Loading...
HomeMy WebLinkAboutLA217906-APPROVED - Michael Mantich Solar Drawings wStamp 09 13 2023COVER PAGECP 0.0PV SYSTEMAS INDICATEDScale:Project:Xcel Energy Application #05573890EXISTINGINVISIMOUNTSITE MAP & PV LAYOUTELECTRICAL 1-LINE DIAGRAMATTACHMENT LAYOUTSYSTEM LABELING DETAILINVERTER DATA SHEETSHEET INDEXPROPERTY PLANRSD DATA SHEETMODULE DATA SHEETATTACHMENT DATA SHEETPV 1.0SYSTEM RATINGEQUIPMENT SUMMARYELECTRICAL INFORMATIONMAIN SERVICE PANEL BUS SIZE:MAIN SERVICE BREAKER SIZE:MOUNTING SYSTEM:BUILDING INFORMATIONCONSTRUCTION TYPE: V-BOCCUPANCY: R3ROOF:VICINITY MAP (SCALE: NTS)SATELLITE VIEW (SCALE: NTS)GENERAL NOTES1.All electrical materials shall be new and listed by recognizedelectrical testing laboratory Custom made equipment shall have complete test data submittedby the manufacturer attesting to its safety2.Outdoor equipment shall be NEMA 3R rated or equivalent3.All metallic equipment shall be grounded4.Contractor shall obtain electrical permits prior to installation andshall coordinate all inspections, testing commissioning andacceptance with the client, utility co. and city inspectors as needed.5.The electrical contractor shall verify the exact locations of servicepoints and service sizes with the serving utility company andcomply with all utility companies requirements.6.Drawings are diagrammatic only, routing of raceways shall beoption of the contractor unless otherwise noted and shall becoordinated with other trades.7.If the roof material or the roof structure not adequate for PVinstallation, call the engineer of record prior to installation. Thecontractor is responsible to verify that the roof is capable ofwithstanding the extra weight.8.If the distances for cable runs are different than shown, thecontractor shall notify the electrical engineer to validate the wiresize. Final drawings will be red-lined and updated as appropriate.9.Whenever a discrepancy in quality of equipment arises on thedrawing or specifications, the contractor shall be responsible forproviding and installing all materials and services required by thestrictest conditions noted on the drawings or in the specificationsto ensure complete compliance and longevity of the operablesystem required by the engineer of record.PHOTOVOLTAIC NOTES:1.Rooftop mounted photovoltaic panels and modules shall be tested,listed and identified by recognized testing laboratory2.Solar system shall not cover any plumbing or mechanical vents3.Modules and support structures shall be grounded unless racking has integrated ground.4.Removal of an interactive inverter or other equipment shall notdisconnect the bonding connection between the groundingelectrode conductor and the photovoltaic source and/or outputcircuit grounded conductors.5.All PV modules and associated equipment and wiring shall beprotected from physical damage.6.Live parts of PV source circuits and PV output circuits over 150v toground shall not be accessible to other than qualified persons while energized.7.Inverter is equipped with integrated DC disconnect, thus providingground fault protection8.All conductors shall be copper and 75 deg rated9.A single conductor shall be permitted to be used to