Loading...
HomeMy WebLinkAboutLA206750 - APPROVED - Christopher J Malo Solar Drawings wStamp 09 14 2022EXISTINGSNAPNRACKSITE MAP & PV LAYOUTELECTRICAL 1-LINE DIAGRAM ATTACHMENT LAYOUTSYSTEM LABELING DETAILENPHASE RAPID SHUTDOWNINVERTER DATA SHEETSHEET INDEXPROPERTY PLANMODULE DATA SHEETRACKING DATA SHEETATTACHMENT DATA SHEETPV 1.0PV 2.0PV 4.0PV 5.1D 6.0D 7.0D 8.0D 9.0D 10.0D 11.0SYSTEM RATINGEQUIPMENT SUMMARYELECTRICAL INFORMATIONMAIN SERVICE PANEL BUS SIZE:MAIN SERVICE BREAKER SIZE:MOUNTING SYSTEM:BUILDING INFORMATIONCONSTRUCTION TYPE: V-BOCCUPANCY: R3ROOF:Truss 2 x 4 @ 24" O.C.COMP SHINGLEVICINITY MAP (SCALE: NTS)SATELLITE VIEW (SCALE: NTS)GENERAL NOTES1.All electrical materials shall be new and listed by recognizedelectrical testing laboratory Custom made equipment shall have complete test data submittedby the manufacturer attesting to its safety2.Outdoor equipment shall be NEMA 3R rated or equivalent3.All metallic equipment shall be grounded4.Contractor shall obtain electrical permits prior to installation andshall coordinate all inspections, testing commissioning andacceptance with the client, utility co. and city inspectors as needed.5.The electrical contractor shall verify the exact locations of servicepoints and service sizes with the serving utility company andcomply with all utility companies requirements.6.Drawings are diagrammatic only, routing of raceways shall beoption of the contractor unless otherwise noted and shall becoordinated with other trades.7.If the roof material or the roof structure not adequate for PVinstallation, call the engineer of record print to installation. Thecontractor is responsible to verify that the roof is capable ofwithstanding the extra weight.8.If the distances for cable runs are different than shown, thecontractor shall notify the electrical engineer to validate the wiresize. Final drawings will be red-lined and updated as appropriate.9.Whenever a discrepancy in quality of equipment arises on thedrawing or specifications, the contractor shall be responsible forproviding and installing all materials and services required by thestrictest conditions noted on the drawings or in the specificationsto ensure complete compliance and longevity of the operablesystem required by the engineer of record.PHOTOVOLTAIC NOTES:1.Rooftop mounted photovoltaic panels and modules shall be tested,listed and identified by recognized testing laboratory2.Solar system shall not cover any plumbing or mechanical vents3.Modules and support structures shall be grounded unless racking has integrated ground.4.Removal of an interactive inverter or other equipment shall notdisconnect the bonding connection between the groundingelectrode conductor and the photovoltaic source and/or outputcircuit grounded conductors.5.All PV modules and associated equipment and wiring shall beprotected from physical damage.6.Live parts of PV source circuits and PV output circuits over 150v toground shall not be accessible to other than qualified persons while energized.7.Inverter is equipped with integrated DC disconnect, thus providingground fault protection8.All conductors shall be copper and 75 deg rated9.A single conductor shall be permitted to be used to perform themultiple functions of dc grounding, AC grounding and bondingbetween AC and DC systems.10.Non-current carrying metal parts of equipment shall be effectivelybonded together. Bond both