A
120% RULE: (200AX1.2)-200A=40A
=>ALLOWABLE BACKFEED IS 40A
INVERTER OVERCURRENT PROTECTION=
INVERTER O/P I X CONTINUOUS LOAD(1.25)X
#OF INVERTERS =1.21x1.25x24=36.30 A
=>PV BREAKER = 40A
ALLOWABLE BACKFEED 40A =>40A PV BREAKER
THE DESIGNED INTERCONNECTION MEETS THE
705.12(D)(2) REQUIREMENTS
ELECTRICAL CALCULATION
PV-4.1
ELECTRICAL CALCULATION
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
MODULE SPECIFICATION
MODEL REC SOLAR REC400AA PURE
MODULE POWER @ STC 400W
OPEN CIRCUIT VOLTAGE:Voc 48.8V
MAX POWER VOLTAGE:Vmp 42.1V
SHORT CIRCUIT CURRENT:Isc 10.25A
MAX POWER CURRENT:Imp 9.51A
MICRO INVERTER SPECIFICATIONS
MODEL ENPHASE
IQ8PLUS-72-2-US(240V,1PH)
POWER RATING 290W
MAX OUTPUT CURRENT 1.21A
CEC WEIGHTED EFFICIENCY 97%
MAX NO OF MICRO INVERTERS/BRANCH 13
MAX DC VOLTAGE 60V
ELECTRICAL NOTES:
1. MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%.
2. BREAKER/FUSE SIZES CONFORMS TO NEC 240.6 CODE SECTION.
3. AC GROUNDING ELECTRODE CONDUCTOR SIZED PER NEC 250.66.
4. AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON NEC 690.31(A).
5. AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON NEC 310.15(B)(2).
6. MAX. SYSTEM VOLTAGE CORRECTION IS PER NEC 690.7.
7. CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE NEC 310.15(B)(16).
8. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER NEC 310.10(D).
9. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER NEC 310.10(C).
AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C
TAG
ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION TERMINAL RATING CHECK DERATED CONDUCTOR AMPACITY CHECK
1 1.21 X 12 =14.52 X 1.25 =18.15A 30 X 0.96 X 1 =28.80A 18.15A <25A 18.15A <28.80A
2 1.21 X 12 =14.52 X 1.25 =18.15A 40 X 0.96 X 0.8 =30.72A 18.15A <35A 18.15A <30.72A
3 1.21 X 24 =29.04 X 1.25 =36.30A 55 X 0.96 X 1 =52.80A 36.30A <50A 36.30A <52.80A
4 100 X 1 =100.00 X 1.00 =100.00A 115 X 0.96 X 1 =110.40A 100.00A ≤100A 100.00A <110.40A
ELECTRICAL CALCULATION
UM
AC
BG
PM
AC
CB
CL
BT
PV-5.0
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS SHALL BE RED
WITH WHITE LETTERING U.O.N.
PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE.FASTENERS
APPROVED BY THE LOCAL JURISDICTION
7063 182ND STREET, LAKEVILLE, MN 55044.WARNING PLACARDS
SYSTEM UTILIZES
MICRO-INVERTERS
LOCATED UNDER
SOLAR MODULE
WARNING PLACARDS
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED
AS SHOWN
WARNING !
NOTE:ALL SIGNAGE CANNOT BE HAND WRITTEN NEC 110.21
LABEL LOCATION
UTILITY AC DISCONNECT
UTILITY AC
DISCONNECT
NOTE:ALL PLACARDS SHALL BE OF WEATHER PROOF
CONSTRUCTION, DURABLE PERMANENTLY MOUNTED,
AND COMPLY TO NEC 690
GENERATION SYSTEM
CONNECTED
LABEL LOCATION
MAIN SERVICE METER
WARNING
CAUTION: SOLAR CIRCUIT
LABEL LOCATION
POINT OF INTERCONNECTION
(PER CODE: NEC 705.12(2)(b)
[ Not Required if Panel board is rated not less than sum of ampere ratings
of all overcurrent devices supplying it]
WARNING
INVERTER OUTPUT CONNECTION
DO NOT RELOCATE THIS
OVER-CURRENT DEVICE
WARNING:PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION
CONDUIT, COMBINER BOX
[PER CODE: NEC690.31(G)(3)]
WARNING-Electric Shock Hazard
No User Serviceable Parts inside
Contact authorized service provide for
assistance
LABEL LOCATION
INVERTER, JUNCTION BOXES(ROOF),
AC DISCONNECT
[PER CODE: NEC 690.13]
LABEL LOCATION
DISCONNECT, POINT OF INTERCONNECTION
[PER CODE: NEC690.13(B)]
LABEL LOCATION
AC DISCONNECT , POINT OF INTERCONNECTION
[PER CODE: NEC 690.54]
LABEL LOCATION
MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC
CONDUIT, RACEWAYS, ENCLOSURES AND CABLE ASSEMBLES AT
LEAST EVERY 10 FT, AT TURNS AND ABOVE/BELOW
PENETRATIONS AND ALL COMBINER/JUNCTION BOXES.
