HomeMy WebLinkAboutLA217901 - APPROVED - BENNETT WADEKAMPER - Plans and specsDISTANCE TO NEAREST CROSS STREET FROM ADDRESS UPPER 206TH STREET WEST PROJECT INFORMATION CONTRACTOR NAME ALL ENERGY SOLAR CONTRACTOR PHONE (800) 620-3370 GENERAL NOTES 1 EQUIPMENT LIKELY TO BE WORKED UPON WHILE ENERGIZED SHALL BE INSTALLED IN LOCATIONS THAT SATISFY MIN. WORKING CLEARANCES PER NEC 110.26. 2 24/7 UNESCORTED KEYLESS ACCESS SHALL BE PROVIDED TO ALL XCEL ENERGY EQUIPMENT. 3 CONTRACTOR SHALL USE ONLY COMPONENTS LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY FOR THE INTENDED USE. 4 CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL EQUIPMENT, CABLES, ADDITIONAL CONDUITS, RACEWAYS, AND OTHER ACCESSORIES NECESSARY FOR A COMPLETE AND OPERATIONAL PV SYSTEM. 5 ALL EXPOSED PV ROOFTOP CONDUCTORS NOT UNDER THE ARRAY SHALL BE PROTECTED BY A RACEWAY WITH A LISTED JUNCTION BOX AT BOTH ENDS AND COMPLY WITH NEC 690.31(A). 6 ALL EMT CONDUIT FITTINGS SHALL BE LISTED AS WEATHERPROOF FITTINGS AND INSTALLED TO ENSURE A RAINTIGHT FIT, PER NEC 358.42. 7 SITE SHALL MEET NESC CLEARANCE REQUIREMENTS (E) MAIN SERVICE PANEL (MSP), INDOOR (N) PV SERVICE DISCONNECT (SW2), OUTDOOR (E) UTILITY METER, OUTDOOR (N) READILY ACCESSIBLE PRODUCTION METER LOCATED WITHIN 10 FT OF UTILITY METER (M2), OUTDOOR (N) AC COMBINER (C1), OUTDOOR (N) VISIBLE-OPEN TYPE, LOCKABLE, READILY ACCESSIBLE, LABELED UTILITY PV DISCONNECT LOCATED WITHIN 10 FT OF UTILITY METER (SW1), OUTDOOR (N) PROPOSED ROOF-MOUNTED PV ARRAY. 6/12 (26.6°) SLOPED ROOF, (13) REC SOLAR REC420AA PURE-R MODULES (BLACK FRAME, BLACK BACKSHEET), 198° AZIMUTH (N) TRANSITION BOX, OUTDOOR, OUTPUT CIRCUIT CONDUCTORS SHALL BE RUN IN EMT CONDUIT THROUGH THE INTERIOR OF THE BUILDING ALL ARRAY CIRCUITS SHALL BE ROUTED THROUGH THE INTERIOR OF THE BUILDING, AND WHERE POSSIBLE, ALONG THE BOTTOM OF LOAD BEARING MEMBERS. NO CONDUIT SHALL BE INSTALLED ABOVE THE ROOF. 77207 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 GRID-TIED PV SYSTEMSITE PLAN DOC ID:F06E22-1 DATE:8/21/23 CREATOR:A.K. REVIEWER:B.W. REVISIONS PV-2BENNETT M WADEKAMPER 9892 UPPER 205TH ST W LAKEVILLE, MN 55044-8845ACCOUNT: 51-0848663-7PREMISE: 302616786 METER: 99229179CASE NUMBER: 05539639Concept Approval ONLY Subject to Field Inspection Inspector Date 2015 MN Bldg Code 09/13/2023jnuetzman PV MODULE MICROINVERTER PM1-13 420W 7 IN BRANCH 6 IN BRANCH 21 1 2 3 4 5 6 7 JUNCTION BOX JB1 43 AC COMBINER COMM GATEWAY C1CB2 15A CB1 15A 5 8 9 PoCRPAPoCRPA UTILITY PV DISCONNECT 6 SW1 30A GENERATION METER KWHR LINE LOAD KWHR LINE LOAD 7 (UTILITY-OWNED) 10 NN PV SERVICE DISCONNECT EATON DG222NRB SW2 60A 8 F1-2 30A 11 12 (E) ACGEC LOADS KWHR LOAD LINE KWHR LOAD LINE UTILITY METER (100A MSP W/100A MCB) 120/240V 1ɸ, 3W S/N: 99229179 13 MODULES REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING PM1-13 13 REC SOLAR REC420AA PURE-R 420W 402W 8.89A 8.40A 59.4V 50.0V -0.1408V/°C (-0.24%/°C)25A INVERTERS REF.QTY .MAKE AND MODEL AC VOLTAGE GROUND RATED POWER MAX OUTPUT CURRENT MAX INPUT CURRENT MAX INPUT VOLTAGE CEC WEIGHTED EFFICIENCY I1-13 13 ENPHASE IQ7X-96-2-US 240V NOT SOLIDLY GROUNDED 315W 1.31A 10.0A 80V 97.5% DISCONNECTS REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE SW1 1 EATON DG221URB OR EQUIV.30A 240VAC SW2 1 EATON DG222NRB OR EQUIV.60A 240VAC OCPDS REF.QTY.RATED CURRENT MAX VOLTAGE CB1 1 15A 240VAC CB2 1 15A 240VAC F1-2 2 30A 240VAC PASS-THRU BOXES AND COMBINERS REF.QTY .MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE JB1 1 SOLADECK 0799-5 WITH 01611 KIT OR EQUIV.30A 240VAC / 600VDC C1 1 ENPHASE IQ COMBINER 4 W/ IQ GATEWAY FOR PRODUCTION MONITORING 64A 240VAC SYSTEM SUMMARY BRANCH 1 BRANCH 2 INVERTERS PER BRANCH 7 6 MAX AC CURRENT 9.17A 7.86A MAX AC OUTPUT 2,205W 1,890W ARRAY STC POWER 5,460W ARRAY PTC POWER 5,232W MAX AC CURRENT 17.03A MAX AC POWER OUTPUT 4,095W DERATED AC POWER OUTPUT 4,095W RAPID SHUTDOWN DEVICES COMPLIANT WITH REQUIREMENTS AS PER NEC 690.12(B)(2). PV CIRCUIT CONDUCTORS LOCATED OUTSIDE THE ARRAY BOUNDARY (DEFINED AS 3 FEET FROM THE POINT OF PENETRATION INTO A BUILDING OR MORE THAN 3 FEET FROM AN ARRAY) SHALL BE LIMITED TO NOT MORE THAN 30V WITHIN 30 SECONDS OF RAPID SHUTDOWN INITIATION. CONDUCTORS LOCATED INSIDE OF THE ARRAY BOUNDARY SHALL BE LIMITED TO NOT MORE THAN 80 VOLTS WITHIN 30 SECONDS OF SHUTDOWN. 