Loading...
HomeMy WebLinkAboutLA219554 - APPROVED - Jeneba Peterson Solar Drawings wStamp 11 01 2023COVER PAGECP 0.0PV SYSTEMAS INDICATEDScale:Project:Dakota ElectricEXISTINGINVISIMOUNTSITE MAP & PV LAYOUTELECTRICAL 1-LINE DIAGRAMATTACHMENT LAYOUTSYSTEM LABELING DETAILINVERTER DATA SHEETSHEET INDEXPROPERTY PLANRSD DATA SHEETMODULE DATA SHEETATTACHMENT DATA SHEETPV 1.0SYSTEM RATINGEQUIPMENT SUMMARYELECTRICAL INFORMATIONMAIN SERVICE PANEL BUS SIZE:MOUNTING SYSTEM:BUILDING INFORMATIONCONSTRUCTION TYPE: V-BOCCUPANCY: R3ROOF:VICINITY MAP (SCALE: NTS)SATELLITE VIEW (SCALE: NTS)GENERAL NOTES1.All electrical materials shall be new and listed by recognizedelectrical testing laboratory Custom made equipment shall have complete test data submittedby the manufacturer attesting to its safety2.Outdoor equipment shall be NEMA 3R rated or equivalent3.All metallic equipment shall be grounded4.Contractor shall obtain electrical permits prior to installation andshall coordinate all inspections, testing commissioning andacceptance with the client, utility co. and city inspectors as needed.5.The electrical contractor shall verify the exact locations of servicepoints and service sizes with the serving utility company andcomply with all utility companies requirements.6.Drawings are diagrammatic only, routing of raceways shall beoption of the contractor unless otherwise noted and shall becoordinated with other trades.7.If the roof material or the roof structure not adequate for PVinstallation, call the engineer of record prior to installation. Thecontractor is responsible to verify that the roof is capable ofwithstanding the extra weight.8.If the distances for cable runs are different than shown, thecontractor shall notify the electrical engineer to validate the wiresize. Final drawings will be red-lined and updated as appropriate.9.Whenever a discrepancy in quality of equipment arises on thedrawing or specifications, the contractor shall be responsible forproviding and installing all materials and services required by thestrictest conditions noted on the drawings or in the specificationsto ensure complete compliance and longevity of the operablesystem required by the engineer of record.PHOTOVOLTAIC NOTES:1.Rooftop mounted photovoltaic panels and modules shall be tested,listed and identified by recognized testing laboratory2.Solar system shall not cover any plumbing or mechanical vents3.Modules and support structures shall be grounded unless racking has integrated ground.4.Removal of an interactive inverter or other equipment shall notdisconnect the bonding connection between the groundingelectrode conductor and the photovoltaic source and/or outputcircuit grounded conductors.5.All PV modules and associated equipment and wiring shall beprotected from physical damage.6.Live parts of PV source circuits and PV output circuits over 150v toground shall not be accessible to other than qualified persons while energized.7.Inverter is equipped with integrated DC disconnect, thus providingground fault protection8.All conductors shall be copper and 75 deg rated9.A single conductor shall be permitted to be used to perform themultiple functions of dc grounding, AC grounding and bondingbetween AC and DC systems.10.Non-current carrying metal parts of equipment shall be effectivelybonded together. Bond both ends of raceways.200A SUNPOWER U-SERIES 405 WATT MODULES INTEGRATED IQ7HS MICROINVERTERSTHE INSTALLATION OF SOLAR ARRAYS ANDPHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITHTHE FOLLOWING CODES:·2023 National Electrical Code·2018 International Building Code·2018 International Residential Code·2020 Minnesota Residential Code·2020 Minnesota