perform themultiple functions of dc grounding, AC grounding and bondingbetween AC and DC systems.10.Non-current carrying metal parts of equipment shall be effectivelybonded together. Bond both ends of raceways.150A150ATHE INSTALLATION OF SOLAR ARRAYS ANDPHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITHTHE FOLLOWING CODES:·2023 National Electrical Code·2018 International Building Code·2018 International Residential Code·2020 Minnesota Residential Code·2020 Minnesota Building Code·2020 Minnesota Energy Code·2020 Minnesota Accessibility Code·2020 Minnesota State Fire Code·2018 International Fire Code·2018 International Energy Conservation Code·2018 Mechanical CodeAS ADOPTED BY THE STATE OF MINNESOTAALL OTHER ORDINANCE ADOPTED BY THELOCAL GOVERNING AGENCIESGOVERNING CODESSURGE PROTECTIONPLACARDDC 12.00 KW STCAC 11.52 KW STC30PV 2.0PV 3.1PV 3.2PV 4.0PV 5.0D 6.0D 7.0D 8.0D 9.0D 10.0D 11.0D 12.0D 13.0COVER PAGECP 0.0COMP. SHINGLETRUSS: 2 X 4 @ 24" O.C.30INVERTER CERTIFICATIONPV INSPECTION CHECKLISTUTILITYDrawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023MONITORING DATA SHEETRACKING DATA SHEETD 14.0 SUNPOWER U-SERIES 400 WATT MODULES INTEGRATED IQ7HS MICROINVERTERSThese drawings are protected by copyright under US law. Any form ofreproduction is strictly prohibited without prior written approval from Engineerinc.WITNESS TESTD 15.0NSI DATA SHEETD 16.0Date Certified andExp. Date : 06/30/2024Signed: 09/13/2023Engineerinc.io,303 N Glenoaks BlvdBurbank, CA 91502(310) 928-0938Concept Approval ONLYSubject to Field InspectionInspectorDate2015MN BldgCode09/13/2023jnuetzman ............................................................................MSP... (E) Main Service PanelINDEXAC....................(N) 60A Utility AC(N) MicroinverterNOTE: Conduit in attic shallbe minimum 18 inches from roof sheatingPVS(N) 125A PV Sub Panel ........Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTNOTE: No clearance issueDistance between all equipments is maximum 10"(E) Main MeterMM.....................................SECONDARY INTERCONNECTION.............INVERTERINVERTER TYPE: Micro:___ Enphase IQ7HS MicroinvertersModel # IQ7HS-66M-US(240V)Xcel Energy Application #05573890TOTAL ROOF AREA: 2247TOTAL MODULE AREA: 66029.37% OF COVERAGESITE MAP & PVLAYOUTPV 1.0PV SYSTEMAS INDICATEDScale:Project:JB(N) Junction Box(N) Solar ModuleEMT Type ConduitFire Setback LineFMT type Conduit3030Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023EQUIPMENT ELEVATIONFrom roofPVSNOTE: Keep 3ft clearance from gas meter and AC unit10"4'PVS6(N) PV Monitoring System.....150APVS6SOLAR MODULES___SUNPOWER 400 WattModel #SUNPOWER U-SERIESMainMeterMainServicePanelUtilityACDisconnect<10'<10'aaaaaaaaaabbbbbbbbbbcccccccccc3' fire setback3' fire setback18'' fire setback18'' fire setbackPVS6PVSACMMMSPUTILITY AC DISCONNECT LOCKABLEAND READLY ACCESSIBLEIberis Ave Solar PV Array 119- Sunpower 400W Modules19-Integrated IQ7HS MicroinvertersPitch: 27 DegOrientation: 90 DegSolar PV Array 22- Sunpower 400W Modules2-Integrated IQ7HS MicroinvertersPitch: 33 DegOrientation: 180 DegSolar PV Array 39- Sunpower 400W Modules9-Integrated IQ7HS MicroinvertersPitch: 27 DegOrientation: 270 DegJBJBJB3' fire setback3' fire setbackSCALE:3/32" = 1'-0" 180° 90° 270°0°SWNE ELECTRICAL 1-LINEDIAGRAMPV 2.0PV SYSTEMAS INDICATEDScale:Project:Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTDesign meet National Electric Code(NEC codes)30SYSTEM RATING AND DER POWER OUTPUTINVERTER:ENPHASE IQ7HSINVERTER MAXIMUM CONTINUOUS OUTPUT:384VASYSTEM POWER OUTPUT:ENPHASE MICROINVERTERS1 PHASE 384VAMAXIMUM OUTPUT CURRENT 1.6AAC PORT BACKFEED CURRENT 0ADC SHORT CIRCUIT CURRENT 15ADC 12.00 KW STCAC 11.52 KW STCDC 12.00 KW STCAC 11.52 KW STCXcel Energy Application #05573890x 384 =11.520SECONDARY INTERCONNECTIONREFERENCE POINT OF APPLICABILITYEXISTING______ MAINSERVICEPANEL120/240V,1P, 3WGEC(E) GROUNDINGELECTRODE SYSTEM150A125A PV SUB PANEL120/240V, NEMA 3RINSTALL (3)20APV 2-POLE C/B60A FUSED UTILITY ACDISCONNECT,WITH 60A FUSES,VISIBLE-OPEN LOCKABLE,READILY ACCESSIBLE,NEMA3R, 120 / 240V(NEW)GECAdd 2nd Ground rod andtie it to the existing ground rod.EXISTINGNON CENTER _____MAIN C/B48 ANOTE: Keep 3ft clearance from gas meter and AC unit3030150AIn locations where there is no local Public Authority, the customer is exempt from inspection, and/or the service has been shut off or disconnected for more than 365 days (1 year),the licensed electrician or wireman shall submit a signed and dated Xcel Energy Electrical Inspection Certificate to the Company’s Builders Call Line attesting that the electricalinstallation has been completed and installed according to the current National Electrical Code®, the Xcel Energy Standard for Electric Installation and Use, and any otherapplicable codes that apply before electric service is energized.Wire Size90C wirerating12 AWGTHWN-2, THHNXHHW-2, USE-210 AWGTHWN-2, THHNXHHW-2, USE-38 AWGTHWN-2, THHNXHHW-2, USE-4304055Temperature rating ofConductors-Ambient Temp.(114-122F) NEC 310.15(B)(2)(a)Number of Current carrying Conductors NEC 310.15(B)(16)4-67-910-2020A Branch Circuit Rating30A Branch Circuit Rating30 x 0.82=24.640 x 0.82=32.855 x 0.82=45.124.6x0.80= 19.6832.8x0.80= 26.2445.1x0.80= 36.0824.6x0.70= 17.2232.8x0.70= 22.9645.1x0.70= 31.5724.6x0.50= 12.332.8x0.50= 16.445.1x0.50= 22.55YES- 6 or less current carryingconductors in the same conduitYES- 9 or less current carryingconductors in the same conduitYES- 20 or less current carryingconductors in the same conduitYES- 9 or less current carryingconductors in the same conduitYES- 3 or less current carryingconductors in the same conduitNOSurge ProtectionMNSPD-300-ACDrawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023AtticWall (6) #12 AWG THWN/THWN-2(1)#12 AWG GND3/4" EMT, 2 FEET(3) #6 AWG THWN/THWN-2(1) #6 AWG GND1" SCH 80 PVC, 2 FEET(3) #6AWG THWN/THWN-21" SCH 80 PVC, 2 FEET(1) #6 AWG GND(E) MAIN METER120/240V,1P, 3WPVS6MONITORING SYSTEM1BRANCHCIRCUIT-A (3) J BOXNEMA3R16A1-PHASE MICRO-INVERTER UL1741210116A210BRANCHCIRCUIT-B (6) #12 AWG THWN/THWN-2(1)#12 AWG GND3/4" FMT, 2 FEETProduction CTsSUNPOWER U-SERIES 400 WATT MODULESINTEGRATED ENPHASE IQ7HS MICROINVERTERSNSI TS250-2Non splicingMechanical LugsSUNPOWER TRUNK CABLE(2) #12 AWG PV WIRE(1) #10 INTEGRATED GROUNDINGFREE IN THE AIRAT THE HOUSE NEAR WIFI15 A1210BRANCHCIRCUIT-C 16A SYSTEMLABELING