PROFESSIONAL CERTIFICATION
ONE LINE
INTERCONNECTION
GREENWAY SOLAR
MIKE RENEAUMIKE@GREENWAYSOLAR.ORG
0 50 100
FEETSCALEIN
1
6
5
7
8
9
1 2 13 3
4
Q.PEAK MODULES
360 W Pmax
50 TOTAL
1a
ENPHASE MICROINVERTERS
IQ8+
50 TOTAL
MAIN SERVICE PANEL
(EXISTING)
UTILITY SERVICE
INSIDE RESIDENCEM
LABEL 3
LABEL 3
POC & PCC
MAIN SERVICE METERUTILITY OWNED
1-PHASE, 3-WIRE, 120/240 V
SCHEDULE 1 - EQUIPMENT
Q.PEAK DUO BLK-G10+
Enphase I8+ Microinverters
Enphase IQ3 Combiner Panel
Utility AC Disconnect
PV Production Meter
Tesla Powerwall 2
Generation Panel
Utility AC Fused Disconnect
Tesla Gateway Backup Relay
Main Service Meter
360 watt Voc Monocrystalline, see notes
240 VAC, 1-Phase, 300 VA peak output
240 VAC, 1-Phase, 3-Wire, 125A Bus
240 VAC, Single Phase, 3-Wire, NEMA 3R
240 VAC, Utility Owned, Single Phase, 3-Wire, Lever Bypass
240 VAC, Single Phase, 3-Wire, 13.5 kWh
240 VAC, Single Phase, 3-Wire
240 VAC, Single Phase, 3-Wire
240 VAC Single Phase, 3-Wire, Automatic Relay Backup
Utility Owned Meter, 1-Phase, 3-Wire, 120/240 V
50
50
1
1
2
2
1
1
1
1
1a
2
3
4
5
5a
6
7
8
9
# ITEM QTY DESCRIPTION
TESLA GATEWAY 2
240 VAC, 1-PH, 3-WIRENEMA 3R
DRAWN BY CHECKED BY
DATE PROJECT NUMBER
MIKE RENEAU XCEL ENERGY
DRAWN BY CHECKED BY
DATE PROJECT NUMBER
MIKE RENEAU
M
PV PRODUCTION METERUTILITY OWNED1-PHASE, 3-WIRE, 120/240 VWITH LEVER BYPASS
INVERTER COMBINER PANEL240VAC, 1-PH, 3-WIRE, 100ANEMA 3R
UTILTY AC DISCONNECT
240 VAC, 1-PH, 3-WIREVISIBLE-OPEN TYPE, LOCKABLE
AND READILY ACCESIBLE NEMA 3RWITH SERVICE EQUIPMENT BARRIERS
FUSED DISCONNECT
240 VAC, 1-PH, 3-WIREVISIBLE-OPEN TYPE, LOCKABLE
AND READILY ACCESIBLE NEMA 3RWITH SERVICE EQUIPMENT BARRIERS
125A
80A
RPA
20A
20A
20A
20A
200A
EXISTING LOADS200A
NOTES:
1-ALL TESTING SHALL BE PERFORMED BY
QUALIFIED PERSONNEL, WITH PROPER
PROTECTIVE EQUIPMENT
2- THE PRODUCTION METER AND UTILITY AC
DISCONNECT LOCATED TOGETHER WITHIN
10’ OF THE MAIN SERVICE METER
3- 24/7 UNESCORTED KEYLESS ACCESS
PROVIDED FOR THE METERS AND UTILITY AC
DISCONNECT
4- UTILITY AC DISCONNECT IS VISIBLE-OPEN
TYPE, LOCKABLE, AND READILY ACCESSIBLE
5-DESIGN MEETS ALL APPLICABLE NEC
CODES
6- ALL LABELS SHALL COMPLY WITH NEC
MNDIP REFERENCE:3.1 Customer Name:3.2 OID:3.3 RPA3.4 NA3.5 Electrical connectoins of all major components identified3.6 Main service meter and main service panel3.7 Main service protection between DER and utlity3.8 Main service meter voltage and phase(s)3.9 Aggregate kW AC nameplate rating of each DER3.10 AC volage of DER system3.11 Expected individual kW AC nameplate rating of each inverter in system3.12 Number of phases of inverters3.13 Number of phases of DER system3.14 NA3.15 ESS: Configuration Mode being applied for shall be clearly indicated3.16 NA3.17 Indicate any control system3.18 PV Production meter, if applicable, with ownership noted3.19 PV production meter noted to have PV generation wired to line side terminals. Note LINE & LOAD.3.19.1 Customer owned meters not located on the DER side of the Xcel Energy production meter3.20 NA3.21 Visible-open type, lockable, and readily accesible 24/7 AC disconnect labeled “Utility AC Disconnect”3.21.1 Other AC Disconnects shall not be labeled or identified as a “Utility AC Disconnect”3.21.2 Installations requiring Production Meter; the utlity disconnect shall be located between DER and production meter3.21.3 Not requiring a production meter; the Utility AC Disconnect shall be located between the DER and main service3.21.4 Mulitple DER units on single service label Utility AC disconnects 1 of 2, etc3.22 NA
