HomeMy WebLinkAboutLA209888 - APPROVED - Thooft Travis Letter SSVSE Project Number: U3356.0074.231
February 7, 2023
MN Solar and More LLC
ATTENTION: Leah Johnson
310 Oak Street South
New London, MN 56276
REFERENCE: Thooft Travis Residence: 16573 Elm Creek Lane, Lakeville, MN 55044
MN Solar and More LLC Project: 75
Solar Array Installation
To Whom It May Concern:
We have reviewed the existing structure at the above referenced site.The purpose of our review was to determine the
adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on the panel
layout plan.
Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation.
Design Parameters
Code: 2020 Minnesota Residential Code (2018 IRC)
Risk Category: II
Design wind speed, Vult: 115 mph (3-sec gust)
Wind exposure category: C
Ground snow load, Pg: 50 psf
Existing Roof Structure
Roof structure: manufactured trusses @ 24" o.c.
Roofing material: composite shingles
Connection to Roof
Mounting connection: (1) 5/16" lag screw w/ min. 2.5" threaded embedment into framing at max. 48" o.c. along rails
Install (2) rails per row of panels, evenly spaced; panel length perpendicular to the rails shall not exceed 70 in
Rail cantilever shall not exceed 33% of connection spacing
Connections shall be staggered so as not to overload any existing structural member
Conclusions
Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation.
The glass surface of the solar panels allows for a lower slope factor per ASCE 7,resulting in reduced design snow load on
the panels.The gravity loads,and thus the stresses of the structural elements,in the area of the solar array are either
decreased or increased by no more than 5%.Stress decreases or increases of no more than 5%are considered acceptable.
Therefore, the structure is permitted to remain unaltered.
651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com
VSE Project Number: U3356.0074.231
Thooft_Travis Residence
2/7/2023
The solar array will be flush-mounted (no more than 10"above the roof surface)and parallel to the roof surface.Thus,we
conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible.
The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift),
the governing load case.Increases in lateral forces less than 10%are considered acceptable.Thus the existing lateral force
resisting system is permitted to remain unaltered.
Limitations
Installation of the solar panels must be performed in accordance with manufacturer recommendations.All work performed
must be in accordance with accepted industry-wide methods and applicable safety standards.The contractor must notify
Vector Structural Engineering,LLC should any damage,deterioration or discrepancies between the as-built condition of the
structure and the condition described in this letter be found.The use of solar panel support span tables provided by others is
allowed only where the building type,site conditions,site-specific design parameters,and solar panel configuration match
the description of the span tables.The design of the solar panels,solar racking (mounts,rails,etc.)and electrical engineering
is the responsibility of others.Waterproofing around the roof penetrations is the responsibility of others.Vector Structural
Engineering assumes no responsibility for improper installation of the solar array.Vector Structural Engineering shall be
notified of any changes from the approved layout prior to installation.
VECTOR STRUCTURAL ENGINEERING, LLC
02/07/2023
_______________________________________________________
Brett Veazie, P.E.
Project Engineer
Enclosures
BDV/jss
I hereby certify that this plan, specification or report was prepared
by me or under my direct supervision and that I am a duly Licensed
Professional Engineer under the laws of the State of Minnesota.
Brett Veazie, License No. 56392,
Expiration Date: 30-June-2024
02/07/2023
651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com
Concept Approval ONLYSubject to Field Inspection
Inspector Date
2020
MN Bldg
Code
02/15/2023dpfannenstein
Please provide a copy of
the City Approved plans on
site at final inspection.
JOB NO.:U3356.0074.231
SUBJECT:WIND PRESSURE
PROJECT:Thooft Travis Residence
Label:Note: Calculations per ASCE 7-10
SITE-SPECIFIC WIND PARAMETERS:
Basic Wind Speed [mph]:115 Notes:
Exposure Category:C
Risk Category:II
Importance Factor, I:
ADDITIONAL INPUT & CALCULATIONS:
Height of Roof, h [ft]:30 (Approximate)
Comp/Cladding Location:No
Enclosure Classification:
Zone 1 GCp:1.0 Figure 30.4-2C (enter negative pressure coefficients)
Zone 2 GCp:1.2
Zone 3 GCp:1.2
α:9.5 Table 26.9-1
zg [ft]:900 Table 26.9-1
Kh:0.98 Table 30.3-1
Kzt:1 Equation 26.8-1
Kd:0.85 Table 26.6-1
Velocity Pressure, qh [psf]:28.3 Equation 30.3-1
GCpi:0 Table 26.11-1
PRESSURES:Equation 30.9-1
Zone 1, p [psf]:27.9 psf (1.0 W, Interior Zones, beyond 'a' from roof edge)
Zone 2, p [psf]:33.5 psf (1.0 W, End Zones, within 'a' from roof edge)
Zone 3, p [psf]:33.5 psf (1.0 W, Corner Zones, within 'a' from roof corner)
(a= 3 ft)
Solar Panel Array
Gable Roofs 27° < θ ≤ 45°
Enclosed Buildings
Components and Cladding Wind Calculations
()()piphGCGCqp−=
JOB NO.:U3356.0074.231
SUBJECT:CONNECTION
PROJECT:Thooft Travis Residence
Calculate Uplift Forces on Connection
Pressure
(0.6 Dead -0.6 Wind)
(psf)
Max Trib. Width1
(ft)
Max Trib.
