Solar Professional Engineering Consulting 2023.05.24 admin@lucenteng.co
Everlight Solar
PO Box 930550
Verona, WI 53593
RE: Engineering Services
Gore Residence
16165 Harmony Path, Lakeville, MN
8.32 kW System
Solo Job #3695819
To Whom It May Concern,
A. Assumptions from Field Observation provided by Everlight Solar
Roof Roof B
Roof Finish :Asphalt Shingle Asphalt Shingle
Roof Underlayment :OSB OSB
Roof Profile :Gable Gable
Roof Structural System :Metal Plate Trusses Metal Plate Trusses
Truss Top Chord/Setup :2 x 4 / Fan 2 x 4 / Fan
Chord/Rafter Wood Grade :Doug-Fir #2 or better Doug-Fir #2 or better
Truss/Rafter Spacing :24'' o.c.24'' o.c.
Roof Slope :30 deg 30 deg
Max Top Chord/Rafter Span :5.79 ft 5.79 ft
Bearing Wall Type : Convl Lt-Frame Constr CLFC
Foundation : Permanent Concrete Permanent Concrete
Stories : Single Single
B. Building Design Criteria
Code : 2020 MNRC (ASCE 7-16) Risk Category : II
Roof Live Load : 20 psf (0 psf at panels) Occupancy Class : IRC-1
Ground Snow Load : 50 psf Roof Dead Load : 6.5 psf
Ult Wind Speed : 115 mph PV Dead Load : 3 psf
Exposure Category : C Total Dead Load : 9.5 psf
C. Summary of Existing Structure Results
Roof
- Adaquate to support the additional imposed loads. No structural upgrades are required.
Lucent Engineering, P.C.
June 22, 2023
We have reviewed the following information regarding the solar panel installation for this project. Alterations to
these documents or plans shall not be made without direct written consent of the Engineer of Record.
The following structural design regarding the proposed alterations have been prepared from these
assumptions. The verification of the field observations is the responsibility of the contractor. Prior to
commencement of work, the contractor shall verify the framing sizes, spacings, and spans noted in the
sealed plans, calculations, and/or certification letter and notify the Engineer of Record of any
discrepancies.
After review of the field observations and based on our calculations and in accordance with the
applicable building codes and current industry standards, the existing roof structure supporting the
proposed alterations consisting of the solar array has been determined to be:
D. Solar Panel Support Bracket Anchorage
1.
2. Manufacturer's Panel Bracket Connection to Roof Chord/Rafter Member:
Fastener : (1) 5/16'' Lag Screw per Bracket
NDS Withdrawl Value : 266 lbs/inch
Min. Thread Length and Pentration Depth : 2.5''
3.
4.
E. Overall Summary
Sincerely,
Nicholas J. Bowens, PE
License No. 60936
Limits of Scope of Work and Liablity
Page 2 of 2
Gore Residence
Should you have any questions regarding this letter or if you require further information, do not hesitate to
contact me.
Considering the existing roof's slope, size, spacing, condition, and calculated loads, the panel
bracket supports shall be placed no greater than 48 in. o/c.
Panel supports connections shall be staggered to distribute load to adjacent trusses.
Solar panels shall be designed, mounted, and installed in accordance with the most recent
''Quickbolt Manual'', which can be found on the Quickbolt website (http://quickbolt.com).
Based on the information supplied to us at the time of this report, on the evaluation of the existing structure,
and solar array panel bracket connection, it is our opinion that the roof system will adequately support the
additional loads imposed by the solar array. This evaluation conforms to 2020 MNRC and current industry
standards.