ends of raceways.200A200A09/13/2022Property Address:Owner:Christopher J MaloProperty Type:Single Family ResidenceDrawn by:New@engineerinc.ioDate: HANWHA 400 WATT MODULESWITH IQ8+ MICROINVERTERS21066 Ivory Ln, Lakeville, MN 55044CONTRACTORAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comTHE INSTALLATION OF SOLAR ARRAYS ANDPHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITHTHE FOLLOWING CODES:·2020 National Electrical Code·2018 International Building Code·2018 International Residential Code·2020 Minnesota Residential Code·2020 Minnesota Building Code·2020 Minnesota Energy Code·2020 Minnesota Accessibility Code·2020 Minnesota State Fire Code·2018 International Fire Code·2018 International Energy Conservation Code·2018 Mechanical CodeAS ADOPTED BY THE STATE OF MINNESOTAALL OTHER ORDINANCE ADOPTED BY THELOCAL GOVERNING AGENCIESGOVERNING CODESINVERTER CERTIFICATIOND 13.0PV 3.1MONITORING DEVICED 12.0PV INSPECTION CHECKLIST ATTACHMENT DETAILPV 5.2SURGE PROTECTIONWITNESS TEST PROCEDURED 14.0D 15.0Xcel Energy Application #05246587PLACARDPV 3.2DC 26.400 KW STCAC 19.140 KW STC66Date Certified andSigned: 09/14/2022 EMT type ConduitSolar Module(N) Junction BoxJB.................................................................................MSP(E) Main Service Panel200AINDEXAC....................(N) 100A Utility AC(N) MicroinverterNOTE: Conduit in attic shallbe minimum 18 inches from roof sheating* Roof access is not located in areas that require placement of ground ladders over exterior wall openings (R324.6.1)SITE MAP & PVLAYOUTPV 1.0PV SYSTEMAS INDICATEDScale:Project:Drawn by:New@engineerinc.ioProject Name:Property Adress:09/13/2022Christopher J Malo21066 Ivory LnLakeville, MN 55044DATE:CONTRACTORPVS(N) 125A PV Sub Panel..........Wolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comEQUIPMENT ELEVATIONNote: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTNOTE: No clearance issue Distance between all equipments is maximum 10"(E) Main MeterMM........................Fire Setback Line.............SECONDARY INTERCONNECTIONFMT type Conduit.............NOTE:A 36-inchwide pathwayshall be provided to the emergencyescape and rescue opening.6666INVERTERINVERTER TYPE: Micro:___ Enphase IQ8PLUSModel # IQ8PLUS-72-2-US(240V)Xcel Energy Application #05246587Xcel Energy Application #05246587Total Roof Area:3750Total Module Area:145238.72% of CoveragePVSUtility ACDisconnect10"From roofMainServicePanel<10'InsideInsideOutsideOutsideMainMeterEnphase PB(N) PVC Box..........................SOLAR MODULES___HANWHA 400 WattModel #Q.PEAK DUO BLK ML-G10+PVC BOX36" fire pathwayRoof AccessMMMSPACPVSPBUTILITY AC DISCONNECT LOCKABLEAND READLY ACCESSIBLESolar PV Array 18- Hanwha 400 W Modules8- IQ8+ MicroinvertersPitch: 45 DegOrientation: 207 Deg3' fir e s e t b a c k aJB13' fire setback18'' fire setback18'' fire setback18'' f i r e s e t b a c k aaaaaaaaaaabbbbbbbbbbcccbcccccccccddddddddddeeeeeeeeeefffffffffffIvory LnSolar PV Array 220- Hanwha 400 W Modules20- IQ8+ MicroinvertersPitch: 45 DegOrientation: 117 DegSolar PV Array 316- Hanwha 400 W Modules16- IQ8+ MicroinvertersPitch: 45 DegOrientation: 27 DegSolar PV Array 415- Hanwha 400 W Modules15- IQ8+ MicroinvertersPitch: 45 DegOrientation: 297 DegSolar PV Array 53- Hanwha 400 W Modules3- IQ8+ MicroinvertersPitch: 45 DegOrientation: 116 DegSolar PV Array 64- Hanwha 400 W Modules4- IQ8+ MicroinvertersPitch: 