(PER CODE: IFC605.11.1.4)
LABEL LOCATION
POINT OF INTERCONNECTION
[PER CODE: NEC705.12(D)(4)]
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION
LABEL LOCATION
AC DISCONNECT,POINT OF INTERCONNECTION
[PER CODE: NEC 690.13(B)]
DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR
MODULES ARE EXPOSED TO SUNLIGHT
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE
ENERGIZED IN THE OPEN POSITION
WARNING
LABEL LOCATION
AC DISCONNECT,POINT OF INTERCONNECTION
[PER CODE: NEC 690.13(B)]
LABEL LOCATION
WEATHER RESISTANT MATERIAL, DURABLE ADHESDIVE,
UL969 AS STANDARD TO WEATHER RATING (UL LISTING
OF MARKINGS NOT REQUIRED), MIN 38" LETTER HEIGHT
ARIAL OR SIMILAR FONT NON-BOLD,PLACED WITHIN
THE MAIN SERVICE DISCONNECT,PLACED ON THE
OUTSIDE OF THE COVER WHEN DISCONNECT IS
OPERATED WITH THE SERVICE PANEL CLOSED.
(PWER CODE: NEC690.15 ,690.13(B))
WARNING
TRI POWER SOURCE SECOND
SOURCE IS PHOTOVOLTAIC SYSTEM
SOLAR DISCONNECT
RATED AC OPERATING CURRENT
AC NOMINAL OPERATING VOLTAGE
29.04
240
AMPS AC
VAC
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH
CAUTION: SOLAR ELECTRIC
SYSTEM CONNECTED
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRICPV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
LABEL LOCATION
AC DISCONNECT, DC DISCONNECT, POINT OF
INTERCONNECTION
(PER CODE: NEC690.56(C)(1))
LABEL LOCATION
INVERTER,POINT OF
INTERCONNECTION
[PER CODE: NEC 690.56(C)(3)]
RAPID SHUTDOWN SWITCH
FOR SOLAR SYSTEM
LABEL LOCATION
TO BE LOCATED ON XCEL OWNED
PRODUCTION METER
UTILITY PV PRODUCTION METER
LABEL LOCATION
POINT OF INTERCONNECTION
CAUTION
SOLAR PV SYSTEM AND BATTERY
BACK-UP INSTALLED. WITHIN
POWER DISCONNET, SOLAR
PANELS AND BATEERY POWER
WIRING MAY REMAIN
ENERGIZED
PHOTOVOLTAIC ARRAY ON THE ROOF
ENPHASE IQ COMBINER 4
UTILITY PV PRODUCTION METER
TESLA BACKUP GATEWAY 2
UTILITY AC DISCONNECT
TESLA POWERWAL II
MAIN SERVICE METER WITH
DISCONNECT
CRITICAL LOAD PANEL
UTILITY BATTERY DISCONNECT
PV-6.0
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
MODULE SPECSHEET
PV-6.1
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
INVERTER SPECSHEET
PV-6.2
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
COMBINER SPECSHEET
PV-6.3
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
TESLA BACKUP GATEWAY 2
PV-6.4
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
BATTERY SPECSHEET
PV-6.5
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
RACKING SPECSHEET
PV-6.6
CUSTOMER INFORMATION
NAME&ADDRESS:
AHJ:MN-COUNTY DAKOTA
UTILITY: DAKOTA ELECTRIC ASSOCIATION
SYSTEM INFORMATION
DESIGNER/CHECKED BY:
KP/LS
PROJECT NUMBER:CCEN-006655
SCALE:AS NOTED PAPER SIZE:17"x11"
JOSHUA VANDERAA
7063 182ND STREET, LAKEVILLE, MN 55044.
ENGINEER OF RECORD
DATE:8/5/2022 REV:A
10361 JAMESTOWN ST NE BLAINE, MN 55449
763-450-9769
LIC:ELEC#EA006457
LIC:GEN#BC638279
DC SYSTEM SIZE: 9600W
AC SYSTEM SIZE: 6960W
MODULES:
(24)REC SOLAR REC400AA PURE
INVERTER:
(24)ENPHASE IQ8PLUS-72-2-US(240V,1PH)
BRANCH DETAILS:
2 BRANCH OF 12 MICRO INVERTERS(12 MODULES)
BATTERY:
(1)TESLA POWERWALL II 5KW, 13.5KWH
MOUNT SPECSHEET