The existing structure is assumed to have been designed and constructed following appropriate codes at the
time of erection and assumed to have appropriated permits. The calculations performed are only for the roof
framing supporting the solar array installation referenced in the stamped plans and were completed according
to generally recognized structural analysis standards and procedures, professional engineering, and design
experience opinions and judgements. Existing deficiencies which are unknown or were not observed during
the time the site observation are not included in this scope of work. All solar panel modules, racking, and
mounting equipment shall be designed and installed per the manufacturer's approved installation
specifications. The Engineer of Record and the engineering consulting firm assume no responsibility for
misuse or improper installation. This analysis is not stamped for water leakage. Framing was determined on
information in provided plans and/or photos, along with engineering judgement. Prior to commencement of
work, the contractor shall verify the framing sizes, spacings, and spans noted in the stamped plans,
calculations, and/or certification letter and notify the Engineer of Record of any discrepancies prior to starting
construction. If during solar panel installation, the roof framing members appear unstable or deflect non-
uniformly, our office should be notified before proceeding with the installation. The contactor shall also verify
that there are no damage/deficiencies (i.e., dry rot, water damage, termite damage, framing
member/connection damage, etc.) to framing that was not addressed in the stamped plans, calculations,
and/or certification letter and notify the Engineer of Record of any concerns prior to starting construction.
Lucent Engineering, P.C.June 22, 2023
06/22/23
Concept Approval ONLYSubject to Field Inspection
Inspector Date
2020
MN Bldg
Code
07/06/2023dpfannenstein
Please provide a City
Approved Plan and Permit
Card on site accessible for
Inspectors until final inspection
DRAWN BY: SoloCAD
6/21/2023
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
COVER - PV01
GENERAL NOTES
1.INSTALLATION OF SOLAR PHOTOVOLTAIC SYSTEM SHALL BE IN ACCORDANCE WITH NEC ARTICLE 690,
AND ALL OTHER APPLICABLE NEC CODES WHERE NOTED OR EXISTING
2.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL
EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110
3.ALL WIRES, INCLUDING THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM
PHYSICAL DAMAGE IN ACCORDANCE WITH NEC ARTICLE 250
4.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE; THIS SYSTEM IS UTILITY INTERACTIVE PER UL
1741 AND DOES NOT INCLUDE STORAGE BATTERIES OR OTHER ALTERNATIVE STORAGE SOURCES
5.ALL DC WIRES SHALL BE SIZED ACCORDING TO [NEC 690.8]
6.DC CONDUCTORS SHALL BE WITHIN PROTECTED RACEWAYS IN ACCORDANCE WITH [NEC 690.31]
7.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL JURISDICTIONAL BUILDING CODE
PHOTOVOLTAIC (PV) SYSTEM SPECIFICATIONS
ELECTRICAL EQUIPMENT
PV MODULES:
(25) SOLAR AMERICA S4A410-72MH5
DC SYSTEM SIZE: 10.25 KW DC
INVERTER(S):
(13) AP SYSTEMS DS3-S INVERTER(S)
AC SYSTEM SIZE: 8.32 KW AC
RACKING
RACKING: IRONRIDGE XR-10
ATTACHMENT: QUICKBOLT 2 (QB2)
APPLICABLE GOVERNING CODES
2020 NATIONAL ELECTRICAL CODE
2020 MINNESOTA BUILDING CODE
2020 MINNESOTA RESIDENTIAL CODE
2020 MINNESOTA FIRE CODE
OCCUPANCY: IRC-1
ZONING: RESIDENTIAL
SITE SPECIFICATIONS
PV01 COVER
PV02 SITE PLAN
PV03 ROOF PLAN
PV04 MOUNTING DETAIL
PV05 LINE DIAGRAM
PV06 ELECTRICAL CALCS
PV07 LABELS
PV08 PLACARD
PV09 SITE PHOTOS
SHEET INDEX
STREET VIEW
AERIAL VIEW
06/22/23
MSP
AC PVC
JB
M
JB
JB
6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:16165 Harmony PathFRONT OF HOMEVISIBLE, LOCKABLE,
LABELED AC DISCONNECT
LOCATED WITHIN 10'
OF UTILITY METER
MP1
MP2
MP3
EQUIPMENT LEGEND:
INVERTERVISIBLE, LOCKABLE, LABELED
AC DISCONNECT
METER SOCKET
(FOR UTILITY PV METER)
UTILITY METER
MAIN SERVICE PANEL LC LOAD CENTER
FIRE ACCESS PATHWAY (3' TYP)
C
INV
PV
AC
MSP
M
COMBINER BOX PROPERTY LINEBATTBATTERY(IES)
SUB SUB PANEL SD SERVICE DISCONNECT
JB JUNCTION BOX
PV MODULES
SITE PLAN - PV02
DRIVEWAY
ARRAY DETAILS:
MOUNTING PLANE:AZIMUTH:TILT:
MP1 180°30°
MP2 270°30°
MP3 270°30°
128'-5"
85'-0"
129'-1"
06/22/23
MSP
AC PVC
JB
M
JB
JB
EQUIPMENT INFORMATION:ROOF INFO:PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA:
RACKING MANUFACTURER:ROOF TYPE:PV MODULE COUNT:
RACKING PART NUMBER:ROOF FRAMING:ARRAY AREA:
ATTACHMENTS RAFTER/TOP CHORD SIZE:ROOF AREA:
ATTACHMENT QTY:RAFTER/TOP CHORD SPACING:PERCENT OF ROOF COVERED:
SPLICE QTY:ATTACHMENT SPACING:ARRAY WEIGHT:
MIDCLAMP QTY:POINT LOAD:
ENDCLAMP QTY:DISTRIBUTED LOAD: (lbs/ft²)
25
MODULE COUNT * 21.38 FT² = 534.5
2514 FT²
21%
MODULE COUNT * 49 LBS = 1225 LBS
ARRAY LBS/ATTACHMENTS = 20.76
ARRAY WEIGHT/AREA = 2.29 LBS/FT²
IRONRIDGE
XR-10
QUICKBOLT 2 (QB2)
59
4
38
24
ASPHALT SHINGLE
MANUFACTURED TRUSS
2x4
24"
48''6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
ROOF PLAN - PV03
3'-0"
1'-6"
3'-0"
1'-6"
06/22/23
Concept Approval
ONLY
Subject to Field Inspection
Inspector Date
2020
MN Bldg
Code
07/06/2023dpfannenstein
For each roof plane with a photo-voltaic array, two
pathways not less than 36" wide shall be provided from
the lowest roof edge to ridge on the same roof plane as
the array,on an adjacent roof plane, or straddling the
same and adjacent roof planes. Not fewer than one
pathway shall be provided on the street or driveway
side of the house.
Not less than an 18" clear setback
is required on both sides of a
horizontal ridge.
RAIL
L-FOOT/ATTACHMENT BRACKET
(E) ROOF FRAMING
QUICKBOLT 2 (QB2)
FLASHING
PV MODULE
(E) COMP SHINGLE ROOF (1 LAYER)
RAIL
END CLAMP
PV MODULE
MID CLAMP
PV MODULE
4"
2 12" MIN.
DEPTH
RAIL
RAIL
FLASHING & QUICKBOLT 2 (QB2)
2'-8" MIN -
3'-10" MAX
3
RAIL
PV MODULE
" MAX."1'-8"
MAX.
21
FRONT VIEW
10" MIN -
1'-4"
MAX2'-8" MIN -
3'-10" MAX
10" MIN -
1'-4"
MAX
SIDE VIEW
(E) RAFTER/TOP CHORDS
(E) RAFTER/TOP CHORD
DETAIL, MOUNTING AND FLASHING
END CLAMP DETAILS MID CLAMP DETAILS
3
21
EQUIPMENT INFORMATION:ROOF INFO:PHOTOVOLTAIC ARRAY STRUCTURAL CRITERIA:
RACKING MANUFACTURER:ROOF TYPE:PV MODULE COUNT:
RACKING PART NUMBER:ROOF FRAMING:ARRAY AREA:
ATTACHMENTS RAFTER/TOP CHORD SIZE:ROOF AREA:
ATTACHMENT QTY:RAFTER/TOP CHORD SPACING:PERCENT OF ROOF COVERED:
SPLICE QTY:ATTACHMENT SPACING:ARRAY WEIGHT:
MIDCLAMP QTY:POINT LOAD:
ENDCLAMP QTY:DISTRIBUTED LOAD: (lbs/ft²)
25
MODULE COUNT * 21.38 FT² = 534.5
2514 FT²
21%
MODULE COUNT * 49 LBS = 1225 LBS
ARRAY LBS/ATTACHMENTS = 20.76
ARRAY WEIGHT/AREA = 2.29 LBS/FT²
IRONRIDGE
XR-10
QUICKBOLT 2 (QB2)
59
4
38
24
ASPHALT SHINGLE
MANUFACTURED TRUSS
2x4
24"
48''6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
MOUNTING DETAIL - PV04
06/22/23
6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
4 4
UTILITY PV PRODUCTION
METER BASE
(N) 45A FUSES
PV AC DISCONNECT
60A FUSED,
VISIBLE, LOCKABLE,
LABELED, OPEN
240V, 2-POLE LINE SIDE
LOAD SIDE
STRING (1): 12 MODULES
STRING (2): 12 MODULES
N
G
3
AC COMBINER BOX
SOLAR LOADS ONLYUL 1741 COMPLIANT
AC
DC
AC
DC6 INVERTERS
AC
DC
AC
DC6 INVERTERS
(N) 100A
STRING (3): 1 MODULES
AC
DC
AC
DC1 INVERTERS
(3) 20A-2P
1 2
1 2
1 2
NEMA 3R
J-BOX
NEMA 3R
J-BOX
NEMA 3R
J-BOX
NEMA 3R
J-BOX
4
(E) LOADS
N
G
K4977-INT MILBANK
LUG KIT TO BE ADDED
(E) 150A-2P
(E) 150A MAIN SERVICE PANEL
(E)
(E) UTILITY METER
1Ø, 120/240 VAC
TO UTILITY GRID
*SUPPLY SIDE CONNECTION*
NEC 230.46, NEC 230.79 & NEC
705.11
(E) GROUNDING
ELECTRODE
VISIBLE, LOCKABLE,
LABELED AC DISCONNECT
LOCATED WITHIN 10'
OF UTILITY METER LINE DIAGRAM - PV05
CONDUIT & CONDUCTOR SCHEDULE
TAG QTY WIRE GAUGE DESCRIPTION CONDUIT SIZETYPEQTYDESCRIPTIONRATING
EQUIPMENT SCHEDULE
1 (2)12-2 PV-WIRE, USE-2 COPPER - (L1, L2)N/A - FREE AIR(1)6 AWG BARE COPPER - (GROUND)
2 (2)10 AWG THHN/THWN-2 COPPER - (L1, L2)1" EMT(1)10 AWG THWN-2 COPPER - (GROUND)
3 (6)10 AWG THHN/THWN-2 COPPER - (L1, L2)1" EMT(1)10 AWG THWN-2 COPPER -(GROUND)
4 (3)6 AWG THWN-2 COPPER - (L1, L2, NEUTRAL)1" EMT(1)8 AWG THWN-2 COPPER - (GROUND)
MODULES:(25)SOLAR AMERICA S4A410-72MH5 410 W
INVERTERS:(13)AP SYSTEMS DS3-S 640 W
AC DISCONNECT(S): (1)PV AC DISCONNECT, 240V, 2-POLE 60 A
AC COMBINER:(1)PV AC COMBINER 100 A
1-PHASE, 60 HZ, UL 1741 LISTED
POWER MAX (PMAX):
OPEN CIRCUIT VOLTAGE (VOC):
MAX POWER-POINT CURRENT (IMP):
MAX POWER-POINT VOLTAGE (VMP):
SHORT CIRCUIT CURRENT (ISC):
SERIES FUSE RATING:
SOLAR AMERICA S4A410-72MH5 SPECS
410 W
49.1 V
10.03 A
40.9 V
10.61 A
20 A
AP SYSTEMS DS3-S SPECS
MAX INPUT VOLTAGE:60 V
MAX DC SHORT CIRCUIT CURRENT:16 A
MAXIMUM OUTPUT POWER:640 W
MAXIMUM OUTPUT CURRENT:2.66 A
NOM. OUTPUT VOLTAGE:240 V
MAX UNITS PER 20A CIRCUIT:6
6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
SYSTEM OCPD CALCULATIONS
INVERTER MODEL(S):AP SYSTEMS DS3-S
# OF INVERTERS:13
MAX OUTPUT CURRENT:2.66A
(# OF INVERTERS) X (MAX OUTPUT CURRENT) X 125% <= OCPD RATING
(13 X 2.66A X 1.25) = 43.225A <= 45A, OK
SUPPLY SIDE INTERCONNECTION
MAIN BUSBAR RATING:150A
MAIN DISCONNECT RATING:150A
PV OCPD RATING:45A
SERVICE RATING >= PV OCPD
150A >= 45A, OK
NUMBER OF CURRENT CARRYING CONDUCTORS PERCENT OF VALUES
4-6 .80
7-9 .70
10-20 .50
ELECTRICAL CALCS - PV06
CONDUIT & CONDUCTOR SCHEDULE
TAG QTY WIRE GAUGE DESCRIPTION CONDUIT SIZE CONDUCTOR RATING CONDUCTOR TEMP. RATE AMBIENT TEMP TEMP. DERATE
# OF CONDUCTORS
DERATE
CONDUCTOR RATING
W/DERATES
1 (2)12-2 PV-WIRE, USE-2 COPPER - (L1, L2)N/A - FREE AIR 30A 90°C 32°C 0.96 N/A - FREE AIR 28.8A N/A - FREE AIR(1)6 AWG BARE COPPER - (GROUND)
2 (2)10 AWG THHN/THWN-2 COPPER - (L1, L2)1" EMT 40A 90°C 32°C 0.96 1 38.4A 7.3%(1)10 AWG THWN-2 COPPER - (GROUND)
3 (6)10 AWG THHN/THWN-2 COPPER - (L1, L2)1" EMT 40A 90°C 32°C 0.96 0.8 30.72A 17.1%(1)10 AWG THWN-2 COPPER -(GROUND)
4 (3)6 AWG THWN-2 COPPER - (L1, L2, NEUTRAL)1" EMT 65A 75°C 32°C 0.94 1 61.1A 21.9%(1)8 AWG THWN-2 COPPER - (GROUND)
5 (3)0 75°C 1(1)0
6 (3)0 75°C 1(1)0
7 (3)0 75°C 1(1)0
8 (3)0 75°C 1(1)0
CONDUIT FILL
AP Systems DS3-S
STRING CALCULATIONS
MAX AC CURRENT:
MICRO INVERTERS IN SERIES
NOMINAL STRING VOLTAGE:
MAX AC OUTPUT POWER
ARRAY DC POWER:
TOTAL MAX AC CURRENT:
STRING #1
15.96A
6
240V
3840W
10250W
34.58A
STRING #3
2.66A
1
240V
640W
STRING #2
15.96A
6
240V
3840W
GROUNDING & GENERAL NOTES:
1. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE.
2. DC GEC AND AC EGC TO BE SPLICED TO EXISTING ELECTRODE
3. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO BE
INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION.
4. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD -
JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS.
5. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER
AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT.
INTERCONNECTION NOTES:
1. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9] & [NEC 230.95]
2. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC 705.11] WITH SERVICE ENTRANCE CONDUCTORS IN
ACCORDANCE WITH [NEC 240.21]
DISCONNECT NOTES:
1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS
REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS)
2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A
VISIBLE-BREAK SWITCH.
3. FUSED AC DISCONNECT TO BE USED.
6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
LABELS - PV07
LABEL 6
MARKED AT AC DISCONNECTING MEANS.
[NEC 690.54]
LABEL 5
EQUIPMENT CONTAINING OVERCURRENT
DEVICES IN CIRCUITS SUPPLYING POWER TO A
BUSBAR OR CONDUCTOR SUPPLIED FROM
MULTIPLE SOURCES SHALL BE MARKED TO
INDICATE THE PRESENCE OF ALL SOURCES.[NEC
705.12(B)(3)(3)]
LABEL 3
PLACED ADJACENT TO THE BACK-FED BREAKER FROM
THE INVERTER IF TIE IN CONSISTS OF LOAD SIDE
CONNECTION TO BUSBAR.
[NEC 705.12(B)(3)(2)]
LABEL 7
AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND
ENCLOSURES OF JUNCTION BOXES, AND OTHER WIRING METHODS; SPACED
AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS,
PARTITIONS, CEILINGS, OR FLOORS.
[NEC 690.31(D)(2)]
LABEL 9
SIGN LOCATED ON OR NO MORE THAN 3FT
FROM INITIATION DEVICE
[NEC 690.56(C)(2)].
LABEL 8
FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND CONDUCTORS
LEAVING THE ARRAY:
SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM
SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE
CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED
RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION.
[NEC 690.56(C)(1)]
LABEL 1
PLACED ON THE MAIN DISCONNECTING MEANS FOR THE PV
SYSTEM.
[NEC 690.13(B)]
LABELING NOTES:
1.LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE
EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE
ADJUSTMENTS.
2.LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRIC CODE, OSHA STANDARD
19010.145, ANSI Z535.
3.MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
4.LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC
110.21]
5.LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND
PERMANENTLY AFFIXED [NEC 690.31(D)(2)]
LABEL 4
PLACED ON EQUIPMENT CONTAINING OVERCURRENT
DEVICES IN CIRCUITS SUPPLYING POWER TO
A BUSBAR OR CONDUCTOR SUPPLIED FROM MULTIPLE
SOURCES
[NEC 705.10]
LABEL 2
FOR PV DISCONNECTING MEANS WHERE THE LINE AND
LOAD TERMINALS MAY BE ENERGIZED IN THE OPEN
POSITION.
[NEC 690.13(B)]
WARNING!
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
!WARNING
THIS EQUIPMENT IS FED BY MULTIPLE
SOURCES. TOTAL RATING OF ALL
OVERCURRENT DEVICES, EXCLUDING
MAIN SUPPLY OVERCURRENT
DEVICE, SHALL NOT EXCEED
AMPACITY OF BUSBAR.
PHOTOVOLTAIC AC DISCONNECT
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:
ELECTRIC SHOCK HAZARD
MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT
WARNING!
POWER SOURCE OUTPUT CONNECTION.
DO NOT RELOCATE THIS OVERCURRENT DEVICE.
PHOTOVOLTAIC POWER SOURCE
TURN RAPID SHUTDOWN
SWICH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
RAPID SHUTDOWN
SWITCH FOR
SOLAR PV SYSTEM
35
240
EXISTING SUB PANEL
(ONLY IF WHERE POINT
OF INTERCONNECTION
IS MADE)
**ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF
EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF
INTERCONNECTION METHOD AND LOCATION PRESENTED ELECTRICAL DIAGRAM PAGE. **
JUNCTION BOX
MAIN SERVICE PANEL
AC DISCONNECT
PV COMBINER
SUBPANEL - IF USED TO
COMBINE PV OUTPUT
CIRCUITS OR INVERTER
(ONLY IF PVINTERCONNECTION
CONSISTS OF LOAD
SIDE BREAKER)
(ONLY IF PVINTERCONNECTION
CONSISTS OF LOAD
SIDE BREAKER)
LABELING DIAGRAM:
1
2
3
4
8
5
2
3 4
5
116
3
9
1
7
7
CAUTION!
MULTIPLE SOURCES OF POWER
MSP
AC PVC
JB
M
JB
JB
6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
CAUTION
16165 Harmony Path, Lakeville MN 55044 FRONT OF HOMESYSTEM UTILIZES MICROINVERTERS LOCATED UNDER EACH MODULE
PLACARD - PV08
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED
SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN:
DIRECTORY:
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION
OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC
SYSTEM.
(ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS OUTLINED
WITHIN: NEC 690.56(B)&(C), [NEC 705.10]
RAPID SHUTDOWN AC
DISCONNECT SWITCH
COMBINER
MAIN DISTRIBUTION
UTILITY DISCONNECT
PV ARRAY
6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
SITE PHOTOS:
SITE PHOTOS - PV09
6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
FRONT/BACK VIEWS - PV09.1
SITE PHOTOS:
6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
SITE PHOTOS:
SIDE VIEWS - PV09.2
6/21/2023
DRAWN BY: SoloCAD
SITE INFORMATION
AMANDA GORE
16165 HARMONY PATH
LAKEVILLE, MN 55044
AC SYSTEM SIZE: 8.32 KW AC
DC SYSTEM SIZE: 10.25 KW DC
LAT, 44.7150804
LONG, -93.2289443
(25) SOLAR AMERICA S4A410-72MH5
PV MODULES
(13) AP SYSTEMS DS3-S INVERTER(S)
DAKOTA ELECTRIC
UTILITY ACCOUNT HOLDER: AMANDA GORE
AND MICHAEL GORE
Everlight Solar Construction
7369 Highway 13 W.
Savage, MN 55378
License #: BCC771658
(833) 786-4387 ext. 701
CONTRACTOR INFORMATION:
SITE PHOTOS:
METER/OPEN MSP - PV09.3
Tech Brief:PTWSPÄLK.YV\UKPUNMVY,]LY`(WWSPJH[PVUThe UFO family of components eliminates the need for separate grounding hardware by bonding solar modules directly to IronRidge XR Rails. All system types that feature the UFO family—Flush Mount, Tilt Mount and Ground Mount—are fully listed to the UL 2703 standard.UFO hardware forms secure electrical bonds with both the module and the rail, resulting in many parallel grounding paths throughout the system. This leads to safer and more reliable installations.UFO Family of Components<UP]LYZHS-HZ[LUPUN6IQLJ[<-6The UFO securely bonds solar modules to XR Rails. It comes assembled and lubricated, and FDQÀWDZLGHUDQJHRIPRGXOHKHLJKWVhe gore<UP]LYZHS-HZ[LThe UFO securely bRails. It comes asseFDQÀWDZLGHUDQJH:[VWWLY:SLL]LThe Stopper Sleeve snaps onto the UFO, converting it into a bonded end clamp.)6::™ SpliceBonded Structural Splice connects rails with built-in bonding teeth. No tools or hardware needed.)VUKLK([[HJOTLU[ZThe bonding bolt attaches and bonds the L-foot to the rail. It is installed with the same socket as the rest of the system..YV\UKPUN3\NA single Grounding Lug connects an entire row of PV modules to the grounding conductor.)6::™ SpliceBonded Structural Splice il i h b il i:`Z[LT+PHNYHT<3*LY[PÄJH[PVUThe IronRidge Flush Mount, Tilt Mount, and Ground Mount Systems have been listed to UL 2703 by Intertek Group plc.UL 2703 is the standard for evaluating solar mounting systems. It ensures these devices will maintain strong electrical and mechanical connections over an extended period of time in extreme outdoor environments.0YVU9PKNL0UJ(SSYPNO[ZYLZLY]LK=PZP[^^^PYWH[LU[ZJVTMVYWH[LU[PUMVYTH[PVU=LYZPVUTech Brief*YVZZ:`Z[LT*VTWH[PIPSP[`-LH[\YL -S\ZO4V\U[ ;PS[4V\U[ .YV\UK4V\U[XR Rails((XR100 & XR1000UFO/Stopper(((BOSS™ Splice((N/AGrounding Lugs1 per Row 1 per Row 1 per ArrayMicroinverters & Power OptimizersCompatible with most MLPE manufacturers.Refer to system installation manual.Fire RatingClass A Class A N/AModulesTested or Evaluated with over 400 Framed ModulesRefer to installation manuals for a detailed list.íApproved Enphase microinverters can provide equipment grounding of IronRidge systems, eliminating the need for JURXQGLQJOXJVDQGÀHOGLQVWDOOHGHTXLSPHQWJURXQGFRQGXFWRUV(*&$PLQLPXPRIWZRPLFURLQYHUWHUVPRXQWHGWRWKHsame rail and connected to the same Engage cable is required. Refer to installation manuals for additional details..V[V0YVU9PKNLJVT<-6