45 DegOrientation: 207 DegJB2JB3JB4JB5JB6JB7SCALE:1/16" = 1'-0" 180° 90° 270°0°SWNEFor each roof plane with a photo-voltaicarray, a 36 inch wide pathway shall beprovided from lowest roof edge to ridge onthe same roof plane, on adjacent roof planes.One shall be on street/driveway side.Concept Approval ONLYSubject to Field InspectionInspectorDate2020MN BldgCode09/26/2022dpfannensteinNo less than 18 inch clearsetback is required on bothsides of a horizontal ridgeor hip MAIN METERENPHASE Q CABLE(2) #12 AWG PV WIRE(1) #6 AWG EGCFREE IN THE AIRPV 2.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044ELECTRICAL 1-LINE DIAGRAMCONTRACTOREnphasePV MONITORING DEVICE125A PV SUB PANEL120/240V, NEMA 3R(2) #14 AWGTHWN/ THWN-210A 2-POLENote: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENT In locations where there is no local Public Authority,the customer is exempt frominspection, and/or the service has been shut off ordisconnected for more than 365 days (1 year),the licensed electrician or wireman shall submit asigned and dated Xcel Energy ElectricalInspection Certificate to the Company’s Builders CallLine attesting that the electrical installationhas been completed and installed according to thecurrent National Electrical Code®, the XcelEnergy Standard for Electric Installation and Use,and any other applicable codes that apply beforeelectric service is energized.Design meet National Electric Code(NEC codes)100A FUSED AC DISCONNECT,WITH 100A FUSESUTILITY AC DISCONNECT VISIBLE-OPENLOCKABLE, READILY ACCESSIBLENEMA3R 120 / 240V 1P 3WINSTALL (6)20A PV2-POLE C/BWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com(3) #3AWG THWN/THWN-2(1) #6 AWG GND1 1/4" EMT, 2 FEETSECONDARY INTERCONNECTIONREFERENCE POINT OF APPLICABILITY (6) #10 AWG THWN/THWN-2 (1) #8 AWG GND 3/4'' EMT, 7 FEETAtticWall (6) #10 AWG THWN/THWN-2 (1) #8 AWG GND 3/4'' FMT, 20 FEETSurge ProtectionMNSPD-300-AC120/240V,1P, 3WXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE:1-PHASE MICRO-INVERTER UL1741HANWHA 400 WATT MODULES6666ENPHASE IQ8PLUS MICROINVERTERSSYSTEM RATING AND DER POWER OUTPUTINVERTER:ENPHASE IQ8PLUS-72-2-USINVERTER MAXIMUM CONTINUOUS OUTPUT:290VASYSTEM POWER OUTPUT:ENPHASE IQ8PLUS MICROINVERTERS1 PHASE 290VAMAXIMUM OUTPUT CURRENT 1.21AAC PORT BACKFEED CURRENT 0ADC SHORT CIRCUIT CURRENT 15ADC 26.400 KW STCAC 19.140 KW STCDC 26.400 KW STCAC 19.140 KW STCXcel Energy Application #0524658779.86A66x 290 =19.140NOTE: AC DISCONNECT VISIBLE AND LOCKABLE79.86ANo loads or energy storage systems shall beconnected on the DER side of the production meter6.05A1BRANCHCIRCUIT-A25 1BRANCHCIRCUIT-A24 4.84AGEC(E) GROUNDINGELECTRODE SYSTEMNOTE: Service Panel is center fed:(3) #3AWG THWN/THWN-21 1/4" EMT, 2 FEETNON CENTER _____MAIN C/B200AEXISTING______ MAINSERVICEPANEL120/240V,1P, 3W200A7.26A1BRANCHCIRCUIT-E264.84A1BRANCHCIRCUIT-E23 AtticWall (6) #10 AWG THWN/THWN-2 (1) #8 AWG GND 3/4'' FMT, 15 FEET (6) #10 AWG THWN/THWN-2 (1) #8 AWG GND 3/4'' EMT, 7 FEETJ BOX2NEMA3RJ BOX6NEMA3R1BRANCHCIRCUIT-F210 12.1APVC BOXCell Kit1BRANCHCIRCUIT-D2J BOX7NEMA3R1BRANCHCIRCUIT-A23J BOX1NEMA3R3.63A12.1A(NEW)GECAdd 2nd Ground rod andtie it to the existing ground rod.