1 ENPHASE SYSTEM MEETS REQUIREMENTS FOR PV HAZARD CONTROL SYSTEM (PVHCS), AS PER NEC 690.12(B)(2).2 THE DC AND AC CONNECTORS OF THE ENPHASE IQ7X-96-2-US AND ARE LISTED TO MEET REQUIREMENTS AS A DISCONNECT MEANS AS ALLOWED BY NEC 690.15(C). MATING CONNECTORS SHALL COMPLY WITH NEC 690.33.3 THE ENPHASE IQ7X-96-2-US HAS A CLASS II DOUBLE-INSULATED RATING AND DOES NOT REQUIRE GROUNDING ELECTRODE CONDUCTORS (GEC) OR EQUIPMENT GROUNDING CONDUCTORS (EGC). THE RATING INCLUDES GROUND FAULT PROTECTION (GFP). TO SUPPORT GFP, USE ONLY PV MODULES EQUIPPED WITH DC CABLES LABELED PV WIRE OR PV CABLE.4 MICROINVERTER BRANCH CIRCUIT CONDUCTORS ARE MANUFACTURED ENPHASE Q CABLES LISTED FOR USE IN 20A OR LESS CIRCUITS OF ENPHASE IQ MICROINVERTERS. THEY ARE ROHS, OIL RESISTANT, AND UV RESISTANT. THEY CONTAIN TWO 12 AWG CONDUCTORS OF TYPE THHN/THWN-2 DRY/WET AND CERTIFIED TO UL 3003 AND UL 9703.5 ALL METAL ENCLOSURES, RACEWAYS, CABLES AND EXPOSED NONCURRENT-CARRYING METAL PARTS OF EQUIPMENT SHALL BE GROUNDED TO EARTH AS REQUIRED BY NEC 250.4(B) AND PART III OF ARTICLE 250 AND DC EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 690.45. THE GROUNDING ELECTRODE SYSTEM SHALL ADHERE TO NEC 690.47(A) AND NEC 250.169 AND INSTALLED IN COMPLIANCE WITH NEC 250.64. 6 MAX DC VOLTAGE OF PV MODULE IS EXPECTED TO BE 67.0V AT -29°C (-28.9°C - 25°C) X -0.141V/C + 59.4V = 67.0V).7 AC AGGREGATION PANEL BUSBAR AND THE OVERCURRENT PROTECTION PROTECTING THE BUSBAR SHALL BE SIZED IN ACCORDANCE WITH NEC 705.12(B)(3).8 THE ENPHASE IQ COMBINER 4 CONTAINS A FACTORY-INSTALLED COMMUNICATIONS GATEWAY WITH AN OCPD RATED NO MORE THAN 20A.9 200A RINGLESS METER SOCKET WITH LEVER SAFETY BYPASS PER XCEL ENERGY SPECIFICATIONS.10 UTILITY PV DISCONNECT SHALL BE A VISIBLE KNIFE-BLADE TYPE DISCONNECT THAT IS ACCESSIBLE AND LOCKABLE BY THE UTILITY IN ACCORDANCE WITH NEC 690.13(E). THE DISCONNECT SHALL BE LOCATED WITHIN 10 FT OF UTILITY METER AND INSTALLED IN COMPLIANCE WITH NEC 705.20 AND GROUPED AS REQUIRED BY NEC 230.72.11 12 UTILITY PV DISCONNECT MEETS NEC 690.12(C) REQUIREMENT FOR A RAPID SHUTDOWN INITIATION DEVICE POINT-OF-CONNECTION IS ON THE SUPPLY SIDE OF SERVICE DISCONNECT, INSIDE PANELBOARD ENCLOSURE USING UNUSED TERMINALS, TERMINALS THAT ARE SUITABLE FOR DOUBLE LUGGING, OR USING OTHER LOCALLY-APPROVED METHODS AND HARDWARE, IN COMPLIANCE WITH NEC 705.11(A). THE PANELBOARD SHALL HAVE SUFFICIENT SPACE TO ALLOW FOR ANY TAP HARDWARE AS REQUIRED BY NEC 110.3 AND NEC 312.8(A) 13 ALL AC EQUIPMENT SHALL BE 3-WIRE, SINGLE-PHASE 120/240 V.14 CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS ID TYP CONDUCTOR CONDUIT / CABLE CURRENT-CARRYING CONDUCTORS IN CONDUIT/CABLE. OCPD EGC TEMP. CORR. FACTOR FILL FACTOR CONT. CURRENT MAX. CURRENT (125%) BASE AMP.DERATED AMP. TERM. TEMP. RATING AMP. @ TERM. TEMP. RATING LEN. V.D. 1 1 10 AWG THHN/THWN-2 IN ENPHASE Q CABLE, COPPER CABLE 2 15A 10 AWG BARE, COPPER 0.76 (54°C)1.0 9.17A 11.46A 30A 23A 90°C 30A 45.9FT 0.69% 2 1 10 AWG THHN/THWN-2 IN ENPHASE Q CABLE, COPPER CABLE 2 15A 10 AWG BARE, COPPER 0.76 (54°C)1.0 7.86A 9.82A 30A 23A 90°C 30A 39.4FT 0.51% 3 1 10 AWG THWN-2, COPPER 0.75" DIA. EMT 4 15A 10 AWG THWN-2, COPPER 0.76 (52°C)0.8 9.17A 11.46A 40A 24.32A 90°C 40A 73.4FT 0.7% 4 1 10 AWG THWN-2, COPPER 0.75" DIA. EMT 4 15A 10 AWG THWN-2, COPPER 0.76 (52°C)0.8 7.86A 9.82A 40A 24.32A 90°C 40A 73.4FT 0.6% 5 1 10 AWG THWN-2, COPPER 0.75" DIA. EMT 2 30A 10 AWG THWN-2, COPPER 0.96 (32°C)1.0 17.03A 21.29A 40A 38.4A 75°C 35A 48IN 0.07% 6 1 6 AWG THWN-2, COPPER 0.75" DIA. EMT 2 30A 10 AWG THWN-2, COPPER 0.96 (32°C)1.0 17.03A 21.29A 75A 72A 75°C 65A 48IN 0.03% 7 1 6 AWG THWN-2, COPPER 0.75" DIA. EMT 2 30A 10 AWG THWN-2, COPPER 