Building Code·2020 Minnesota Energy Code·2020 Minnesota Accessibility Code·2020 Minnesota State Fire Code·2018 International Fire Code·2018 International Energy Conservation Code·2018 Mechanical CodeAS ADOPTED BY THE STATE OF MINNESOTAALL OTHER ORDINANCE ADOPTED BY THELOCAL GOVERNING AGENCIESGOVERNING CODESSURGE PROTECTIONPLACARDDC 9.720 KW STCAC 9.216 KW STC24PV 2.0PV 3.1PV 3.2PV 4.0PV 5.0D 6.0D 7.0D 8.0D 9.0D 10.0D 11.0D 12.0D 13.0COVER PAGECP 0.0COMP. SHINGLETRUSS: 2 X 4 @ 24" O.C.24INVERTER CERTIFICATIONPV INSPECTION CHECKLISTD 14.0UTILITYDrawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938MONITORING DATA SHEETRACKING DATA SHEETThese drawings are protected by copyright under US law. Any form ofreproduction is strictly prohibited without prior written approval from Engineerinc.MILBANK DATA SHEETD 15.0Date Certified andExp. Date : 06/30/2024Signed: 11/01/2023Engineerinc.io,303 N Glenoaks BlvdBurbank, CA 91502(310) 928-0938Concept Approval ONLYSubject to Field InspectionInspectorDate2015MN BldgCode11/01/2023jnuetzman ............................................................................MSP(E) Main Service PanelINDEXAC....................(N) 60A Utility AC(N) MicroinverterNOTE: Conduit in attic shallbe minimum 18 inches from roof sheatingPVS(N) 125A PV Sub Panel ........Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTNOTE: No clearance issueDistance between all equipments is maximum 10"(E) Main MeterMM.....................................SECONDARY INTERCONNECTION.............SOLAR MODULES___SUNPOWER 405 WattModel #SPR-U405-BLKINVERTERINVERTER TYPE: Micro:___ Enphase IQ7HS MicroinvertersModel # IQ7HS-66M-US(240V)Dakota ElectricTOTAL ROOF AREA:2656TOTAL MODULE AREA:52819.87% OF COVERAGESITE MAP & PVLAYOUTPV 1.0PV SYSTEMAS INDICATEDScale:Project:JB(N) Junction Box(N) Solar ModuleEMT Type ConduitFire Setback LineFMT type Conduit2424Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938EQUIPMENT ELEVATIONNOTE: Keep 3ft clearance from gas meter and AC unitPVS6(N) PV Monitoring System.....200APM(N) Performance Meter...........From roofPVSPVS6MainServicePanelInsideOutsideInsideOutsideUtility ACDisconnectPerformanceMeterMeterMain4'10"10"<10'3' f ire se tback 3' fire setback18'' f ire setback18'' f ire setback18'' fire setbackaaaaaaabbbbbbbbb c c c c c c c cJBJBJBPVSACPMMSPMMEmbers AveSolar PV Array 17 - SunPower 405W Modules7 - Enphase IQ7HS MicroinvertersPitch: 34 DegOrientation: 258 DegSolar PV Array 29 - SunPower 405W Modules9 - Enphase IQ7HS MicroinvertersPitch: 34 DegOrientation: 168 DegSolar PV Array 38 - SunPower 405W Modules8 - Enphase IQ7HS MicroinvertersPitch: 34 DegOrientation: 168 DegPVS6SCALE:3/32" = 1'-0" 180° 90° 270°0°SWNE ELECTRICAL 1-LINEDIAGRAMPV 2.0PV SYSTEMAS INDICATEDScale:Project:Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTDesign meet National Electric Code(NEC codes)SUNPOWER U-SERIES 405 WATT MODULES24INTEGRATED ENPHASE IQ7HS MICROINVERTERSSYSTEM RATING AND DER POWER OUTPUTINVERTER:ENPHASE IQ7HSINVERTER MAXIMUM CONTINUOUS OUTPUT:384VASYSTEM POWER OUTPUT:ENPHASE MICROINVERTERS1 PHASE 384VAMAXIMUM OUTPUT CURRENT 1.6AAC PORT BACKFEED CURRENT 0ADC SHORT CIRCUIT CURRENT 15ADC 9.720 KW STCAC 9.216 KW STCDC 9.720 KW STCAC 9.216 KW STCDakota Electricx 384 =9216SECONDARY INTERCONNECTIONREFERENCE POINT OF APPLICABILITY15AEXISTING______ MAINSERVICEPANEL120/240V,1P, 3WGEC(E) GROUNDINGELECTRODE SYSTEM200A125A PV SUB PANEL120/240V, NEMA 3RINSTALL (3)20APV 2-POLE C/B60A FUSED UTILITY ACDISCONNECT,WITH 50A FUSESVISIBLE-OPEN LOCKABLE,READILY ACCESSIBLE,NEMA3R, 120 / 240V(NEW)GECAdd 2nd Ground rod andtie it to the existing ground rod.MILBANK k497738.4A38.4ANOTE: Keep 3ft clearance from gas meter and AC unit2424Wire Size90C wirerating12 AWGTHWN-2, THHNXHHW-2, USE-210 AWGTHWN-2, THHNXHHW-2, USE-38 AWGTHWN-2, THHNXHHW-2, USE-4304055Temperature rating ofConductors-Ambient Temp.