(1) #6 AWG GNDLine Side Tap3J BOX3NEMA3R1BRANCHCIRCUIT-B212 14.52A4.84A1BRANCHCIRCUIT-C24J BOX4NEMA3R1BRANCHCIRCUIT-C28 9.68AJ BOX5NEMA3R104 PV 3.1PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044PV ARRAYJ BOXPV SUB-PANELACDISCONNECTMAIN SERVICEPANELMETER122221516207124Note: LABELS SHALL COMPLY WITH NEC 690“Labels shall be weatherproof, durable and permanently mounted”Photovoltaic Power SourceLABEL 1CAUTION: SOLAR CIRCUITLABEL 2WARNINGELECTRIC SHOCK HAZARDTHE DC CONDUCTORS OF THISPHOTOVOLTAIC SYSTEM AREUNDERGROUND AND MAY BE ENERGIZEDLABEL 3WARNINGELECTRIC SHOCK HAZARDIF GROUND FAULT IS INDICATEDNORMALLY GROUNDED CONDUCTORSMAY BE UNDERGROUND AND ENERGIZEDLABEL 4WARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE AND LOADSIDES MAY BE ENERGIZED IN THE OPENPOSITIONLABEL 5WARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE AND LOADSIDES MAY BE ENERGIZED IN THE OPENPOSITIONDC VOLTAGE IS ALWAYS PRESENTWHEN SOLAR MODULESARE EXPOSED TO SUNLIGHTLABEL 6WARNINGLABEL 7TURN OF PHOTOVOLTAICAC DISCONNECT PRIOR TOWORKING INSIDE PANELDO NOT DISCONNECTUNDER LOADLABEL 8MAIN PV SYSTEMDISCONNECTLABEL 9MAIN PV SYSTEMAC DISCONNECTLABEL 10LABEL 11CAUTIONLABEL 12SOLAR ELECTRIC SYSTEMCONNECTEDWARNING-LABEL 13 DUAL POWER SOURCESECOND SOURCE IS PV SYSTEMCAUTIONLABEL 14PHOTOVOLTAIC SYSTEM CIRCUITIS BACKFEDLABEL 15PHOTOVOLTAIC AC DISCONNECTMAXIMUM AC OPERATING CURRENTMAXIMUM AC OPERATING CURRENTPHOTOVOLTAICLABEL 16UTILITY AC DISCONNECTPHOTOVOLTAICLABEL 17DC DISCONNECTNOMINAL OPERATING AC VOLTAGENOMINAL OPERATING AC FREQUANCYMAXIMUM AC POWERMAXIMUM AC CURRENTMAX OCERCURRENT DEVICE RATINGFOR AC MODULE PROTECTIONLABEL 18LABEL 19PV SYSTEM DC DISCONNECTOPERATING CURRENTOPERATING VOLTAGEMAXIMUM SYSTEM VOLTAGESHORT CIRCUIT CURRENTRATED MAX POWER-FONT CURRENTRATED MAX POWER-FONT VOLTAGEMAXIMUM SYSTEM VOLTAGESHORT CIRCUIT CURRENTMAX RATED OUTPUT CURRENT OFTHE CHARGE CONTROLLER IF INSTALLEDLABEL 20***ALL LABELS = RED THERMOPLASTIC/REFLECTIVE , Permanently mounted240VSOLAR DISCONNECT20CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587SYSTEM LABELING DETAILDrawn by:New@engineerinc.io09/13/2022DATE:79.86A PLACARDPV 3.2PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587CAUTIONPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:SERVICE 1 OF 2CAUTIONPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:SERVICE 2 OF 2NWESNWESDrawn by:New@engineerinc.io09/13/2022DATE:21066 Ivory LnLakeville, MN 5504421066 Ivory LnLakeville, MN 55044SERVICE POINT &UTILITY METERINGPV SUB PANELPV SYSTEM DISCONNECTFOR UTILITY OPERATIONPVC BOXSOLAR PV ARRAYSERVICE POINT &UTILITY METERINGPV SUB PANELPV SYSTEM DISCONNECTFOR UTILITY OPERATIONPVC BOXSOLAR PV ARRAY PROPERTY PLANLEGENDMSPMain Service Panel................PV 4.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORPV Sub PanelPVS..........................Wolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comMMMain Meter............................Xcel Energy Application #05246587Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTDrawn by:New@engineerinc.io09/13/2022DATE:Xcel Energy Application #05246587 Utility AC DisconnectAC ...............PVC BoxPB...................................Ivory LnDrivewayPROPERTY LINEMMMSPACPVSPB31'-3"77'-9"122'-10"129'-7"12'-2"27'-1"6'59'-7"62'-8"96'-7"SCALE:1/16" = 1'-0" 180° 90° 270°0°SWNEDate Certified andSigned: 09/14/2022 ATTACHMENTLAYOUTDESIGN CRITERIAModules:Max Distributed Load: 3 PSFPOINT LOAD CALCULATION PER ARRAYModule Weight (lbs)# Of Modules48.5Total Module Weight (lbs)Rack Weight (lbs)MicroInverters Weight (lbs)Total System Weight (lbs)# Of StandoffsMax Span Between Standoffs (in)Loading Per