0.96 (32°C)1.0 17.03A 21.29A 75A 72A 75°C 65A 48IN 0.03% 8 1 6 AWG THWN-2, COPPER 1.0" DIA. PVC-80 2 30A N/A 0.96 (32°C)1.0 17.03A 21.29A 75A 72A 75°C 65A 48IN 0.03% REVISIONS PROJECT ID: CREATED BY: CHECKED BY: DATE: SCALE:GRID-TIED PV SYSTEMPV-3 77207 8/21/23 B.W. A.K. F06E22-1 SINGLE-LINE DIAGRAM 1 PV-3 SINGLE-LINE DIAGRAM NTS 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 GROUNDING NOTES 1 ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE REQUIREMENTS OF NEC ARTICLES 250 & 690 2 PV MODULES SHALL BE GROUNDED TO MOUNTING RAILS USING MODULE LUGS OR RACKING INTEGRATED GROUNDING CLAMPS AS ALLOWED BY LOCAL JURISDICTION. ALL OTHER EXPOSED METAL PARTS SHALL BE GROUNDED USING UL-LISTED LAY-IN LUGS. 3 INSTALLER SHALL CONFIRM THAT MOUNTING SYSTEM HAS BEEN EVALUATED FOR COMPLIANCE WITH UL 2703 "GROUNDING AND BONDING" WHEN USED WITH PROPOSED PV MODULE. 4 IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE A VERIFIABLE GROUNDING ELECTRODE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE. 5 AC SYSTEM GROUNDING ELECTRODE CONDUCTOR (GEC) SHALL BE A MINIMUM SIZE #8AWG WHEN INSULATED, #6AWG IF BARE WIRE. 6 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC ARTICLE 690.45, AND BE A MINIMUM OF #10AWG WHEN NOT EXPOSED TO DAMAGE, AND #6AWG SHALL BE USED WHEN EXPOSED TO DAMAGE 7 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLOR CODED GREEN, OR MARKED GREEN IF #4AWG OR LARGER GENERAL ELECTRICAL NOTES 1 UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE SERVICE ENTRANCE. 2 CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER NEC ARTICLE 300.6 (C) (1) AND ARTICLE 310.10 (D). 3 CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C).BENNETT M WADEKAMPER 9892 UPPER 205TH ST W LAKEVILLE, MN 55044-8845ACCOUNT: 51-0848663-7PREMISE: 302616786 METER: 99229179CASE NUMBER: 05539639 EATON DG222URB PV MODULEMICROINVERTERPM1-13420W7 INBRANCH6 INBRANCH211234567JUNCTION BOXJB143AC COMBINERCOMMGATEWAYC1CB215ACB115A589PoCPoCRPARPA6SW130AKWHRKWHRLINELINELOADLOADGENERATION METER (UTILITY-OWNED)10NN7PV SERVICE DISCONNECTEATON DG222NRBSW260A8F1-230A1112(E) AC GECLOADSKWHRKWHRLOADLOADLINELINEUTILITY METER(100A MSP W/100A MCB)120/240V 1ɸ, 3WS/N: 9922917913CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONSID TYP CONDUCTOR CONDUIT / CABLE CURRENT-CARRYINGCONDUCTORS INCONDUIT/CABLE.OCPD EGC TEMP. CORR.FACTOR FILL FACTOR CONT.CURRENT MAX.CURRENT(125%)BASE AMP.DERATEDAMP.TERM.TEMP.RATING AMP. @TERM.TEMP.RATING LEN. V.D.1 1 10 AWG THHN/THWN-2 IN ENPHASE Q CABLE, COPPER CABLE 2 15A 10 AWG BARE, COPPER 0.76 (54°C)1.0 9.17A 11.46A 30A 23A 90°C 30A 45.9FT 0.69% 2 1 10 AWG THHN/THWN-2 IN ENPHASE Q CABLE, COPPER CABLE 2 15A 10 AWG BARE, COPPER 0.76 (54°C)1.0 7.86A 9.82A 30A 23A 90°C 30A 39.4FT 0.51% 3 1 10 AWG THWN-2, COPPER 0.75" DIA. EMT 4 15A 10 AWG THWN-2, COPPER 0.76 (52°C)0.8 9.17A 11.46A 40A 24.32A 90°C 40A 73.4FT 0.7% 4 1 10 AWG THWN-2, COPPER 0.75" DIA. EMT 4 15A 10 AWG THWN-2, COPPER 0.76 (52°C)0.8 7.86A 9.82A 40A 24.32A 90°C 40A 73.4FT 0.6% 5 1 10 AWG THWN-2, COPPER 0.75" DIA. EMT 2 30A 10 AWG THWN-2, COPPER 0.96 (32°C)1.0 17.03A 21.29A 40A 38.4A 75°C 35A 48IN 0.07% 6 1 6 AWG THWN-2, COPPER 0.75" DIA. EMT 2 30A 10 AWG THWN-2, COPPER 0.96 (32°C)1.0 17.03A 21.29A 75A 72A 75°C 65A 48IN 0.03% 7 1 6 AWG THWN-2, COPPER 0.75" DIA. EMT 2 30A 10 AWG THWN-2, COPPER 0.96 (32°C)1.0 17.03A 21.29A 75A 72A 75°C 65A 48IN 0.03% 8 1 6 AWG THWN-2, COPPER 1.0" DIA. PVC-80 2 30A N/A 0.96 (32°C)1.0 17.03A 21.29A 75A 72A 75°C 65A 48IN 0.03%UTILITY PV DISCONNECTEATON DG222URB AC COMBINER SW1 - DISCONNECT (EATON DG221URB) SW2 - DISCONNECT (EATON DG222NRB) UTILITY METER MAIN SERVICE PANEL SEE NOTE NO. 4 (SW2, MSP) SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE 'OFF' POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY. NEC 690.12(D) AND IFC 1204.5.1 AC COMBINER PANEL (C1) ! WARNING ! EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE SHALL NOT EXCEED AMPACITY OF BUSBAR. NEC 705.12(B)(3) POINT-OF-INTERCONNECTION OR AT