DETAILPV 3.1PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023PV ARRAYJ BOXPV SUB-PANELACDISCONNECTMAIN SERVICEPANELMETER122221516207124Note: LABELS SHALL COMPLY WITH NEC 690“Labels shall be weatherproof, durable and permanently mounted”Photovoltaic Power SourceLABEL 1CAUTION: SOLAR CIRCUITLABEL 2WARNINGELECTRIC SHOCK HAZARDTHE DC CONDUCTORS OF THISPHOTOVOLTAIC SYSTEM AREUNDERGROUND AND MAY BE ENERGIZEDLABEL 3WARNINGELECTRIC SHOCK HAZARDIF GROUND FAULT IS INDICATEDNORMALLY GROUNDED CONDUCTORSMAY BE UNDERGROUND AND ENERGIZEDLABEL 4WARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE AND LOADSIDES MAY BE ENERGIZED IN THE OPENPOSITIONLABEL 5WARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE AND LOADSIDES MAY BE ENERGIZED IN THE OPENPOSITIONDC VOLTAGE IS ALWAYS PRESENTWHEN SOLAR MODULESARE EXPOSED TO SUNLIGHTLABEL 6WARNINGLABEL 7TURN OF PHOTOVOLTAICAC DISCONNECT PRIOR TOWORKING INSIDE PANELDO NOT DISCONNECTUNDER LOADLABEL 8MAIN PV SYSTEMDISCONNECTLABEL 9MAIN PV SYSTEMAC DISCONNECTLABEL 10LABEL 11CAUTIONLABEL 12SOLAR ELECTRIC SYSTEMCONNECTEDWARNING-LABEL 13 DUAL POWER SOURCESECOND SOURCE IS PV SYSTEMCAUTIONLABEL 14PHOTOVOLTAIC SYSTEM CIRCUITIS BACKFEDLABEL 15PHOTOVOLTAIC AC DISCONNECTMAXIMUM AC OPERATING CURRENTMAXIMUM AC OPERATING CURRENTPHOTOVOLTAICLABEL 16UTILITY AC DISCONNECTPHOTOVOLTAICLABEL 17DC DISCONNECTNOMINAL OPERATING AC VOLTAGENOMINAL OPERATING AC FREQUANCYMAXIMUM AC POWERMAXIMUM AC CURRENTMAX OCERCURRENT DEVICE RATINGFOR AC MODULE PROTECTIONLABEL 18LABEL 19PV SYSTEM DC DISCONNECTOPERATING CURRENTOPERATING VOLTAGEMAXIMUM SYSTEM VOLTAGESHORT CIRCUIT CURRENTRATED MAX POWER-FONT CURRENTRATED MAX POWER-FONT VOLTAGEMAXIMUM SYSTEM VOLTAGESHORT CIRCUIT CURRENTMAX RATED OUTPUT CURRENT OFTHE CHARGE CONTROLLER IF INSTALLEDLABEL 20***ALL LABELS = RED THERMOPLASTIC/REFLECTIVE , Permanently mounted240VSOLAR DISCONNECT20SOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNTURN RAPID SHUTDOWNSWITCH TO THE"OFF" POSITION TOSHUT DOWN PV SYSTEMAND REDUCESHOCK HAZARDIN THE ARRAYSOLAR ELECTRICPV PANELS48 A PLACARDPV 3.2PV SYSTEMAS INDICATEDScale:Project:CAUTIONPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:SERVICE 1 OF 2CAUTIONPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:SERVICE 2 OF 2NWESNWES19808 Iberis AveSt. Paul, MN 5504419808 Iberis AveSt. Paul, MN 55044Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023PV SUB PANELPV MONITORING SYSTEMSERVICE POINT &UTILITY METERINGPV SYSTEM DISCONNECTFOR UTILITY OPERATIONSOLAR PV ARRAYPV SUB PANELPV MONITORING SYSTEMSERVICE POINT &UTILITY METERINGPV SYSTEM DISCONNECTFOR UTILITY OPERATIONSOLAR PV ARRAY PROPERTY PLANPV 4.0PV SYSTEMAS INDICATEDScale:Project:.....................MSPMain Service PanelINDEXAC..................................Utility ACPVSPV Sub Panel ......................Main MeterMM..............................Solar Module...............Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTXcel Energy Application #05573890Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023PVS6PV Monitoring System............DrivewayPVS6PVSACMMMSPIberis Ave PROPERTY LINE220'-5"169'-4"134'-3"23'-4"32'-2"45'-7"SCALE:1/32" = 1'-0" 180° 90° 270°0°SWNEDate Certified andExp. Date : 06/30/2024Signed: 09/13/2023Engineerinc.io,303 N Glenoaks BlvdBurbank, CA 91502(310) 928-0938 ATTACHMENTLAYOUTPV 5.0PV SYSTEMAS INDICATEDScale:Project:DESIGN CRITERIAModules:Max Distributed Load: 3 PSFPOINT LOAD CALCULATION PER ARRAYModule Weight (lbs)# Of Modules48.5Total Module Weight (lbs)Rack Weight (lbs)MicroInverters Weight (lbs)Total System Weight (lbs)# Of StandoffsMax Span Between Standoffs (in)Loading Per Standoff (lbs)Total Area (sq.ft.)Loading (PSF)145529171.41817.4604830.296602.75RAIL ATTACHMENTTRUSS: 2 X 4 @ 24" O.C.30301 Layer of .Plywood & Building FeltSolar Module6"AttachmentROOF SECTION DETAILTRUSS: 2 X 4 @ 24" O.C.COMP. SHINGLEPrior to the commencement of work, thecontractor shall verify the existing roof andframing conditions. Notify New@engineerinc.ioof any Discrepancies prior to startingconstruction. Prior to the commencement ofwork, the contractor shall inspect framing forany damage such as water damage, crackedframing, etc. and These Plans are stamped forstructural code compliance of the roof framingsupporting the proposed PV installationreference only. These plans are not stampedfor water leakage. PV modules, racking, andattachment components must followmanufacturer guidelines and requirements.Attachments to be installed in a staggeredorientation to properly distribute loads.Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTDrawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023LightSpeed FlashingSupport BlockEPDM WASHERROOF ASSEMBLYPEGASUS COMP SHINGLE DETAILS17'-2"13'Date Certified andExp. Date : 06/30/2024Signed: 09/13/2023Engineerinc.io,303 N Glenoaks BlvdBurbank, CA 91502(310) 928-0938 PV 6.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023MONITORINGDATA SHEET INVERTERDATA SHEETD 7.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023 RSDDATA SHEETD 8.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023 MODULEDATA SHEETD 9.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023 RACKINGDATA SHEETD 10.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023 ATTACHMENTDATA SHEETD 11.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023 D 12.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023SURGEPROTECTION D 13.0PV SYSTEMAS INDICATEDScale:Project:INVERTERCERTIFICATIONDrawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023 PV INSPECTIONCHECKLISTD 14.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023Wolf RIver ElectricSt. Paul, MN 5504419808 Iberis Ave WITNESS TEST PROCEDUREA TEST PROCEDURE THAT WILL BE USED TO VERIFY THE PROTECTION AND OPERATION OF THE SYSTEMSHALL BE SUBMITTED TO XCEL ENERGY FOR APPROVAL. THE PROCEDURE INCLUDES AN ANTI-ISLANDINGTEST(FOR ALL SYSTEMS) TO VERIFY THE SYSTEM CEASES GENERATING IN PARALLEL WITH THE XCELENERGY DISTRIBUTION SYSTEM WHEN THE UTILITY SOURCE IS LOST. EACH SYSTEM IS UNIQUE AND WILLREQUIRE A CUSTOM TEST PROCEDURE BASED ON THE INVERTER MANUFACTURER'S RECOMENDATIONS FORCOMISSIONIND AND ANTI-ISLANDING. IN ADDITION TO THE MANUFACTURER'S RECOMENDATIONS.ALL TESTING SHALL BE PERFORMED BY QUALIFIED PERSONELL ONLYALL TESTING SHALL BE PERFORMED BY QUALIFIED PERSONELL ONLY1. SITE SECURITY- SITE SHOULD HAVE 24/7 KEYLESS ENTRY AND DRIVABLE ACCESS IF XCEL EQUIPMENT IS PRESENT WITHIN THE SITE FENCE- IF APPLICABLE, SITE SHOULD HAVE 24/7 DRIVABLE ACCESS TO ANY XCEL EQUIPMENT INSTALLED OUTSIDE OF THE SITEFENCE THAT IS USED FOR THE SOLE PURPOSE OF FEEDING THE PV SYSTEM2. PROPER LABELLING'VERIFY LABELING FOR THE MAIN SERVICE PANEL, PV SYSTEM CIRCUIT BREAKER, DC DISCONNECT (WHENAPPLICABLE), UTILITY AC DISCONNECT, PRODUCTION METER AND OTHER RELEVANT LABELLING AND SIGNAGE.3. ENERGIZE THE PV SYSTEM BY CLOSING THE UTILITY DISCONNECT. PLEASE ALLOW 5-MINUTE FOR THE INVERTER TO BOOT-UP.4. WHILE IN NORMAL OPERATION, REFER TO THE REFERENCE POINT OF APPLICABILITY TO VERIFY THE VOLTAGES ATTHE INVERTER AC OUTPUT ARE WITHIN 5% OF THE COMBINED INVERTED AC VOLTAGE RATINGS AND ALL INVERTERLED’S, ALARMS, AND/OR LCD CODES ARE “NORMAL.”5. WHILE IN NORMAL OPERATION, VERIFY THAT ALL INVERTERS ARE OPERATIONAL AND PRODUCING POWER. VERIFYTHAT SYSTEM IS GENERATING AT FULLEST REASONABLE CAPACITY. WHILE IN NORMAL OPERATION VERIFY THEVOLTAGES AT THE DER AC TERMINALS ARE WITHIN 5% OF THE COMBINED DER AC VOLTAGE RATINGS AND ALL LEDs,ALARMS AND/OR LCD CODES ARE "NORMAL"6. SIMULATE THE LOSS OF UTILITY SOURCE FOR THE ANTI-ISLANDING TEST BY OPENING THE "UTILILITY AC DISCONNECT".7. USING A VOLTMETER, VERIFY THE VOLTAGE AT THE INVERTER SIDE OF THE AC DISCONNECT HAS DROPPED TO ZERONOTE: ONLY CUSTOMER-OWNED EQUIPMENT SHALL BE USED FOR THIS VERIFICATION.8. USING AN AMMETER OR THE INVERTER’S DISPLAY, VERIFY THE DER OUTPUT OF THEINVERTER HAS CEASED WITHIN TWO SECONDS.9. VERIFY INVERTER LED’S, ALARMS, AND/OR LCD CODES ARE APPROPRIATE FOR LOSS OF UTILITY SOURCE10. RESTORE THE LOST UTILITY SOURCE BY CLOSING THE "UTILITY AC DISCONNECT"11. VERIFY THAT THE INVERTER SYSTEM DELAYS 5 MINUTES BEFORE RESUMING POWER OUTPUT AFTER THE UTILITYSOURCE IS RESTORED12. VERIFY FIXED POWER FACTOR SETTINGS FOR EACH INVERTER MEET THE PROJECT REQUIREMENTS13. METER TECH HAS VERIFIED METERING EQUIPMENT14. SYSTEM RESUMED DELIVERY OF POWER NO LESS THAN 5 MINUTES AFTER UTILITY SOURCE IS RESTOREDMichael Mantich19808 Iberis AveSt. Paul, MN 55044UTILITY: XCEL ENERGYPHOTOVOLTAIC PROJECT INFOPV MODULE: ( ) SUNPOWER 400 WINVERTER:1-PHASE 120/240( ) IQ7HS MICROINVERTERS12.00 Kw (DC)ARRAY1 AZIMUT: 90 (19)ARRAY TILT: 27, 33NEC 2020/ IRC 2018/ IBC 2018WOLF RIVER ELECTRIC COMPANY101 ISANTI PARKWAY NE #GISANTI, MN 55040CONTACT@WOLFRIVERELECTRIC.COMWOLFRIVERELECTRIC.COMMichael MantichWOLF RIVER SOLAR24/7 UNESCORTED ACCESS SHALL BEPROVIDED FOR THE METERS & ACDISCONNECTMETERS & UTILITY DISCONNECT WITHIN10' & LINE OF SIGHTUTILITY AC DISCONNECT IS VISIBLELOCKABLE & READILY ACCESSIBLEGROUND SNOW: 50PSFWIND SPEED: 115MPHEXPOSURE CATEGORY: BPV ARRAY: 2.75 PSFPRODUCTS:RAILS: INVISIMOUNTMOUNTS: PEGASUSROOF-MOUNTXcel Energy Application #05573890WITNESS TESTPROCEDURED 15.0PV SYSTEMAS INDICATEDScale:Project:3030Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023ARRAY2 AZIMUT: 180 (2)ARRAY3 AZIMUT: 270 (9) D 16.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.com19808 Iberis AveSt. Paul, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Michael Mantich08/30/2023REVISION DATE:REVISION DATE:09/13/2023NSIDATASHEET