Standoff (lbs)Total Area (sq.ft.)Loading (PSF)3201640.2157.083998.281674823.9414522.75RAIL ATTACHMENTMODULES ON ROOFTruss 2 x 4 @ 24" O.C.6666PV 5.1PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com1 Layer of .Plywood & Building FeltSolar Module6"AttachmentMODULES ON ROOFTruss 2 x 4 @ 24" O.C.COMP SHINGLEPrior to the commencement of work, the contractor shall verify the existing roof and framingconditions. Notify New@engineerinc.io of any Discrepancies prior to starting construction.Prior to the commencement of work, the contractor shall inspect framing for any damagesuch as water damage, cracked framing, etc. and These Plans are stamped for structuralcode compliance of the roof framing supporting the proposed PV installation reference only.These plans are not stamped for water leakage. PV modules, racking, and attachmentcomponents must follow manufacturer guidelines and requirements. Attachments to beinstalled in a staggered orientation to properly distribute loads.1.86"3.05"0.25"Ø2.24"2.58"1"0.17"3.20"1.37"0.38"0.30"1.08"2.78"1.78"1.50"1.99"1.21"R 1.12"Ø0.33"R 0.82"12345SNAPNRACK, SPEEDSEAL FOOT, BASE, SEALING, SILVER/BLACKBOLT, FLANGE, SERRATED, 5/16IN-18 X 2IN, SSSNAPNRACK, RL UNIVERSAL, MOUNT SPRING, SSSNAPNRACK, ULTRA RAIL MOUNT THRU PRC, CLEAR/BLACKSNAPNRACK, ULTRA RAIL MOUNT TAPPED PRC, CLEAR/BLACK12345DESCRIPTIONITEMQTI11111MATERIALS:DESIGN LOAD (LBS):ULTIMATE LOAD (LBS):TORQUE SPECIFICATION:CERTIFICATION:WEIGHT (LBS):DIE CAST A380 ALUMINUM, 6000 SERIES ALUMINUM, STAINESS STEEL802 UP, 1333 DOWN, 357 SIDE2118 UP, 4006 DOWN, 1331 SIDE12 LB-FTUL 2703, FILE E359313; WIND-DRIVEN RAIN TEST FROM SUBJECT UL 25820.45OPTIONS:CLEAR/BLACKPARTS LISTSNAPNRACK, ULTRA RAIL SPEEDSEAL TM FOOTXcel Energy Application #05246587Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTDrawn by:New@engineerinc.io09/13/2022DATE:Xcel Energy Application #0524658724'-11"19'-6"Date Certified andSigned: 09/14/2022 PV 5.2PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044ATTACHMENT DETAILCONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: INVERTERDATA SHEETD 6.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: ENPHASE RAPIDSHUTDOWN,COMPATIBILITY WITH PVD 7.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: MODULEDATA SHEETD 8.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: RACKINGDATA SHEETD 9.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: ATTACHMENTDATA SHEETD 10.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: D 11.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORENPHASEAC COMBINER BOXDATASHEETWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: D 12.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORINVERTERCERTIFICATIONWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: D 13.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044CONTRACTORSURGE PROTECTIONWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: D 14.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044WITNESS TESTPROCEDURECONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: D 15.0PV SYSTEMAS INDICATEDScale:Project:Project Name:Property Adress:Christopher J Malo21066 Ivory LnLakeville, MN 55044PV INSPECTIONCHECKLISTCONTRACTORWolf RIver ElectircAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comWolf RIver ElectricLakeville, MN 5504421066 Ivory LnXcel Energy Application #05246587Drawn by:New@engineerinc.io09/13/2022DATE: