HomeMy WebLinkAboutLA208506 - APPROVED - Stamped Plans1.1.1PROJECT NOTES:1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRICCODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATIONINSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITYHAVING JURISDICTION’S (AHJ) APPLICABLE CODES.1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PVSYSTEM INSPECTED PRIOR TO PARALLEL OPERATION1.1.4 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE IS INTEGRATEDWITH THE MICROINVERTER IN ACCORDANCE WITH NEC 690.41(B)1.1.5 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, ANDSOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE INPHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4: PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY1.1.6 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMPCOEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATEDACCORDING TO NEC 690.7.1.1.7 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, ANDSOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWERSYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D).SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING ORLABELING [NEC 110.3].1.1.8 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IFEXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGEWILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.1.2.1 SCOPE OF WORK:1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OFTHE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BERESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN,SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THEPHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.1.3.1 WORK INCLUDES:1.3.2 PV ROOF ATTACHMENTS - IRONRIDGE FLASHFOOT21.3.3 PV RACKING SYSTEM INSTALLATION - IRONRIDGE XR-1001.3.4 PV MODULE AND INVERTER INSTALLATION - LG ELECTRONICS LG370N1K-E6 /ENPHASE IQ8PLUS-72-2-US1.3.5 PV EQUIPMENT GROUNDING1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX1.3.7 PV LOAD CENTERS (IF INCLUDED)1.3.8 PV METERING/MONITORING (IF INCLUDED)1.3.9 PV DISCONNECTS1.3.10 PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.3.11 PV FINAL COMMISSIONING1.3.12 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV1.3.13 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODEGENERAL NOTESN2017MSCOPE OF WORK:SYSTEM SIZE: STC: 29 X 370W = 10.730KWPTC: 29 X 344.1W = 9.979KW(29) LG ELECTRONICS LG370N1K-E6(29) ENPHASE IQ8PLUS-72-2-US (240VAC)ATTACHMENT TYPE: IRONRIDGE FLASHFOOT2MSP UPGRADE: NOOWNERNAME: DEBBIE MONSONPROJECT MANAGERNAME: KEVIN VICKERSPHONE: 763-412-5714CONTRACTORNAME: GOLDEN ELECTRIC, LLCPHONE: 763-412-5714AUTHORITIES HAVING JURISDICTIONBUILDING: CITY OF LAKEVILLEZONING: CITY OF LAKEVILLEUTILITY: DAKOTA ELECTRICDESIGN SPECIFICATIONSOCCUPANCY: IICONSTRUCTION: SINGLE-FAMILYZONING: RESIDENTIAL GRID-TIEDGROUND SNOW LOAD: 50 PSFWIND EXPOSURE: CWIND SPEED: 115 MPHAPPLICABLE CODES & STANDARDSBUILDING: MSBC 2020 MSRC 2020ELECTRICAL: NEC 2017FIRE: MSFC 2020PROJECT INFORMATIONNEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)MONSON RESIDENCE5744 162ND ST WLAKEVILLE, MN 55044ASSESSOR'S #: 222058001020BFAD E23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)AC D EG HB CF G H1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674T-001.00COVER PAGE(SHEET 1)01AERIAL PHOTONOT TO SCALENEWS02PLAT MAPNOT TO SCALESHEET LISTSHEET NUMBER SHEET TITLET-001COVER PAGEG-001 NOTESA-101SITE PLANA-102ELECTRICAL PLANA-103SOLAR ATTACHMENT PLANE-601LINE DIAGRAME-602E-603DESIGN TABLESS-501 ASSEMBLY DETAILSR-001 RESOURCE DOCUMENTR-002 RESOURCE DOCUMENTR-003 RESOURCE DOCUMENTR-004 RESOURCE