HomeMy WebLinkAboutLA207835 - APPROVED - Paider20725_Plans_10_20_2022_V0SS63561f62249b0COVER SHEETPHOTOVOLTAIC ROOF MOUNT SYSTEM20725 ISLANDVIEW CIRCLE LAKEVILLE, MN 55044 USAREVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-0 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSYSTEM SUMMARY:DESIGN CRITERIA:GOVERNING CODES:(N) 28 - HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES(N) 28 - ENPHASE ENERGY IQ7PLUS-72-2-US MICRO-INVERTERS(N) JUNCTION BOX(E) 150A MAIN SERVICE PANEL WITH (E) 150A MAIN BREAKER(N) 60A SERVICE FUSED AC DISCONNECT VISIBLE-OPEN TYPE, LOCKABLE,READILY ACCESSIBLE(N) ENPHASE IQ COMBINER BOX 328 MODULES-ROOF MOUNTED - 11.20 kWDC, 8.12 kWACROOF TYPE: - COMP SHINGLENUMBER OF LAYERS: - 01ROOF FRAME: - 2"X4" TRUSSES @24" O.C.STORY: - TWO STORYSNOW LOAD : - 50 PSFWIND SPEED :- 115 MPHWIND EXPOSURE:- BRISK CATEGORY:- IICOORDINATE:- 44.652110, -93.2608502VICINITY MAPSCALE: NTSPV-01AERIAL PHOTOSCALE: NTSPV-0SHEET INDEXPV-0COVER SHEETPV-1SITE PLAN WITH ROOF PLANPV-2ROOF PLAN WITH MODULESPV-3ATTACHMENT DETAILSPV-4 ELECTRICAL LINE DIAGRAM WITH CALCULATIONPV-5 PLACARDS & WARNING LABELSPV-6+EQUIPMENT SPEC SHEETS2020 NATIONAL ELECTRICAL CODE (NEC)2020 MINNESOTA STATE BUILDING CODE (MSBS)2018 INTERNATIONAL EXISTING BUILDING CODES AND AMENDMENTS2018 INTERNATIONAL RESIDENTIAL CODE (IRC)2018 INTERNATIONAL FUEL GAS CODE (IFGC)2018 INTERNATIONAL MECHANICAL CODE (IMC)2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)HASTINGS CITY CODEGENERAL NOTES·ALL ELECTRICAL WORK SHALL BE PERFORMED BY A QUALIFIEDLICENSED ELECTRICIAN AND/OR APPRENTICES WORKING UNDER THEDIRECT SUPERVISION OF THE LICENSED CONTRACTOR.·ALL WORK CARRIED OUT SHALL COMPLY WITH THE SPECIFICATIONS,APPLICABLE MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS ANDLOCAL JURISDICTIONAL CODES, ORDINANCES, AND APPLICABLEREGULATIONS.·PRIOR TO COMMENCEMENT OF ANY WORK, THE CONTRACTOR SHALLNOTIFY THE ENGINEER OF AN DISCREPANCIES NOTED AMONG SITECONDITIONS, MANUFACTURER RECOMMENDATIONS, OR AUTHORITYHAVING JURISDICTION. IF THE SPECIFIED EQUIPMENT CANNOT BEINSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALLSUBMIT TO THE ENGINEER OF RECORD A WRITTEN "RFI"(REQUEST FORINFORMATION) PROPOSING AN ALTERNATIVE OR SEEKINGCLARIFICATION.·THE CONTRACTOR SHALL MAINTAIN IN GOOD CONDITION ONECOMPLETE SET OF PLANS WITH ALL REVISIONS, ADDENDA, AND CHANGEORDERS ON THE PREMISES AT ALL TIMES.·UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHINGMATERIALS, EQUIPMENT, ACCESSORIES, AND LABOR NECESSARY TOCOMPLETE ALL INSTALLATIONS AS INDICATED ON THE DRAWINGS.·ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICTACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS, ANDORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICESAND COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS, ANDLAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THEPERFORMANCE OF WORK.·THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS INACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESSSPECIFICALLY STATED OTHERWISE.·CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF WORKAREA, ADJACENT AREAS AND BUILDING OCCUPANTS THAT ARE LIKELYTO BE AFFECTED BY THE WORK UNDER THIS CONTRACT. WORK SHALLCONFORM TO ALL OSHA REQUIREMENTS AND THE LOCAL JURISDICTION.·FALL ARREST PROTECTION PER OSHA REQUIREMENTS SHALL BEPROVIDED FOR ALL ROOF WORK.·WHEN INSTALLING IN FIRE RATED AREAS, SEAL ALL PENETRATIONS WITHUL LISTED MATERIALS APPROVED BY LOCAL JURISDICTION.CONTRACTOR SHALL KEEP AREA CLEAN, HAZARD FREE, AND DISPOSEOF ALL DEBRIS.·CONTRACTOR SHALL LEAVE PREMISES IN A CLEAN CONDITION. ALLDEBRIS AND OTHER REFUSE SHALL BE REMOVED FROM THE SITE ANDDISPOSED OF IN A LAWFUL MANNER.·THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS,PAVEMENTS, CURBS, LANDSCAPING AND STRUCTURES NOT PART OFTHE SCOPE OF WORK AS IDENTIFIED IN THESE PLANS.·THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURITY OF THE SITEFOR THE DURATION OF CONSTRUCTION UNTIL JOB COMPLETION.·DUE TO THE FACT THAT PV MODULES ARE ENERGIZED WHENEVER THEYARE EXPOSED TO LIGHT, CONTRACTOR SHALL DISABLE THE ARRAYDURING INSTALLATION AND SERVICE BY SHORT CIRCUITING, OPENCIRCUITING, OR COVERING ARRAY WITH AN OPAQUE COVERACCORDING TO MANUFACTURER'S INSTRUCTION.·CONSTRUCTION LOADING ON THE ROOF, SUCH AS MATERIAL STAGED ONTHE ROOF, SHALL BE LIMITED TO 20 PSF. CONCENTRATED LOADINGSHALL BE AVOIDED TO PREVENT LOCALIZED DAMAGE TO THE ROOF.ARRAY LOCATIONSLOCATIONProfessional EngineerI hereby certify that this plan, specification, or report wasprepared by me or under my direct supervision and that I ama duly Licensed Professional Engineer under the laws of thestate of Minnesota.Signature: Typed or Printed Name: Saddam AhmadDate: License Number: 5538124-OCT-2022
ACDUMCB
MSPJB ~86.87'~187.36'~86.87'~187.
3
6
'
46'-0"11'-10"103'-7"8'-0"ACDUMCBMSPSITE PLAN WITH ROOF PLANREVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-1 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSITE PLAN WITHROOF PLAN1SCALE: 1/32" = 1'-0"NOTE:A.ALL ELECTRICAL EQUIPMENT, INVERTERS,DISCONNECTS, MAIN SERVICE PANELS, ETC. SHALLNOT BE INSTALLED WITHIN 3’ OF THE GAS METERS’SUPPLY OR DEMAND PIPING. ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRETHE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWSOR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION INLOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEADOBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS.74.00"41.10"PHOTOVOLTAIC MODULESHANWHA Q CELLS Q.PEAK DUOBLK ML-G10+ (400W)LEGENDJUNCTION BOXUMJBENPHASE IQ COMBINER 3CBUTILITY METERACDSERVICE AC DISCONNECT FUSED ACD VISIBLEOPEN LOCKABLE LABELED DISCONNECTCONDUITOPEN VISIBLE, LOCKABLE, LABELEDAC DISCONNECT LOCATED WITHIN10' OF UTILITY METERGATEFENCEMSPMAIN SERVICE PANELROOF ACCESS POINT(N) (28) ENPHASE IQ8PLUS-72-2-USMICRO-INVRTERS(E) FENCEISLANDVIEW CIRCLEEXISTINGDRIVEWAYTWO- STORYHOUSEPROP