(114-122F) NEC 310.15(B)(2)(a)Number of Current carrying Conductors NEC 310.15(B)(16)4-67-910-2020A Branch Circuit Rating30A Branch Circuit Rating30 x 0.82=24.640 x 0.82=32.855 x 0.82=45.124.6x0.80= 19.6832.8x0.80= 26.2445.1x0.80= 36.0824.6x0.70= 17.2232.8x0.70= 22.9645.1x0.70= 31.5724.6x0.50= 12.332.8x0.50= 16.445.1x0.50= 22.55YES- 6 or less current carryingconductors in the same conduitYES- 9 or less current carryingconductors in the same conduitYES- 20 or less current carryingconductors in the same conduitYES- 9 or less current carryingconductors in the same conduitYES- 3 or less current carryingconductors in the same conduitNOSurge ProtectionMNSPD-300-ACDrawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938AtticWall(6) #12 AWG THWN/THWN-2(1)#12 AWG GND3/4" EMT, 2 FEET(3) #6 AWG THWN/THWN-2(1) #6 AWG GND1" SCH 80 PVC, 2 FEET(3) #6 AWG THWN/THWN-21" SCH 80 PVC, 2 FEETMETER MAIN120/240V,1P, 3WPVS6MONITORING SYSTEM1BRANCHCIRCUIT-A (3) J BOXNEMA3R11.2A1-PHASE MICRO-INVERTER UL174127114.4A29BRANCHCIRCUIT-B(6) #12 AWG THWN/THWN-2(1)#12 AWG GND3/4" FMT, 2 FEETProduction CTsUTILITY PV METER PRODUCTIONMETER SOCKET LABELED INACCORDANCE WITH NEC ANDAHJ REQUIRMENTS LOCATEDWITHIN 5' OF MAIN. INVERTEROUTPUT WIRED TO LOAD SIDETERMINAL OF METER 1 PHASE3-WIRE 120/240VLINELOAD38.4ASUNPOWER TRUNK CABLE(2) #12 AWG PV WIRE(1) #10 INTEGRATED GROUNDINGFREE IN THE AIR(1) #6 AWG GND128BRANCHCIRCUIT-C 12.8A(3) #6 AWG THWN/THWN-21" SCH 80 PVC, 2 FEET200AConsuption CTs SYSTEMLABELING DETAILPV 3.1PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938PV ARRAYJ BOXPV SUB-PANELACDISCONNECTMAIN SERVICEPANELMETER233321716218135Note: LABELS SHALL COMPLY WITH NEC 690“Labels shall be weatherproof, durable and permanently mounted”Photovoltaic Power SourceLABEL 2CAUTION: SOLAR CIRCUITLABEL 3WARNINGELECTRIC SHOCK HAZARDTHE DC CONDUCTORS OF THISPHOTOVOLTAIC SYSTEM AREUNDERGROUND AND MAY BE ENERGIZEDLABEL 4WARNINGELECTRIC SHOCK HAZARDIF GROUND FAULT IS INDICATEDNORMALLY GROUNDED CONDUCTORSMAY BE UNDERGROUND AND ENERGIZEDLABEL 5WARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE AND LOADSIDES MAY BE ENERGIZED IN THE OPENPOSITIONLABEL 6WARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE AND LOADSIDES MAY BE ENERGIZED IN THE OPENPOSITIONDC VOLTAGE IS ALWAYS PRESENTWHEN SOLAR MODULESARE EXPOSED TO SUNLIGHTLABEL 7WARNINGLABEL 8TURN OF PHOTOVOLTAICAC DISCONNECT PRIOR TOWORKING INSIDE PANELDO NOT DISCONNECTUNDER LOADLABEL 9MAIN PV SYSTEMDISCONNECTLABEL 10MAIN PV SYSTEMAC DISCONNECTLABEL 11LABEL 12CAUTIONLABEL 13SOLAR ELECTRIC SYSTEMCONNECTEDWARNING-LABEL 14 DUAL POWER SOURCESECOND SOURCE IS PV SYSTEMCAUTIONLABEL 15PHOTOVOLTAIC SYSTEM CIRCUITIS BACKFEDLABEL 16PHOTOVOLTAIC AC DISCONNECTMAXIMUM AC OPERATING CURRENTMAXIMUM AC OPERATING CURRENTPHOTOVOLTAICLABEL 17UTILITY AC DISCONNECTPHOTOVOLTAICLABEL 18DC DISCONNECTNOMINAL OPERATING AC VOLTAGENOMINAL OPERATING AC FREQUANCYMAXIMUM AC POWERMAXIMUM AC CURRENTMAX OCERCURRENT DEVICE RATINGFOR AC MODULE PROTECTIONLABEL 19LABEL 20PV SYSTEM DC DISCONNECTOPERATING CURRENTOPERATING VOLTAGEMAXIMUM SYSTEM VOLTAGESHORT CIRCUIT CURRENTRATED MAX POWER-FONT CURRENTRATED MAX POWER-FONT VOLTAGEMAXIMUM SYSTEM VOLTAGESHORT CIRCUIT CURRENTMAX RATED OUTPUT CURRENT OFTHE CHARGE CONTROLLER IF INSTALLEDLABEL 21***ALL LABELS = RED THERMOPLASTIC/REFLECTIVE , Permanently mounted240VSOLAR DISCONNECT21SOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNTURN RAPID SHUTDOWNSWITCH TO THE"OFF" POSITION TOSHUT DOWN PV SYSTEMAND REDUCESHOCK