Area2
(ft2)
Max Uplift
Force
(lbs)
Zone 1 14.9 4.0 11.7 174
Zone 2 18.3 4.0 11.7 214
Zone 3 18.3 4.0 11.7 214
Calculate Connection Capacity
Lag Screw Size [in]:5/16
Cd:1.6 NDS Table 2.3.2
Embedment3 [in]:2.5
Grade:
Nominal Capacity [lbs/in]:205 NDS Table 12.2A
Number of Screws:1
Prying Coefficient:1.4
Total Capacity [lbs]:586
Determine Result
Maximum Demand [lbs]:214
Lag Screw Capacity [lbs]:586
Result:Capacity > Demand, Connection is adequate.
Notes
1. 'Max Trib. Width' is the width along the rails tributary to the connection.
3. Embedment is measured from the top of the framing member to the beginning of the tapered tip of the lag
screw. Embedment in sheathing or other material is not effective. The length of the tapered tip is not part of the
embedment length.
2. 'Max Trib Area' is the product of the 'Max. Trib Width' and 1/2 the panel width/height perpendicular to the
rails. (2) rails per row of panels. Length of panels perpendicular to the rails shall not exceed 70".
SPF (G = 0.42)
VECTOR STRUCTURAL ENGINEERS
JOB NO.:U3356.0074.231
SUBJECT:GRAVITY LOADS
PROJECT:Thooft Travis Residence
GRAVITY LOADS Roof Pitch: 8.0 :12
ROOF DEAD LOAD (D)
Increase due to
pitch
Material weight
[psf]
Composite Shingles 1.20 2.0
1/2" Plywood 1.20 1.0
Framing 1.00 3.0
Insulation 1.00 0.5
1/2" Gypsum Clg.1.20 2.0
M, E & Misc 1.00 6.5
Total Existing Roof DL
PV Array DL 1.20 3
DL:1.20
ROOF LIVE LOAD (Lr)
Existing Design Roof Live Load [psf]20 ASCE 7-10 Table 4.3-1
Roof Live Load With PV Array [psf]0
SNOW LOAD (S):w/ Solar Array
Roof Slope [x:12]:8.0
Roof Slope [°]:34
Ground Snow Load, pg [psf]:50 ASCE 7-16, Section 7.2
Terrain Category:C ASCE 7-16, Table 7.3-1
Exposure of Roof:Fully Exposed ASCE 7-16, Table 7.3-1
Exposure Factor, Ce:0.9 ASCE 7-16, Table 7.3-1
Thermal Factor, Ct:1.1 ASCE 7-16, Table 7.3-2
Risk Category:II ASCE 7-16, Table 1.5-1
Importance Factor, Is:1.0 ASCE 7-16, Table 1.5-2
Flat Roof Snow Load, pf [psf]:35 ASCE 7-16, Equation 7.3-1
Minimum Roof Snow Load, pm [psf]:0 ASCE 7-16, Section 7.3.4
Unobstructed Slippery Surface?Yes ASCE 7-16, Section 7.4
Slope Factor Figure:Figure 7-2b ASCE 7-16, Section 7.4
Roof Slope Factor, Cs:0.61 ASCE 7-16, Figure 7.4-1
Sloped Roof Snow Load, ps [psf]:21 ASCE 7-16, Equation 7.4-1
Design Snow Load, S [psf]:2135
8.0
34
50
C
Fully Exposed
0.9
1.1
II
1.0
35
0
No
Figure 7-2b
1.00
35
Design material
weight [psf]
2.4
1.2
3.0
0.5
2.4
6.5
16.0
3.6
#VALUE!
2020 MRC, Section R324.4.1.1
Existing
JOB NO.:U3356.0074.231
SUBJECT:LOAD COMPARISON
PROJECT:Thooft Travis Residence
Summary of Loads
Existing With PV Array
D [psf]16 20
Lr [psf]20 0
S [psf]35 21
Maximum Gravity Loads:
Existing With PV Array
(D + Lr) / Cd [psf]29 22 ASCE 7-10, Section 2.4.1
(D + S) / Cd [psf]44 35 ASCE 7-10, Section 2.4.1
Maximum Gravity Load [psf]:44 35
Ratio Proposed Loading to Current Loading:80%OK
The gravity loads, and thus the stresses of the structural elements, in the area of the
solar array are either decreased or increased by no more than 5%. Stress decreases or
increases of no more than 5% are considered acceptable. Therefore, the structure is
permitted to remain unaltered.
(Cd = Load Duration Factor = 0.9 for D, 1.15 for S, and 1.25 for Lr)
VECTOR STRUCTURAL ENGINEERS
JOB NO.:U3356.0074.231
SUBJECT:SOLAR LAYOUT
PROJECT:Thooft Travis Residence