MAIN SERVICE DISCONNECT (MSP, UM) ! CAUTION: MULTIPLE SOURCES OF POWER ! POWER TO THIS BUILDING IS ALSO SUPPLIED FROM A ROOF-MOUNTED SOLAR ARRAY WITH SAFETY DISCONNECTS AS SHOWN 9892 UPPER 205TH ST W, LAKEVILLE • INSTALLED BY ALL ENERGY SOLAR • (800) 620-3370 NEC 690.56 AND NEC 705.10 EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT (SW1, SW2) ! WARNING ! ELECTRIC SHOCK HAZARD. TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. NEC 690.13(B) AC DISCONNECT (SW1, SW2) MAXIMUM AC OPERATING CURRENT: 17.0A MAXIMUM AC OPERATING VOLTAGE: 240V SEE NOTE NO. 5 (SW2) RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM NEC 690.12(D)(2) AND IFC 1204.5.3 EMERGENCY CONTACT DETAILS (SW2, MSP) IN CASE OF EMERGENCY CONTACT ALL ENERGY SOLAR (800) 620-3370 NEC 705.10 ANY AC ELECTRICAL PANEL THAT IS FED BY BOTH THE UTILITY AND THE PHOTOVOLTAIC SYSTEM (SW2, MSP) ! CAUTION ! MULTIPLE SOURCES OF POWER NEC 705.10 LABELING NOTES 1 ALL PLAQUES AND SIGNAGE REQUIRED BY 2023 NEC AND 2018 IFC WILL BE INSTALLED AS REQUIRED. 2 LABELS, WARNING(S) AND MARKING SHALL COMPLY WITH ANSI Z535.4, WHICH REQUIRES THAT DANGER, WARNING, AND CAUTION SIGNS USED THE STANDARD HEADER COLORS, HEADER TEXT, AND SAFETY ALERT SYMBOL ON EACH LABEL. THE ANSI STANDARD REQUIRES A HEADING THAT IS AT LEAST 50% TALLER THAN THE BODY TEXT, IN ACCORDANCE WITH NEC 110.21(B). 3 A PERMANENT PLAQUE OR DIRECTORY SHALL BE INSTALLED PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION IN ACCORDANCE WITH NEC 690.56. 4 LABEL(S) WITH MARKING, "TURN RAPID SHUTDOWN SWITCH TO THE 'OFF' POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY," SHALL BE LOCATED WITHIN 3 FT OF SERVICE DISCONNECTING MEANS. THE TITLE SHALL UTILIZE CAPITALIZED LETTERS WITH A MINIMUM HEIGHT OF 3/8″. ALL TEXT SHALL BE LEGIBLE AND CONTRAST THE BACKGROUND. . 5 LABEL(S) WITH MARKING, "RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM," SHALL BE LOCATED WITHIN 3 FT OF RAPID SHUTDOWN SWITCH THE LABEL SHALL HAVE 3/8″ TALL LETTERS AND BE REFLECTIVE WITH WHITE TEXT ON A RED BACKGROUND. 77207 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 GRID-TIED PV SYSTEMSAFETY LABELS DOC ID:F06E22-1 DATE:8/21/23 CREATOR:A.K. REVIEWER:B.W. REVISIONS PV-4BENNETT M WADEKAMPER 9892 UPPER 205TH ST W LAKEVILLE, MN 55044-8845ACCOUNT: 51-0848663-7PREMISE: 302616786 METER: 99229179CASE NUMBER: 05539639 UTILITY PV DISCONNECT (OUTDOOR) PV SERVICE DISCONNECT (OUTDOOR) STRUCTURAL DESIGN PARAMETERS ELEVATION 995 FT SEISMIC 0.051 SDS WIND (ASCE 7-16)109 MPH, EXPOSURE CATEGORY B, RISK CATEGORY II GROUND SNOW LOAD 50 PSF ROOF PROPERTIES ROOF MATERIAL COMPOSITION SHINGLE (1 LAYER) SLOPE 6/12 (26.6°) MEAN ROOF HEIGHT 13.6FT ROOF DECKING 15/32" OSB CONSTRUCTION TRUSSES (2X4 TOP-CHORD), 24IN OC MODULE MECHANICAL PROPERTIES MODEL REC SOLAR REC420AA PURE-R DIMENSIONS (AREA) 68.1IN X 44.0IN X 1.2IN (20.8 SQ FT) WEIGHT 47.4 LBS MOUNTING SYSTEM PROPERTIES RAIL MODEL SNAPNRACK UR-40 ANCHOR MODEL SNAPNRACK UR COMPOSITION FLASHED L-FOOT (FLASHED), 3.75IN AIR GAP FASTENING METHOD 2.5 INCH EMBEDMENT INTO TRUSSES WITH (1) 5/16IN DIA. FASTENER GROUNDING AND BONDING INTEGRAL GROUNDING CERTIFIED TO UL 2703 REQUIREMENTS DEAD LOAD CALCULATIONS LOAD QTY LBS TOTAL LBS MODULES 13 47.4 616.2 MICROINVERTERS 13 2.4 31.0 LINEAR FEET OF RAIL 99 FT 0.4 41.5 ANCHORS 29 2.4 68.9 MISC. HARDWARE 7.2 7.2 TOTAL ARRAY WEIGHT 764.7 LBS AREA NAME QTY SQFT TOTAL SQFT MODULES 13 20.8 270.4 POINT LOAD (764.7 LBS / 29 ATTACHMENTS) 26.4 LBS DIST. LOAD (764.7 LBS / 270.4 SQFT)2.83 PSF NOTES 1 TRUSS LOCATIONS ARE APPROXIMATE. CONTRACTOR MAY NEED TO MAKE MINOR ADJUSTMENTS TO ANCHOR LOCATIONS. IN NO CASE SHALL THE ANCHOR SPACING EXCEED "MAX. ANCHOR SPACING" ANCHOR PLACEMENT PARAMETERS (ASCE 7-16) WIND PRESSURE ZONE MODULE WIND EXPOSURE MAX. ALLOWABLE RAIL SPAN MAX. ANCHOR SPACING MAX. ALLOWABLE CANTILEVER ZONES 1, 2E, 2R NORMAL 48.0IN 48.0IN 16.3IN DISTANCE α IS EQUAL TO 10% OF THE BUILDING'S LEAST HORIZONTAL DIMENSION ("LHD") OR 40% OF THE MEAN ROOF HEIGHT, WHICHEVER IS SMALLER, BUT NOT LESS THAN 4% OF THE LHD OR 3 FT. THESE SETBACKS ARE APPLIED TO THE BUILDING FOOTPRINT AND PROJECTED TO THE ROOF PLANES IN ACCORDANCE WITH GUIDANCE PROVIDED BY ASCE 7-16 FIGURES 30.3-2B–I. α = MAX(MIN(0.4 * MEAN ROOF HEIGHT, 0.1 * LHD), 0.04 * LHD, 3 FT) 3.0 FT = MAX(MIN(0.4 * 13.6 FT, 0.1 * 27.1 FT), 0.04 * 27.1 FT, 3 FT) 77207 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 GRID-TIED PV SYSTEMATTACHMENT PLAN DOC ID:F06E22-1 DATE:8/21/23 CREATOR:A.K. REVIEWER:B.W. REVISIONS PV-5BENNETT M WADEKAMPER 9892 UPPER 205TH ST W LAKEVILLE, MN 55044-8845ACCOUNT: 51-0848663-7PREMISE: 302616786 METER: 99229179CASE NUMBER: 05539639 18" 24' 77207 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 GRID-TIED PV SYSTEMATTACHMENT DETAILS DOC ID:F06E22-1 DATE:8/21/23 CREATOR:A.K. REVIEWER:B.W. REVISIONS PV-6BENNETT M WADEKAMPER 9892 UPPER 205TH ST W LAKEVILLE, MN 55044-8845ACCOUNT: 51-0848663-7PREMISE: 302616786 METER: 99229179CASE NUMBER: 05539639 GENERAL NOTES 1 AT LEAST TWO 3′-WIDE PATHWAYS ON SEPARATE ROOF PLANES, FROM LOWEST ROOF EDGE TO RIDGE, SHALL BE PROVIDED ON ALL BUILDINGS, WITH AT LEAST ONE PATHWAY ON THE STREET OR DRIVEWAY SIDE OF THE ROOF. FOR EACH ROOF PLANE WITH A PV ARRAY, AT LEAST ONE SUCH PATHWAY FROM LOWEST ROOF EDGE TO RIDGE SHALL BE PROVIDED ON THE SAME ROOF PLANE, OR ON AN ADJACENT ROOF PLANE, OR STRADDLING THE SAME AND ADJACENT ROOF PLANES. (IFC 1204.2.1.1) 2 FOR PV ARRAYS OCCUPYING 33% OR LESS OF THE PLAN VIEW TOTAL ROOF AREA, A MIN. 18″-WIDE SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. (IFC 1204.2.1.2) 3 PV MODULES SHALL NOT BE PLACED BELOW AN EMERGENCY ESCAPE/RESCUE OPENING. A 3′-WIDE PATHWAY SHALL BE PROVIDED TO SUCH AN OPENING. (IFC 1204.2.2) 4 ROOF FACES WITH NO PV ARE DESIGNATED FOR FIRE VENTILATION AND ACCESS 1.5′ WIDE SMOKE-VENTILATION SETBACK, PER IFC 1204.2.1.2 3.0′ WIDE FIRE ACCESS PATHWAY, PER IFC 1204.2.1.1 PV MODULES INSTALLED ON ROOF WITH SNAPNRACK ULTRA RAIL MOUNTING SYSTEM. THE MOUNTING SYSTEM IS UL 2703 CLASS A FIRE RATED ON THIS STEEP-SLOPED ROOF WHEN INSTALLED WITH TYPE 1 OR 2 MODULES. THE REC SOLAR REC420AA PURE-R IS UL 61730-1 CERTIFIED TYPE 2. ROOF ACCESS POINT BUILDING IS 1-STORY, GROUP R3 TOTAL PLAN VIEW ARRAY AREA IS 242.1 SQ.FT, WHICH REPRESENTS 13.8% OF TOTAL PLAN VIEW ROOF AREA (1754.4 SQ.FT) THIS SYSTEM UTILIZES MICROINVERTERS. THERE ARE NO DC CIRCUITS OUTSIDE OF THE ARRAY PERIMETER OR INSIDE THE BUILDING. ALL ARRAY CIRCUITS SHALL BE ROUTED THROUGH THE INTERIOR OF THE BUILDING, AND WHERE POSSIBLE, ALONG THE BOTTOM OF LOAD BEARING MEMBERS. NO CONDUIT SHALL BE INSTALLED ABOVE THE ROOF. 77207 1264 ENERGY LANE ST PAUL, MN 55108 (800) 620-3370 GRID-TIED PV SYSTEMFIRE SAFETY PLAN DOC ID:F06E22-1 DATE:8/21/23 CREATOR:A.K. REVIEWER:B.W. REVISIONS PV-7BENNETT M WADEKAMPER 9892 UPPER 205TH ST W LAKEVILLE, MN 55044-8845ACCOUNT: 51-0848663-7PREMISE: 302616786 METER: 99229179CASE NUMBER: 05539639 COMPACT PANEL Size9 A module Current compatible with MLPErec Alpha Pure-R SERIESProduct Specificationsα experienceperformancewp43020.7w ft2ELIGIBLELEAD-FREErohs cOMPLIANT22.3%Efficiency Ref: PM-DS-12-06-Rev- B 08.22www.recgroup.comGENERAL DATACell type:80 half-cut REC bifacial, heterojunction cells with lead-free, gapless technologyGlass:0.13 in (3.2 mm) solar glass with anti-reflective surface treatment in accordance with EN 12150Backsheet:Highly resistant polymer (black)Frame:Anodized aluminum (black)Junction box:4-part, 4 bypass diodes, lead-free IP68 rated, in accordance with IEC 62790 Connectors:Stäubli MC4 PV-KBT4/KST4 (4 mm²) in accordance with IEC 62852, IP68 only when connectedCable:12 AWG (4 mm²) PV wire, 67 + 67 in (1.7 + 1.7 m) in accordance with EN 50618Dimensions:68.1 x 44.0 x 1.2 in (20.77 ft2) / 1730 x 1118 x 30 mm (1.93 m2)Weight:47.4 lbs (21.5 kg)Origin:Made in SingaporeSpecifications subject to change without notice.Measurements in inches [mm]LOW LIGHT BEHAVIOURTypical low irradiance performance of module at STC:WARRANTYStandardREC