E
R
T
Y
L
I
N
E
PROPERTY LINEPROPERTY LINEPROPERTY LINEROOF #1ROOF #2(E) TREE (TYP.)(N) 3/4" OR GREATER EMT CONDUITRUN (7/8 INCHES ABOVE ROOF)Professional EngineerI hereby certify that this plan, specification, or report wasprepared by me or under my direct supervision and that I ama duly Licensed Professional Engineer under the laws of thestate of Minnesota.Signature: Typed or Printed Name: Saddam AhmadDate: License Number: 5538124-OCT-2022
ACD
UM
CB
MSPJB3'-4"2'-9"31'-2"3"3'-0"
13'-11"
1'-6"6"18'-8"3'-11"3'-6"10'-5"6"REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-2 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comROOF PLAN WITHMODULESROOF PLAN WITH MODULESSCALE: 3/32" = 1'-0"1MODULE TYPE, DIMENSIONS & WEIGHTNUMBER OF MODULES = 28 MODULESMODULE TYPE = HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULESMODULE WEIGHT = 48.50 LBS / 22.0 KG.MODULE DIMENSIONS = 74.00"X 41.10" = 21.12 SFUNIT WEIGHT OF ARRAY = 2.30 PSFROOF DESCRIPTIONROOF TYPECOMP SHINGLE ROOFROOF# OFMODULESROOFTILTAZIMUTHTRUSSESSIZETRUSSESSPACING#11934°196°2"x4"24" O.C.#20934°196°2"x4"24" O.C.BILL OF MATERIALSEQUIPMENTQTYDESCRIPTIONRAIL22UNIRAC NXT HORIZON RAIL,168"DARKSPLICE16NXT HORIZON RAIL SPLICEUNIVERSAL CLAMP76NXT HORIZAN COMBO CLAMP - DARKACCESSORIES112NXT HORIZON RL & CLMP CAP KITCOMPROOFATTACHMENT107UNIRAC FLASHLOC ATTACHMENTMLPE & GROUNDING37NXT HORIZON MLPE & LUG CLAMP74.00"41.10"PHOTOVOLTAIC MODULESHANWHA Q CELLS Q.PEAKDUO BLK ML-G10+ (400W)INVERTER TYPE, DIMENSIONS & WEIGHTNUMBER OF INVERTER = 28 MICRO-INVERTERSINVERTER TYPE = ENPHASE ENERGY IQ7PLUS-72-2-USMICRO-INVERTERSINVERTER WEIGHT = 2.38 LBS / 1.08 KG.INVERTER DIMENSIONS (HXWXD) = 8.3" X 6.9" X 1.2"ENPHASE ENERGY IQ7PLUS-72-2-US MICRO-INVERTERSLOCATED UNDER EACH MODULEOPEN VISIBLE, LOCKABLE, LABELEDAC DISCONNECT LOCATED WITHIN10' OF UTILITY METER· PLUMBING VENTS, SKYLIGHTS AND MECHANICAL VENTS SHALL NOT BE COVERED, MOVED, RE-ROUTED OR RE-LOCATED.NOTE: ACTUAL ROOF CONDITIONS ANDTRUSSES (OR SEAM) LOCATIONS MAY VARY.INSTALL PER MANUFACTURER(S) INSTALLATIONGUIDELINES AND ENGINEERED SPANS FORATTACHMENTSLEGENDJUNCTION BOXUMJBENPHASE IQ COMBINER 3CBUTILITY METERACDUTILITY AC DISCONNECT VISIBLE OPEN LOCKABLELABELED DISCONNECTCONDUITROOF ATTACHMENT@ 48" O.C.RAILTRUSSESVENT, ATTIC FAN(ROOFOBSTRUCTION)R324.6.2 - PROVING ARRAYS TAKELESS THAN 33% OF TOTAL ROOFAREA.WHEN THE ARRAYS TAKE LESSTHAN 33% WE CAN JUSTIFY AN 18"SETBACK ON BOTH SIDES OF THERIDGE. WHEN IT TAKES MORE THAN33% OF THE ROOF AREA WE MUSTUSE A 3' SETBACKS AT THE RIDGE.TOTAL ROOF AREA:2471.22 sqftAREA OF ARRAYS:74.00"X 41.10" ( PANEL DIMENSIONS)74.00"X 41.10" = 21.12 sqft (PER PANEL)21.12 sqftpanel X 28 panels = 591.38 sqft(TOTAL PANEL AREA)PERCENTAGE OF TOTAL ROOF AREA:(591.38 sqft / 2471.22 sqft)(100)= 23.93% THE PANELS USE 23.93% OFTHE TOTAL ROOF AREA3'-0"36" FIRE PATHWAY18"18" FIRE PATHWAYCHIMNEY(N) 3/4" OR GREATERFMC CONDUIT RUN(THROUGH ATTIC)MSPMAIN SERVICE PANEL(N) (107) UNIRAC FLASHLOC ATTACHMENTSSPACED AT 48" O.C.(DECK MOUNT)ROOF #1ROOF #218" FIRE PATHWAY18" FIRE PATHWAY18" FIRE PATHWAY18" FIRE PATHWAY36" FIR