HAZARDIN THE ARRAYSOLAR ELECTRICPV PANELS38.4AProduction MeterLABEL 1PerformanceMeter31 PLACARDPV 3.2PV SYSTEMAS INDICATEDScale:Project:CAUTIONPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:SERVICE 1 OF 2CAUTIONPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:SERVICE 2 OF 2NWESNWES17829 Embers Ave,Lakeville, MN 5504417829 Embers Ave,Lakeville, MN 55044Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938SERVICE POINT &UTILITY METERINGPV SYSTEM DISCONNECTFOR UTILITY OPERATIONPV SUB PANELPV MONITORING SYSTEMPERFORMANCE METERSOLAR PV ARRAYSERVICE POINT &UTILITY METERINGPV SYSTEM DISCONNECTFOR UTILITY OPERATIONPV SUB PANELPV MONITORING SYSTEMPERFORMANCE METERSOLAR PV ARRAY PROPERTY PLANPV 4.0PV SYSTEMAS INDICATEDScale:Project:.....................MSPMain Service PanelINDEXAC..................................Utility ACPVSPV Sub Panel ......................Main MeterMM..............................Solar Module.................Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTDakota ElectricDrawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938PVS6PV Monitoring System............PM.................Performance MeterDrivewayPVSACPMMSPMM124'-11"89'-5"114'-2"89'-7"26'-6"27'33'-3"28'-8"PROPERTY LINEEmbers AvePVS6SCALE:1/16" = 1'-0" 180° 90° 270°0°SWNEDate Certified andExp. Date : 06/30/2024Signed: 11/01/2023Engineerinc.io,303 N Glenoaks BlvdBurbank, CA 91502(310) 928-0938 ATTACHMENTLAYOUTPV 5.0PV SYSTEMAS INDICATEDScale:Project:DESIGN CRITERIAModules:Max Distributed Load: 3 PSFPOINT LOAD CALCULATION PER ARRAYModule Weight (lbs)# Of Modules48.5Total Module Weight (lbs)Rack Weight (lbs)MicroInverters Weight (lbs)Total System Weight (lbs)# Of StandoffsMax Span Between Standoffs (in)Loading Per Standoff (lbs)Total Area (sq.ft.)Loading (PSF)1164232.857.121453.92544826.925282.75RAIL ATTACHMENTTRUSS: 2 X 4 @ 24" O.C.24241 Layer of .Plywood & Building FeltSolar Module6"AttachmentROOF SECTION DETAILTRUSS: 2 X 4 @ 24" O.C.COMP. SHINGLEPrior to the commencement of work, thecontractor shall verify the existing roof andframing conditions. Notify New@engineerinc.ioof any Discrepancies prior to startingconstruction. Prior to the commencement ofwork, the contractor shall inspect framing forany damage such as water damage, crackedframing, etc. and These Plans are stamped forstructural code compliance of the roof framingsupporting the proposed PV installationreference only. These plans are not stampedfor water leakage. PV modules, racking, andattachment components must followmanufacturer guidelines and requirements.Attachments to be installed in a staggeredorientation to properly distribute loads.Note: 24/ 7 Unescorted keyless access is to beprovided for ALL UTILITY EQUIPMENTDrawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938LightSpeed FlashingSupport BlockEPDM WASHERROOF ASSEMBLYPEGASUS COMP SHINGLE DETAILS21'-11"19'-6"Date Certified andExp. Date : 06/30/2024Signed: 11/01/2023Engineerinc.io,303 N Glenoaks BlvdBurbank, CA 91502(310) 928-0938 PV 6.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938MONITORINGDATA SHEET INVERTERDATA SHEETD 7.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938 RSDDATA SHEETD 8.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938 MODULEDATA SHEETD 9.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938 RACKINGDATA SHEETD 10.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938 ATTACHMENTDATA SHEETD 11.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938 D 12.