ProTrustInstalled by an REC Certified Solar ProfessionalNoYesYesSystem Size All≤25 kW25-500 kWProduct Warranty (yrs)202525Power Warranty (yrs)252525Labor Warranty (yrs)02510Power in Year 198%98%98%Annual Degradation0.25%0.25%0.25%Power in Year 2592%92%92%See warranty documents for details. Conditions apply Irradiance (W/m²)Rel. Efficiency (%)TEMPERATURE RATINGS*Nominal Module Operating Temperature:44°C (±2°C)Temperature coefficient of PMAX:-0.26 %/°CTemperature coefficient of VOC:-0.24 %/°CTemperature coefficient of ISC:0.04 %/°C*The temperature coefficients stated are linear valuesCERTIFICATIONSIEC 61215:2016, IEC 61730:2016, UL 61730IEC 62804PIDIEC 61701 Salt MistIEC 62716Ammonia ResistanceUL 61730Fire Type Class 2IEC 62782 Dynamic Mechanical LoadIEC 61215-2:2016Hailstone (35mm)IEC 62321Lead-free acc. to RoHS EU 863/2015ISO 14001, ISO 9001, IEC 45001, IEC 62941MAXIMUM RATINGSOperational temperature:-40 ... +85°CSystem voltage:1000 VTest load (front): + 7000 Pa (146 lbs/ft2)*Test load (rear):- 4000 Pa (83.5 lbs/ft2)*Series fuse rating:25 AReverse current:25 A* See installation manual for mounting instructions. Design load = Test load / 1.5 (safety factor) STC NMOTFounded in 1996, REC Group is an international pioneering solar energy company dedicated to empowering consumers with clean, affordable solar power. As Solar’s Most Trusted, REC is committed to high quality, innovation, and a low carbon footprint in the solar materials and solar panels it manufactures. Headquartered in Norway with operational headquarters in Singapore, REC also has regional hubs in North America, Europe, and Asia-Pacific.8590951001052001003004005006007008009001000Lead-FreeELECTRICAL DATAProduct Code*: RECxxxAA PURE-RPower Output - PMAX (Wp) 400410420430Watt Class Sorting - (W)0/+100/+100/+100/+10Nominal Power Voltage - VMPP (V) 48.849.450.050.5Nominal Power Current - IMPP (A) 8.208.308.408.52Open Circuit Voltage - VOC (V) 58.959.259.459.7Short Circuit Current - ISC (A) 8.738.818.898.97Power Density (W/ft2)19.2619.7420.2220.7Panel Efficiency (%) 20.721.221.822.3Power Output - PMAX (Wp)305312320327Nominal Power Voltage - VMPP (V) 46.046.647.147.6Nominal Power Current - IMPP (A) 6.646.706.786.88Open Circuit Voltage - VOC (V) 55.555.856.056.3Short Circuit Current - ISC (A) 7.057.127.187.24Values at standard test conditions (STC: air mass AM 1.5, irradiance 10.75 W/sq ft (1000 W/m²), temperature 77°F (25°C), based on a production spread with a tolerance of PMAX, VOC & ISC ±3% within one watt class. Nominal module operating temperature (NMOT: air mass AM 1.5, irradiance 800 W/m², temperature 68°F (20°C), windspeed 3.3 ft/s (1 m/s). * Where xxx indicates the nominal power class (PMAX) at STC above.GR GRGR GRGR11±0.2[0.43±0.01]6.6±0.2 [0.26±0.01]20.5±0.5[0.8±0.02]6.0±0.2[0.24±0.01]1700 [67]1700 [67]Lorem ipsum1730±2.5 [68.1±0.1]880 [34.6]425 [16.7]1077±2.5 [42.4±0.1]22.5 [0.9] 594±3 [23.4±0.12] 1118±2.5 [44.0±0.1]17 [0.7]45 [1.8] 30 [1.2]DELIVERY INFORMATIONPanels per pallet:33Panels per 40 ft GP/high cube container:858 (26 pallets)Panels per 53 ft truck:858 (26 pallets)REC Alpha PURE-R Series Product SPECIFICATIONSAvailable from: The high-powered smart grid-ready Enphase IQ 7X Micro™ dramatically simplifies the installation process while achieving the highest system efficiency for systems with 96-cell modules.Part of the Enphase IQ System, the IQ 7X Micro integrates with the Enphase IQ Envoy™, Enphase IQ Battery™, and the Enphase Enlighten™ monitoring and analysis software.The IQ Series Microinverters extend the reliability standards set forth by previous generations and undergo over a million hours of power-on testing, enabling Enphase to provide an industry-leading warranty of up to 25 years. Enphase IQ 7X MicroinverterTo learn more about Enphase offerings, visit enphase.comData SheetEnphase MicroinvertersRegion: AMERICASEasy to Install• Lightweight and simple• Faster installation with improved, lighter two-wire cabling• Built-in rapid shutdown compliant (NEC 2014 & 2017)Efficient and Reliable• Optimized for high powered 96-cell* modules• Highest CEC efficiency of 97.5%• More than a million hours of testing• Class II double-insulated enclosure• UL listedSmart Grid Ready• Complies with advanced grid support, voltage and frequency ride-through requirements• Remotely updates to respond to changing grid requirements• Configurable for varying grid profiles• Meets CA Rule 21 (UL 1741-SA)* The IQ 7X is required to support 96-cell modules.1. No enforced DC/AC ratio. See the compatibility calculator at https://enphase.com/en-us/support/module-compatibility. 2. Nominal voltage range can be extended beyond nominal if required by the utility.3. Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area.To learn more about Enphase offerings, visit enphase.com© 2019 Enphase Energy. All rights reserved. All trademarks or brands used are the property of Enphase Energy, Inc. 2019-3-26INPUT DATA (DC)IQ7X-96-2-USCommonly used module pairings¹320 W - 460 W +Module compatibility96-cell PV modulesMaximum input DC voltage79.5 VPeak power tracking voltage53 V - 64 VOperating range25 V - 79.5 VMin/Max start voltage33 V / 79.5 VMax DC short circuit current (module Isc)10 AOvervoltage class DC portIIDC port backfeed current0 APV array configuration1 x 1 ungrounded array; No additional DC side protection required; AC side protection requires max 20A per branch circuitOUTPUT DATA (AC)@ 240 VAC@ 208 VACPeak output power320 VAMaximum continuous output power315 VANominal (L-L) voltage/range²240 V / 211-264 V208 V / 183-229 VMaximum continuous output current1.31 A (240 VAC)1.51 A (208 VAC)Nominal frequency60 HzExtended frequency range47 - 68 HzAC short circuit fault current over 3 cycles5.8 ArmsMaximum units per 20 A (L-L) branch circuit³12 (240 VAC)10 (208 VAC)Overvoltage class AC portIIIAC port backfeed current18 mAPower factor setting1.0Power factor (adjustable)0.85 leading ... 0.85 laggingEFFICIENCY@240 VAC@208 VACCEC weighted efficiency97.5 %97.0 %MECHANICAL DATAAmbient temperature range-40ºC to +60ºCRelative humidity range4% to 100% (condensing)Connector type (IQ7X-96-2-US)MC4 (or Amphenol H4 UTX with optional Q-DCC-5 adapter)Dimensions (WxHxD)212 mm x 175 mm x 30.2 mm (without bracket)Weight1.08 kg (2.38 lbs)CoolingNatural convection - No fansApproved for wet locationsYesPollution degreePD3EnclosureClass II double-insulated, corrosion resistant polymeric enclosureEnvironmental category / UV exposure ratingNEMA Type 6 / outdoorFEATURESCommunicationPower Line Communication (PLC)MonitoringEnlighten Manager and MyEnlighten monitoring optionsCompatible with Enphase IQ EnvoyDisconnecting meansThe AC and DC connectors have been evaluated and approved by UL for use as the load-break disconnect required by NEC 690.ComplianceCA Rule 21 (UL 1741-SA)UL 62109-1, UL1741/IEEE1547, FCC Part 15 Class B, ICES-0003 Class B, CAN/CSA-C22.2 NO. 107.1-01 This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and NEC-2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems, for AC and DC conductors, when installed according manufacturer’s instructions.Enphase IQ 7X Microinverter snapnrack.comUltra RailIndustry leading Wire Management SolutionsSingle Tool Installation Mounts available for all roof typesAll SnapNrack Module Clamps & Accessories are compatible with both raiil profi lesStart Installing Ultra Rail TodayUR-40UR-60The Ultimate Value in Rooftop SolarSolar Mounting Solutions© 2016 by SnapNrack Solar Mounting Solutions. All rights reserved 877-732-2860 www.snapnrack.com contact@snapnrack.comSnapNrack_Ultra Rail Sales Brochure_v.1.4SnapNrack Solar Mounting Solutions are engineered to optimize material use and labor resources and improve overall installation quality and safety.Quality. Innovative. Superior. Unparalleled Wire Management• Open rail channel provides room for running wires resulting in a long-lasting quality install• Industry best wire management o ering includes Junction Boxes, Universal Wire Clamps, MLPE Attachment Kits, and Conduit Clamps• System is fully bonded and listed to UL 2703 Standard© 2019 by SnapNrack Solar Mounting Solutions. All rights reserved 877-732-2860 www.snapnrack.com contact@snapnrack.comSnapNrack Ultra Rail SystemA sleek, straightforward rail solution for mounting solar modules on all roof types. Ultra Rail features two rail profi les; UR-40 is a lightweight rail profi le that is suitable for most geographic regions and maintains all the great features of SnapNrack rail, while UR-60 is a heavier duty rail profi le that provides a larger rail channel and increased span capabilities. Both are compatible with all existing mounts, module clamps, and accessories for ease of install.The Entire System is a Snap to Install• New Ultra Rail Mounts include snap-in brackets for attaching rail• Compatible with all the SnapNrack Mid Clamps and End Clamps customers love• Universal End Clamps and snap-in End Caps provide a clean look to the array edgeHeavy Duty UR-60 Rail • UR-60 rail profi le provides increased span capabilities for high wind speeds and snow loads • Taller, stronger rail profi le includes profi le-specifi c rail splice and end cap• All existing mounts, module clamps, and accessories are retained for the same great install experience DESCRIPTION:PART NUMBER(S):DRAWN BY:SNAPNRACK, ULTRA RAIL COMP KITSEE BELOWmwatkinsSolar Mounting SolutionsTHE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANYREPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THEWRITTEN CONSENT OF SUNRUN SOUTH LLC.595 MARKET STREET, 29TH FLOOR ● SAN FRANCISCO, CA 94105 USAPHONE (415) 580-6900 ● FAX (415) 580-6902BREVISION:MATERIALS:DESIGN LOAD (LBS):ULTIMATE LOAD (LBS):TORQUE SPECIFICATION:CERTIFICATION:WEIGHT (LBS):6000 SERIES ALUMINUM, STAINLESS STEEL, RUBBER802 UP, 1333 DOWN, 356 SIDE2005 UP, 4000 DOWN, 1070 SIDE12 LB-FTUL 2703, FILE E359313; WIND-DRIVEN RAIN TEST FROM UL SUBJECT 25820.80PARTS LISTDESCRIPTIONPART NUMBERQTYITEMSNAPNRACK, UMBRELLA LAG, TYPE 3, 4IN, SS242-9226611SNAPNRACK, ULTRA FOOT FOR U FLASHING, SILVER / BLACK242-01219, 242-0122012SNAPNRACK, COMP FLASHING, 9IN X 12IN, SILVER / BLACK ALUM232-01375, 232-01376133122DESCRIPTION:PART NUMBER(S):DRAWN BY:SNAPNRACK, ULTRA RAIL COMP KITSEE BELOWmwatkinsSolar Mounting SolutionsTHE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANYREPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THEWRITTEN CONSENT OF SUNRUN SOUTH LLC.595 MARKET STREET, 29TH FLOOR ● SAN FRANCISCO, CA 94105 USAPHONE (415) 580-6900 ● FAX (415) 580-6902BREVISION:ALL DIMENSIONS IN INCHES11.753.258.75.456.754.20.303.251.00SLOT1.50 2.781.781.50.38.301.371.62UMBRELLA L FOOT PROPERTIESSKUDESCRIPTION242-01219ULTRA RAIL UMBRELLA L FOOT, SILVER242-01220ULTRA RAIL UMBRELLA L FOOT, BLACKCOMP FLASHING PROPERTIESSKUDESCRIPTION232-01375COMP FLASHING, 9" X 12", BLACK ALUM232-01376COMP FLASHING, 9" X 12", SILVER ALUM.351.801.00105° :(676+25( '(6,*1(1*,1((563& 100 GREAT OAKS BLVD. ͿSUITE 115 ALBANY Ϳ NEW YORK Ϳ 12203 :HVW6KRUH'HVLJQ(QJLQHHUVۅ*UHDW2DNV%OYGۅ6XLWHۅ$OEDQ\1<ۅ  6XEMHFW :DGHNDPSHU5HVLGHQFH   8SSHU WK:   /DNHYLOOH01  7R:KRP,W0D\&RQFHUQ  7KHIROORZLQJUHIHUHQFHVWKH:DGHNDPSHU5HVLGHQFHLQ/DNHYLOOH01  ([LVWLQJURRIIUDPLQJ 3UHIDEULFDWHGHQJLQHHUHG ZRRG WUXVV LV [ DW ´RF 7KLV H[LVWLQJ VWUXFWXUH LV FDSDEOH RI VXSSRUWLQJDOOWKHORDGVLQGLFDWHGEHORZIRUWKLVSKRWRYROWDLF 5RRI/RDGLQJ SVIGHDGORDG VRODUPRGXOHVSOXVPRXQWLQJKDUGZDUH  SVIJURXQGVQRZORDG SVIURRIPDWHULDOV SVI[SVIVKHDWKLQJSVIDVSKDOWVKLQJOHV  ([SRVXUH&DWHJRU\%PSKZLQG VHF   7KLVLQVWDOODWLRQGHVLJQZLOOEHLQJHQHUDOFRQIRUPDQFHWRWKHPDQXIDFWXUHU¶VVSHFLILFDWLRQVDQGFRPSOLHV ZLWKDOODSSOLFDEOHODZVFRGHVDQGRUGLQDQFHVVSHFLILFDOO\WKH,QWHUQDWLRQDO%XLOGLQJ&RGH,%& DQG,QWHUQDWLRQDO5HVLGHQWLDO&RGH,5&LQFOXGLQJDOO01UHJXODWLRQVDQGDPHQGPHQWV7KHVSDFLQJ DQGIDVWHQLQJRIWKHPRXQWLQJEUDFNHWVLVWRKDYHDPD[LPXPRI´RFVSDQEHWZHHQPRXQWLQJEUDFNHWV VWDJJHUHGDQGVHFXUHGXVLQJ´GLDPHWHUFRUURVLYHUHVLVWDQWVWHHOODJEROWVDQGD´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