E
P
A
T
H
W
A
Y
36" FIR
E
P
A
T
H
W
A
Y
36" FIRE PATHWAY 36" FIRE PATHWAY
ISLANDVIEW CIRCLEFRONT YARDREAR YARDProfessional EngineerI hereby certify that this plan, specification, or report wasprepared by me or under my direct supervision and that I ama duly Licensed Professional Engineer under the laws of thestate of Minnesota.Signature: Typed or Printed Name: Saddam AhmadDate: License Number: 5538124-OCT-2022Concept Approval ONLYSubject to Field InspectionInspectorDate2020MN BldgCode10/27/2022dpfannenstein
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-3 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comATTACHMENTDETAILATTACHMENT DETAIL1ATTACHMENT DETAIL (ENLARGED VIEW)2NOTE: ACTUAL ROOF CONDITIONS AND TRUSSES (OR SEAM)LOCATIONS MAY VARY. INSTALL PER MANUFACTURER(S)INSTALLATION GUIDELINES AND ENGINEERED SPANS FORATTACHMENTS(E) 2"X4" TRUSSES @24" O
.CENLARGE VIEW(N) PV MODULES~5"(E) COMP SHINGLE ROOF1.26"(E) COMP SHINGLE ROOF(N) PV MODULESBUILDING STRUCTUREROOF / DECK MEMBRANE2.5" MIN.EMBEDMENT(E) COMP SHINGLE ROOF5/16" x 4" STAINLESS STEEL LAG BOLTW/ SS EPDM BONDED WASHERNXT HORIZON COMBO CLAMP NXT HORIZON RAILFLASHLOC BASE MILL OR DARK4X - 5/16" -18 x 5/8"HEX FLANGE SCREW - TYPE FProfessional EngineerI hereby certify that this plan, specification, or report wasprepared by me or under my direct supervision and that I ama duly Licensed Professional Engineer under the laws of thestate of Minnesota.Signature: Typed or Printed Name: Saddam AhmadDate: License Number: 5538124-OCT-2022
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-4 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comELECTRICAL LINEDIAGRAM WITHCALCULATIONELECTRICAL LINE DIAGRAMSCALE: NTS1SOLAR MODULE SPECIFICATIONSMANUFACTURER / MODEL #VMPIMPVOCISCTEMPERATURECOEFFICIENTOF VocHANWHA Q CELLS Q.PEAK DUOBLK ML-G10+ (400W)37.1310.7745.3011.14-0.27%/°CMODULE DIMENSION74.00" L x 41.10" W x 1.26" DAMBIENT TEMPERTURE SPECIFICATIONSRECORDLOW TEMPAMBIENT TEMP(HIGH TEMP 2%)CONDUITHEIGHTCONDUCTORTEMPERATURERATE (ONROOF)CONDUCTORTEMPERATURERATE (OFFROOF)-28°31°7/8"90°75°INVERTER SPECIFICATIONSMANUFACTURER / MODEL #QUANTITYNOMINAL OUTPUTVOLTAGENOMINAL OUTPUTCURRENTNOMINAL ACPOWERENPHASE ENERGYIQ7PLUS-72-2-US28290 VAC1.21A8.12kW(28) ENPHASE ENERGY IQ7PLUS-72-2-USMICROINVERTERS (240V)(LOCATED UNDER EACH PANEL)NGM*IQ-ENVOYBRANCH TERMINATORE-TERM-10 (TYP.)15A(N) JUNCTIONBOX #1(N) ENPHASE IQ COMBINER BOX 3(X-IQ-AM1-240-3) WITH ENVOYCOMMUNICATION(N) UTILITY ACDISCONNECT 60AFUSED,VISIBLELOCKABLE LABELED,50A FUSES, 240 VACGNNL2L1L2L150A FUSESAPHOTOVOLTAICAC DISCONNECTPHOTOVOLTAIC SYSTEMCONNECTEDCONDUCTOR