CASE NUMBER (OID)
LINE LOAD
OPERATING MODE 2CParallel Non-Exporting Storage
with Renewable Generation,
Net Metering
DCAC DCAC DCAC
1 2 12
DCAC DCAC DCAC
1 2 13
DC
AC
DC
AC
DC
AC
1 2 12
DC
AC
DC
AC
DC
AC
+
_
TESLA POWERWALL 2 (2)
+
_
5 kW, 13.5 kWh
NEMA 3R
AC
DC
AC
DC
GENERATION PANEL
125A MAIN BREAKERNEMA 3R
30A
80A
30A
125A 125A21 Amps Continuous21 Amps Continuous5a
MCMILLAN TESLA MODULES
04/29/22
04989566
21199 IXONIA LANELAKEVILLE, MN 55044
CARLTON MCMILLAN
COMMBOARDSYSTEM SIZE:
18 kW DC/ 15 kW AC
INVERTER NOTES:
(50) ENPHASE IQ8+ MICRO-
INVERTERS (240V)
MAX CONT OUTPUT: 300W
TOTAL OUTPUT: 15000W
UL1741 CERTIFIED
MAX CONT CURRENT: 15.95A (per
circuit string)
OCPD PROTECTION: 20 A
PV MODULE NOTES:
Q.PEAK DUO BLK-G10+
max: 360 W
Voc: 45.3
Vmpp: 37.13
Isc: 11.14 A
Impp: 10.77 A
TOTAL: 16000 W DC
-
-
-
SHEET NUMBER
CUSTOMER NAME
SHEET
SUBMITTAL
DATENO.REVISION
SCALE
PROFESSIONAL CERTIFICATION
ONE LINE LABELING
INTERCONNECTION
GREENWAY SOLAR
MIKE RENEAUMIKE@GREENWAYSOLAR.ORG
0 50 100
FEETSCALEIN
LB-130089-10X
Per Code: NEC 690.31.G.3
Label Location: (C)(CB)(JB)
LB-050081-10X
Per Code: NEC 690.13.B
Label Location: (DC) (INV)
690_53_2017
Per Code: NEC 690.53
Label Location: (DC) (INV)
LB-070004-10X
Per Code: 690.41.B
Label Location: (DC) (INV)
LB-010001-10X
Per Code: CEC 690.13.B
Label Location: (DC) (CB)
LB-050082-10X
Per Code: NEC 690.13.B
Label Location: (AC) (POI)
LB-040007-10X
Per Code: NEC 690.54
Label Location: (AC) (POI)
LB-070005-10X
Per Code: NEC 690.13.B
Label Location: (AC)(POI)
LB_040108_10X
Per Code: NEC 690.56.C.3
Label Location: (INV)
LB-070039-10X
Per Code: NEC 705.12.B.2.3.b
Label Location: (POI)
LB-040008-10X
Per Code: NEC 690.64.B.4
Label Location: (D) (POI)
LB-040009-10X
Per Code: NEC 705.12.B.3
Label Location: (POI)
LB-060046-10X
Per Code: CEC 690.13.B
Label Location: (POI)
LB-070016-10X Label Location: (DC) (INV)
LB-250001-10X
Per Code: 690.56(C)(1)(b)
Label Location: ABB/Delta Solivia Inverter
LB-250002-34X
Per Code: 690.56(C)(1)(a)
Label Location: SolarEdge and,Delta M-Series and,Telsa Inverter
(POI): Point of Interconnection(M): Utility Meter(LC): Load Center(INV): Inverter With Integrated DC Disconnect(IC): Interior Run Conduit(DC): DC Disconnect(D): Distribution Panel(CB): Combiner Box(C): Conduit(AC): AC Disconnect
PROJECT
DRAWN BY CHECKED BY
DATE PROJECT NUMBER
MIKE RENEAU
DRAWN BY CHECKED BY
DATE PROJECT NUMBER
MIKE RENEAU
Per Code: 690.56(C)(1)(a)
Label Location: At Disconnects
N
21199 IXONIA LANELAKEVILLE, MN 55044
CASE NUMBER (OID)
IXONIA LANE
LOCATION OF DISCONNECTS NOTES:
1-ALL TESTING SHALL BE PERFORMED BY
QUALIFIED PERSONNEL, WITH PROPER
PROTECTIVE EQUIPMENT
2- THE PRODUCTION METER AND UTILITY AC
DISCONNECT LOCATED TOGETHER WITHIN
10’ OF THE MAIN SERVICE METER
3- 24/7 UNESCORTED KEYLESS ACCESS
PROVIDED FOR THE METERS AND UTILITY AC
DISCONNECT
4- UTILITY AC DISCONNECT IS VISIBLE-OPEN
TYPE, LOCKABLE, AND READILY ACCESSIBLE
5-DESIGN MEETS ALL APPLICABLE NEC
CODES
6- ALL LABELS SHALL COMPLY WITH NEC
MCMILLAN TESLA MODULES
04/29/22
04989566
21199 IXONIA LANELAKEVILLE, MN 55044
CARLTON MCMILLAN
DRIVEWAY
FRONT OF HOUSE
SOLAR ARRAY
SOLAR ARRAYSOLAR ARRAY
SOLAR ARRAY