DOCUMENTR-005 RESOURCE DOCUMENTPLACARDSESTATE LN162ND ST W10/17/2022 2.1.1SITE NOTES:2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHAREGULATIONS.2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM ISA UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING,MECHANICAL, OR BUILDING ROOF VENTS.2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING ANDPROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTIONNEC 110.26.2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED INACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'SINSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THEBUILDING OR STRUCTURE.2.2.1EQUIPMENT LOCATIONS:2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BYNEC 110.26.2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOREXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C)AND NEC TABLES 310.15 (B)(2)(A) AND 310.15 (B)(3)(C).2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULESACCORDING TO NEC 690.34.2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTERIS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT.2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNELACCORDING TO NEC APPLICABLE CODES.2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOROUTDOOR USAGE WHEN APPROPRIATE.2.3.1STRUCTURAL NOTES:2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TOCODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE ADESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND AMINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY,ACCORDING TO RAI MANUFACTURER’S INSTRUCTIONS.2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS.IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCALREQUIREMENTS.2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED ANDSEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY A LICENSEDCONTRACTOR.2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THESPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BESTAGGERED AMONGST THE ROOF FRAMING MEMBERS.2.4.1WIRING & CONDUIT NOTES:2.4.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODEREQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.2.4.3 CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.2.4.4 VOLTAGE DROP LIMITED TO 1.5%.2.4.5 DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRINGSYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLEWIRING CLIPS.2.4.6 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GRAYIN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGETO BE MARKED ORANGE [NEC 110.15].4.5.1GROUNDING NOTES:2.5.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FORSUCH USE.2.5.3 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 ANDMINIMUM NEC TABLE 250.122.2.5.4 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURESCONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).2.5.5 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC690.45 AND MICROINVERTER MANUFACTURERS' INSTRUCTIONS.2.5.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS ASSHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IFWEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED ATTHE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS'INSTALLATION REQUIREMENTS.2.5.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCHTHAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDINGCONDUCTOR TO ANOTHER MODULE.2.5.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLOREDGREEN OR MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]2.5.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC250.50 THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, ORINADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TONEC 250, NEC 690.47 AND AHJ.2.5.10 GROUND-FAULT DETECTION SHALL COMPLY WITH NEC 690.41(B)(1) AND (2) TOREDUCE FIRE HAZARDS2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCHIS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TOTHE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS).2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BELOCKABLE, AND BE A VISIBLE-BREAK SWITCH2.6.4 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE ARAPID SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCYRESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D).2.6.5 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9,AND 240.2.6.6 MICROINVERTER BRANCHES CONNECTED TO A SINGLE BREAKER ORGROUPED FUSES IN ACCORDANCE WITH NEC 110.3(B).2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTIONACCORDING TO NEC 690.11 AND UL1699B.2.7.1INTERCONNECTION NOTES:2.7.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC705.12 (B)]2.7.3 THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS OUTPUT MAYNOT EXCEED 120% OF BUSBAR RATING [NEC 705.12(D)(2)(3)].2.7.4 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUITCURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THEBUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THEBUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE LOCATED OPPOSITEEND OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(2)(3)].2.7.5 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTALRATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OFBUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BEEXCLUDED ACCORDING TO NEC 705.12 (B)(2)(3)(C).2.7.6 FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12(B)(2)(1)2.7.7 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.12 (A) WITHSERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230.422.7.8 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPTFROM ADDITIONAL FASTENING [NEC 705.12 (B)(5)].N2017M N2017M BFAD E23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)AC D EG HB CF G H1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674G-001.00NOTES(SHEET 2)10/17/2022 GENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGE3. 24/7 UNESCORTED KEYLESS ACCESS SHALL BEPROPERTY LINENEWS01/32"=1'SITE PLAN0116' 32'BFAD E23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)AC D EG HB CF G H1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674A-101.00SITE PLAN(SHEET 3)UTILITY METERAC COMBINER BOXAC DISCONNECTPV METERENTRANCEAREA OF WORK162ND ST WE S T A T E L N79'-5"10'-1"35'-8"12'-8"10/17/2022 MODULE:LG ELECTRONICSLG370N1K-E6370 WATTS41.02''69.61"GENERAL NOTES1.FIELD VERIFY ALL MEASUREMENTS2.ITEMS BELOW MAY NOT BE ON THIS PAGE3.24/7 UNESCORTED KEYLESS ACCESS SHALL BEBFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674A-102.00ELECTRICAL PLAN(SHEET 4)01/8"=1'-0"ELECTRICAL PLAN014'8'(E) (1) UTILITY METER(E) (1) MAIN ELECTRICAL PANELEXTERIOR PV EQUIPMENT(N) (1) AC COMBINER BOX(N) (1) AC DISCONNECT(N) (1) PV METER(N) (1) JUNCTION BOXNEWSARRAY 3 - 5.550 kW[x15] (N) MODULESTILT: 35 DEGREESROOF PITCH: 8:12AZIMUTH: 220 DEGREESARRAY 1 - 4.440 kW[x12] (N) MODULESTILT: 35 DEGREESROOF PITCH: 8:12AZIMUTH: 130 DEGREESINTERIOR PV EQUIPMENT18 IN. FIRE ACCESS PATH18 IN. FIRE ACCESS PATH18 IN. FIRE ACCESS PATH18 IN. FIRE ACCESS PATH18 IN. FIRE ACCESS PATH36 IN. FIRE ACCESS PATH36 IN. FIRE ACCESS PATH36 IN. FIRE ACCESS PATHAMODULE STRINGINGAMODULE STRINGINGBFIRE CLEARANCE36 IN. FIRE ACCESS PATH36 IN. FIRE ACCESS PATHAAAAAAAAAAABBBCCCCBBBBBCCCCARRAY 2 - 0.740 kW[x2] (N) MODULESTILT: 35 DEGREESROOF PITCH: 8:12AZIMUTH: 220 DEGREESMODULE STRINGINGCBConcept Approval ONLYSubject to Field InspectionInspectorDate2020MN BldgCode11/28/2022dpfannensteinNo less than 18 inch clearsetback is required on bothsides of a horizontal ridge,valley, or hipFor each roof plane with a photo-voltaicarray, a 36 inch wide pathway shall beprovided from lowest roof edge to ridge onthe same roof plane, on adjacent roof planes.One shall be on street/driveway side. GENERAL NOTES1.FIELD VERIFY ALL MEASUREMENTS2.ITEMS BELOW MAY NOT BE ON THIS PAGE3.24/7 UNESCORTED KEYLESS ACCESS SHALL BEROOF TRUSSESMODULE:LG ELECTRONICSLG370N1K-E6370 WATTS41.02''69.61"BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674A-103.00SOLAR ATTACHMENT PLAN(SHEET 5)03/32"=1'-0"ELECTRICAL PLAN015'-4"10'-8"FLUSH MOUNT SOLAR MODULES ATTACHEDTO ROOF SURFACE (SEE SHEET S-501 FORMOUNTING DETAILS)ROOF MATERIAL IS ASPHALT SHINGLENEWS17'-1"24'-9"6'-10" IN BRANCHBLACKREDL1NL2G20AACB110A(29) (N) ENPHASEIQ8PLUS-72-2-US(29) (N) LG ELECTRONICSLG370N1K-E6370WSYSTEM EQUIPPED WITH RAPIDSHUTDOWN DISCONNECT PER NEC 690.12SYSTEM COMPLIANT WITH NEC 690.13CB4ETHERNET CABLETO BROADBAND ROUTERENPHASEENVOYCOMMUNICATIONSGATEWAYIN BRANCHBLACKRED20AB9CB2IN BRANCHBLACKRED120AСCB3(N ) AC COMBINER BOX125A, 120/240V, 1Ø, 3W MAX.ENPHASE IQ COMBINER 4(X-IQ-AM1-240-4)CONTINUOUS CURRENT: 65AMAX. OCPD: 90A(N) JUNCTION BOXNG(E)UTILITYMETERTO (E)LOADS(E) GROUNDINGELECTRODEGROUNDRODTO UTILITYGRID (UG)L1L2NEQUIPMENT LEFTLINE IS (N) NEWEQUIPMENT RIGHTLINE IS (E) EXISTINGUNLESS OTHERWISE NOTED.(E)MAIN200A4AC DISCONNECT60AGF1-2FUSES 45A3(E) MAIN ELECTRICAL PANEL240/120 V 1Ø, 3WMAIN BUSS: 200A1282PV METERMODULE STRINGINGAMODULE STRINGINGBMODULE STRINGINGCL1L2TAPNV LINELOADCONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONSIDTYPICALCONDUCTORCONDUITCURRENT-CARRYINGCONDUCTORS IN CONDUITOCPDEGCTEMP. CORR.FACTORCONDUIT FILLFACTORCONT.CURRENTMAX. CURRENT(125%)BASE AMP.DERATEDAMP.TERM. TEMP. RATINGAMP. @ TERMINAL1110 AWG THWN-2, COPPER0.75'' DIA EMT620A6 AWG THWN-2, COPPER0.96 (32.1 °C)0.813.31A16.64A40A30.72A75°C35A218 AWG THWN-2, COPPER0.75'' DIA EMT2N/A6 AWG THWN-2, COPPER0.96 (32.1 °C)135.09A43.86A55A52.8A75°C50A318 AWG THWN-2, COPPER0.75'' DIA EMT245A6 AWG THWN-2, COPPER0.96 (32.1 °C)135.09A43.86A55A52.8A75°C50A416 AWG THWN-2, COPPER0.75'' DIA EMT2N/A6 AWG THWN-2, COPPER0.96 (32.1 °C)135.09A43.86A75A72A75°C65ABFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674E-601.00LINE DIAGRAM(SHEET 6) SYSTEM SUMMARYBRANCH #1BRANCH #2BRANCH #3INVERTERS PER BRANCH1298MAX AC CURRENT14.52A10.89A9.68AMAX AC OUTPUT POWER3,600W2,700W2,400WARRAY STC POWER10,730WARRAY PTC POWER9,979WMAX AC CURRENT35.09AMAX AC POWER8,700WDERATED (CEC) AC POWER8,700WDISCONNECTSINVERTERSOCPDSMODULESASHRAE EXTREME LOW-35.2°C (-31.4°F), SOURCE: AIRLAKE (44.63°; -93.22°)ASHRAE 2% HIGH32.1°C (89.8°F), SOURCE: AIRLAKE (44.63°; -93.22°)REF.QTY.RATED CURRENTMAX VOLTAGECB1-3320A240VACCB4110A240VACF1-2245A240VACREF.QTY.MAKE AND MODELRATED CURRENTMAX RATED VOLTAGESW11EATON DG222NRB OR EQUIV.60A240VACREF.QTY.MAKE AND MODELPMAXPTCISCIMPVOCVMPTEMP. COEFF. OF VOCFUSE RATINGPM1-2929LG ELECTRONICS LG370N1K-E6370W344.1W11.23A10.68A41.4V34.7V-0.108V/°C (-0.26%/°C)20AREF.QTY.MAKE AND MODELACVOLTAGEGROUNDOCPDRATINGRATEDPOWERMAX OUTPUTCURRENTMAX INPUTCURRENTMAX INPUTVOLTAGECEC WEIGHTEDEFFICIENCYI1-2929ENPHASE IQ8PLUS-72-2-US240VFLOATING20A290W1.21A15A60V97.0%BILL OF MATERIALSCATEGORYMAKEMODEL NUMBERREFQTYUNITQTY/UNITDESCRIPTIONMODULELG ELECTRONICSLG370N1K-E6PM1-2929PIECES1LG ELECTRONICS LG370N1K-E6 370W 120 HALF-CUT CELLS, MONOCRYSTALLINE SILICONINVERTERENPHASEIQ8PLUS-72-2-USI1-2929PIECES1ENPHASE IQ8PLUS-72-2-US 290W INVERTERDISCONNECTEATONDG222NRBSW11PIECE1EATON DG222NRB, FUSED, 2-POLE, 60A, 240VAC OR EQUIVALENTPRODUCTION METERGENERIC MANUFACTURERGEN-METER-80AM11PIECE1ELECTRICAL METER, OWNER APPROVEDMISC ELECTRICAL EQUIPMENTGEN-CABLE-CLIPHDWR32-177145PIECES1GENERIC CABLE CLIPAC COMBINER PANELENPHASE-IQ4-PANELEP11PIECE1ENPHASE IQ COMBINER 4 (X-IQ-AM1-240-4)WIRINGENPHASEQ-12-17-240EN1-2929PIECES1ENPHASE ENGAGE (TM) TRUNK CABLEWIRINGENPHASEQ-TERM-10EN301BUNDLE10ENPHASE ENGAGE (TM) BRANCH TERMINATORWIRINGENPHASEQ-SEAL-10EN311BUNDLE10ENPHASE ENGAGE (TM) WATERTIGHT SEALING CAPWIRINGGEN-10-AWG-THWN-2-CU-RDWR1135FEET110 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-10-AWG-THWN-2-CU-BLKWR1135FEET110 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-8-AWG-THWN-2-CU-RDWR2-320FEET18 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-8-AWG-THWN-2-CU-BLKWR2-320FEET18 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-8-AWG-THWN-2-CU-WHWR2-320FEET18 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIRINGGEN-6-AWG-THWN-2-CU-RDWR410FEET16 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-6-AWG-THWN-2-CU-BLKWR410FEET16 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-6-AWG-THWN-2-CU-WHWR410FEET16 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIRINGGEN-6-AWG-THWN-2-CU-GRWR1-475FEET16 AWG THWN-2, COPPER, GREEN (GROUND)WIREWAYENPHASEET-SPLK-05EN61BUNDLE5ENPHASE ENGAGE (TM) ENGAGE COUPLERWIREWAYGEN-EMT-0.75'' DIAWW1-475FEET1EMT CONDUIT, 0.75'' DIAOCPDGENERIC MANUFACTURERGEN-CB-20A-240VACCB1-33PIECES1CIRCUIT BREAKER, 20A, 240VACOCPDGENERIC MANUFACTURERGEN-CB-10A-240VACCB41PIECE1CIRCUIT BREAKER, 10A, 240VACOCPDGENERIC MANUFACTURERGEN-FU-45A-240VACF1-22PIECES1FUSE, 45A, 240VACTRANSITION BOXGENERIC MANUFACTURERGEN-AWB-TB-4-4XJB11PIECE1TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKSE-602.00DESIGN TABLES(SHEET 7)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674 (E) UTILITY METERGRADE(E) UTILITYTO (E) MEP(INTERIOR)TO PV ARRAY(N) AC LOADCENTER(N) AC DISCONNECT(N) PV METER!CAUTION!POWER TO THIS BUILDING IS ALSO SUPPLIEDFROM ROOF MOUNTED SOLAR ARRAYS WITHSAFETY DISCONNECTS AS SHOWN:E-603.00PLACARDS(SHEET 8)BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA76867401EQUIPMENT ELEVATIONNOT TO SCALEMAIN DISTRIBUTIONUTILITY DISCONNECTLABELING NOTES1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE, INTERNATIONALFIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z5351.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING”WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535]ELECTRICAL SHOCK HAZARDTERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONWARNINGLABEL 1AT EACH DISCONNECTING MEANS FORPHOTOVOLTAIC EQUIPMENT (2" X 4").[NEC 690.13].POWER SOURCEOUTPUT CONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICEWARNINGLABEL 2AT POINT OF INTERCONNECTIONOVERCURRENT DEVICE (2" X 4").[NEC 705.12(B)(2)(3)(B)].PHOTOVOLTAIC SYSTEMAC DISCONNECTRATED AC OUTPUT CURRENTNOMINAL OPERATING AC VOLTAGELABEL 3AT POINT OF INTERCONNECTION, MARKEDAT DISCONNECTING MEANS (4" X 2").[NEC 690.54]LABEL 4AT EACH AC DISCONNECTING MEANS(4" X 1").[NEC 690.13(B)].INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTEDPHOTOVOLTAIC SYSTEM DISCONNECT LOCATEDSOUTH SIDE OF THE HOUSEDIRECTORYPERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICEDISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTINGMEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").[NEC 690.56(B)]WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, ADIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PVSYSTEM DISCONNECTING MEANS.PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED INBATHROOMS[NEC 690.4(D),(E)]WARNING: PHOTOVOLTAICPOWER SOURCELABEL 9AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRINGMETHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERESEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,OR FLOORS (5 3/4" X 1 1/8").[NEC 690.31(G)]LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;REFLECTIVE[IFC 605.11.1.1]SOLAR PV SYSTEMEQUIPPED WITHRAPID SHUTDOWNTURN RAPID SHUTDOWN SWITCH TOTHE "OFF" POSITION TO SHUT DOWNPV SYSTEM AND REDUCE SHOCKHAZARD IN ARRAYSOLAR ELECTRICPV PANELSLABEL 6AT RAPID SHUTDOWN SYSTEM(3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)].WARNINGDUAL POWER SUPPLYSOURCES: UTILITY GRID AND PV SOLAR ELECTRICSYSTEMLABEL 7AT POINT OF INTERCONNECTION(2 3/4" X 1 5/8").[NEC 705.12(B)(3)]WARNINGSOLAR ELECTRICCIRCUIT BREAKERIS BACKFEDPHOTOVOLTAIC SOLARAC DISCONNECTLABEL 8AT POINT OF INTERCONNECTION(2" X 1").[NEC 705.12(B)(3)]CAUTIONSOLAR ELECTRIC SYSTEM CONNECTEDLABEL 10AT UTILITY METER (5 3/4" X 1 1/8")[NEC 690.56(B)]RAPID SHUTDOWNSWITCH FORSOLAR PV SYSTEMLABEL 5AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2").[NEC 690.56(C)(3)].35.09AV240FRONTBACKNEWSPV ARRAYPV ARRAY SHEET KEYNOTES1. ROOF MATERIAL: ASPHALT SHINGLE2. ROOF STRUCTURE: TRUSS3. ATTACHMENT TYPE: IRONRIDGE FLASHFOOT24. MODULE MANUFACTURER: LG ELECTRONICS5. MODULE MODEL: LG370N1K-E66. MODULE LENGTH: 69.61''7. MODULE WIDTH: 41.02''8. MODULE WEIGHT: 40.79 LBS.9. SEE SHEET A-103 FOR DIMENSION(S)10. MIN. FIRE OFFSET: 18" FROM RIDGE, 36" FROM EDGE.11. TRUSS SPACING: 18 IN. O.C.12. TRUSS SIZE: 2X4", 2X6" NOMINAL13. LAG BOLT DIAMETER: 5/16" IN.14. LAG BOLT EMBEDMENT: 2-1/4" IN.15. TOTAL # OF ATTACHMENTS: 8316. TOTAL AREA: 575.05 SQ. FT.17. TOTAL WEIGHT: 1386.75 LBS.18. WEIGHT PER ATTACHMENT: 16.71 LBS.19. DISTRIBUTED LOAD: 2.41 PSF20. MAX. HORIZONTAL STANDOFF: 36 IN.21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITHMODULE MANUFACTURER'S INSTRUCTIONS.22. STANDOFF STAGGERING: YES23. RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE24. RAIL MODEL (OR EQUIVALENT): XR10025. RAIL WEIGHT: 0.68 PLF.26. MAX. TRUSS SPAN: 24, 28 FT.27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.S-501D52011121413151822ROOF SLOPE 910106217S-501D4315425242382721. FIELD VERIFY ALL MEASUREMENTSGENERAL NOTESBFAD E23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)AC D EG HB CF G H1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674S-501.00ASSEMBLY DETAILS(SHEET 9)D4DETAIL (TRANSVERSE)NOT TO SCALED5DETAIL (LONGITUDINAL)NOT TO SCALED1RACKING DETAIL (TRANSVERSE)NOT TO SCALED3RACKING DETAIL (TOP)NOT TO SCALED2RACKING DETAIL (LONGITUDINAL)NOT TO SCALE10/17/2022 BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674R-001.00RESOURCE DOCUMENT(SHEET 10) BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674R-002.00RESOURCE DOCUMENT(SHEET 11) BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674R-003.00RESOURCE DOCUMENT(SHEET 12) BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674R-004.00RESOURCE DOCUMENT(SHEET 13) BFADE23UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.NEW PV SYSTEM:10.730 kWp (DC) / 8.410 kWp (AC)ENGINEER OF RECORD07.11.2022DESIGN BY:I.P.M.M.MONSONRESIDENCE5744 162ND ST WLAKEVILLE, MN 55044APN: 222058001020CASE #:PAPER SIZE: 11" x 17" (ANSI B)ACDEGHBCFGH1456CONTRACTORGOLDEN ELECTRIC, LLCPHONE:763-412-5714LIC. NO.:DATE:CHECKED BY:REVISIONSHIC. NO.:ELE. NO.:ADDRESS:4250 INLAND LANE NORTHPLYMOUTH, MN 55446EA768674R-005.00RESOURCE DOCUMENT(SHEET 14)