SCHEDULE AND CALCULATIONSTAGLOCATION DESCRIPTION# OFBRANCHCURRENT (A)#C. CARRYINGCONDUCTORWIRESIZEWIRETYPECOND.RATING (A)AMBIENTTEMPCOND. FILLFACTORDERATEDGROUNDSIZECONDUITTYPECONDUITSIZEWIRE RUNFROMBRANCHMAX. MOD. INBRANCHLENGTHINVERTER OUTPUTCURRENT690.8(A)(1)(A)ABRANCH TO J-BOX3101.2115.13312 AWGQ-CABLE300.961.028.806 AWGFREE AIRN/ABJ-BOX TO COMBINER BOX3101.2115.13610 AWGTHWN-2400.960.8030.7210 AWGFMC3/4"CCOMBINER BOX TO ACDISCONNECT3101.2115.13310 AWGTHWN-2400.960.8030.7210 AWGEMT3/4"DAC DISCONNECT TOINTERCONNECTION1281.2142.3536 AWGTHWN650.941.061.108 AWGEMT3/4"SYSTEM SIZE:- 28 x 400W = 11.20 kWDCSYSTEM SIZE:- 28 x 290W = 8.12 kWAC(28) HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES(28) ENPHASE ENERGY IQ7PLUS-72-2-US MICRO-INVERTERS(01) BRANCH OF 10 MODULES &(02) BRANCHES OF 09 MODULES CONNECTED IN PARALLRL PER BRANCH09 MICRO-INVERTERS IN BRANCH CIRCUIT #2L1L1L2L220ALBI-DIRECTIONALUTILITY METER1-PHASE, 3-W,120V/240V, 60Hz(E) MAIN SERVICE PANEL,150A RATED, 120/240VAC DISCONNECT SHALL BE LOCATEDWITHIN 10 FEET OF UTILITY METEREXISTING GROUNDINGSYSTEM(N) LINE SIDE TAPC20A10 MICRO-INVERTERS IN BRANCH CIRCUIT #1L1L1L2L2150A(E) MAIN BREAKER150A/2P, 240V09 MICRO-INVERTERS IN BRANCH CIRCUIT #320AL1L1L2L2DB
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-5 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comWARNING LABELS &PLACARDCAUTION !POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THEFOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN20725 ISLANDVIEW CIRCLE(E) UTILITY METER(N) COMBINER BOX 3(E) MAIN SERVICE PANELWITH (E) MAIN BREAKER(INSIDE HOUSE)WARNINGPOWER SOURCE OUTPUTCONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICE! WARNING DUAL POWER SOURCESECOND SOURCE IS PHOTOVOLTAIC SYSTEMLABEL LOCATION:EMT/CONDUIT RACEWAYS(PER CODE: NEC690.31(D)(2)PHOTOVOLTAIC POWER SOURCELABEL LOCATION:POINT OF INTERCONNECTIONPRODUCTION METERNEC 705.12(B)(3)(3) & NEC 690.59)NOTES AND SPECIFICATIONS:·SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE2020 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONSARE REQUIRED BY SECTION 690, OR IF REQUESTED BY THELOCAL AHJ.·SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDSUSING EFFECTIVE WORDS, COLORS AND SYMBOLS.·LABELS SHALL BE PERMANENTLY AFFIXED TO THEEQUIPMENT OR WIRING METHOD AND SHALL NOT BE HANDWRITTEN.·LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTANDTHE ENVIRONMENT INVOLVED.·SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011,PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISESPECIFIED.·DO NOT COVER EXISTING MANUFACTURER LABELS.ELECTRICAL SHOCK HAZARDWARNINGTERMINALS ON LINE AND LOADSIDES MAY BE ENERGIZED INTHE OPEN POSITIONLABEL LOCATION:INVERTER(S), AC DISCONNECT(S), ACCOMBINER PANEL (IF APPLICABLE).PER CODE(S): NEC 2020: NEC 706.15(C)(4) & NEC 690.13(B)MAXIMUM AC OPERATING CURRENT:NOMINAL OPERATING AC VOLTAGE: 33.88 AMPS 240 VACLABEL LOCATION:AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OFINTERCONNECTION.PER CODE(S): NEC 2020: 690.54SOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNSOLAR ELECTRICPV PANELSTURN RAPID SHUTDOWNSWITCH TO THE "OFF"POSITION TO SHUT DOWNPV SYSTEM AND REDUCESHOCK HAZARD IN THEARRAY.LABEL LOCATION:ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE DISCONNECTINGMEANS TO WHICH THE PV SYSTEMS ARE CONNECTED.PER CODE(S): NEC 2020: IFC 690.56(C)!4"3"PHOTOVOLTAIC AC DISCONNECTMAIN PHOTOVOLTAICSYSTEM DISCONNECTLABEL LOCATION:MAIN SERVICE DISCONNECT / UTILITY METER(PER CODE: NEC 690.13(B))THIS EQUIPMENT FED BYMULTIPLE SOURCES TOTALRATING OF ALL OVERCURRENTDEVICES EXCLUDING MAIN POWERSUPPLY SHALL NOT EXCEEDAMPACITY OF BUSBARWARNINGLABEL LOCATION: POINTS OF CONNECTION/BREAKERCODE: NEC 705.12(B)(3)(3)LABEL LOCATION:SERVICE PANEL IF SUM OFBREAKERS EXCEEDS PANEL RATINGNEC 705.12 (B)(3)(2)LABEL LOCATION:UTILITY SERVICE ENTRANCE/METER, INVERTER/DCDISCONNECT IF REQUIRED BY LOCAL AHJ, OROTHER LOCATIONS AS REQUIRED BY LOCAL AHJ.PER CODE(S): NEC 2020: 690.56(C)(2)RAPID SHUTDOWN FOR SOLARPV SYSTEM!!WARNINGTHE DISCONNECTION OF THEGROUNDED CONDUCTOR(S)MAY RESULT IN OVERVOLTAGEON THE EQUIPMENT!LABEL LOCATION:INVERTERPER CODE: NEC 690.31(E)!LABEL LOCATION:AC DISCONNECT/BREAKER/POINT OF CONNECTION(PER CODE: NEC 690.13(B)PHOTOVOLTAICAC DISCONNECTPHOTOVOLTAIC SYSTEMCONNECTEDLABEL LOCATION:METER, MAIN SERVICE PANEL (PER NECCODE: NEC690.13 (B)WARNING - SOLAR PVSYSTEM CONNECTEDAHEAD OF MAINBREAKER(N) PV MODULES(N) FUSED AC DISCONNECT
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-6 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSPEC SHEETS
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-7 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSPEC SHEETS
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-8 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSPEC SHEETS
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-9 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSPEC SHEETS
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-10 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSPEC SHEETS
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-11 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSPEC SHEETS
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-12 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSPEC SHEETS
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-13 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSPEC SHEETS
REVSHEET NAMESHEET NUMBERDATEDESCRIPTIONVERSIONPV-14 PROJECT NAMEUR20/10/2022INITIAL RELEASEPAIDER20725
20725 ISLANDVIEW CIRCLE,
LAKEVILLE, MN 55044 USA
UTILITY: XCEL ENERGY
AHJ: CITY OF LAKEVILLESHEET SIZEANSI B11" X 17"APN: 224747804120 THREE RIVERSCONTRACTING LLC2676 47TH ST E, INVER GROVEHEIGHTS, MN 55076TEL: (563) 202-0018CSLB#: BC760638Email - dan@3riversmn.comSPEC SHEETS