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938SURGEPROTECTION D 13.0PV SYSTEMAS INDICATEDScale:Project:INVERTERCERTIFICATIONDrawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938 D 14.0PV SYSTEMAS INDICATEDScale:Project:PV INSPECTIONCHECKLISTDrawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938Wolf RIver ElectricLakeville, MN 5504417829 Embers Ave D 15.0PV SYSTEMAS INDICATEDScale:Project:Drawn by: New@engineerinc.ioProject Name:Property Address:DATE CREATED:CONTRACTORWolf RIver ElectricAddress:101 Isanti ParkwayNE, Isanti, MN 55040Phone number: (763) 229-6662E-mail: contact@wolfriverelectric.comREVISION DATE:17829 Embers Ave,Lakeville, MN 55044REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:REVISION DATE:Jeneba Peterson10/24/2023Phone Number: (310) 928-0938MILBANKDATA SHEET Structural Engineering Letter Date: 11/01/2023 Project Name: Jeneba Peterson Project Address: 17829 Embers Ave, Lakeville, MN, 55044 Contractor : Wolf RIver Electric Contractor Address : 101 Isanti Parkway NE, Isanti, MN 55040 Attn : To Whom It May Concern A Field observation of the condition of the existing framing system was performed by an audit team from Wolf RIver Electric. From the Field observation of the property, the existing roof structure observed as follows: Existing roof is supported by 2 x 4 @ 24" rafters at the solar array. The rafters are sloped at approximately 34 degree and have maximum projected horizontal span of 7 feet in between load bearing supports. Design Criteria Applicable codes: 2020 Minnesota Building Code (2018 IBC) ASCE 7-16 Ground Snow Load: 50 psf Roof Dead Load: 20 psf Wind speed: 125 mph Risk Category: II I certify that the capacity of the structural roof framing that directly supports the additional gravity loading due to the solar panel supports and modules had been reviewed and determined to meet or exceed the requirements in accordance with the Design Criteria. If you have any questions or concerns please contact us, Engineerinc.io, 303 N Glenoaks Blvd Suite 200 Burbank, CA 91502 (310) 928-0938 new@engineerinc.io Date Certified and Exp. Date : 06/30/2024 Signed: 11/01/2023 Date: 11/01/2023 Job Number: 15791 Prepared for : Wolf RIver Electric, 101 Isanti Parkway NE, Isanti, MN 55040 Project.: Jeneba Peterson , 17829 Embers Ave, Lakeville, MN, 55044 The following calculations are for the structural engineering design of the photovoltaic panels and are valid only for the structural info referenced in the stamped plan set. The verification of such info is the responsibility of others. After review, I certify that the roof structure has sufficient structural capacity for the applied PV loads. All PV mounting equipment shall be designed and installed per manufacturer's approved installation specifications. Engineerinc.io 303 N Glenoaks Blvd Suite 200 Burbank, CA 91502 (310) 928-0938 new@engineerinc.io 303 N. Glenoaks Blvd Suite #200 Burbank, CA 91502 | (310) 928-0938 | new@engineerinc.io Date Certified and Exp. Date : 06/30/2024 Signed: 11/01/2023 Solar Module Details Module Type Sunpower Module Quantity 24 Module Model Number 405 watt Design Criteria Code: 2020 Minnesota Building Code (2018 IBC) ASCE 7-16 Live Load (psf)20 Ult Wind Speed (mph)125 Exposure Cat C Ground Snow (psf)50 Structure Geometry Eave Height, he (ft)15 to 20ft Pitch of main roof (deg)34 Building Length, L (ft)40 Building Width, B (ft)55 Roof Area (Module Area) ft2 2200.00 Standoff(i.e., Roof Mount) Spacing Feet 4` NOTE: attachments should be installed in a staggered configuratiion to properly destributor loading. Roof Properties Roof Geometry type Gable Roof Roof Type Truss Roof Pitch (deg)34 303 N. Glenoaks Blvd Suite #200 Burbank, CA 91502 | (310) 928-0938 | new@engineerinc.io Roofing Type Comp Shingles Sheathing Type 1/2" OSB Board Wood species No. 2, Douglas Fir-Larch Wood Fb (psf)900 Wood Fv (psf)180 Wood E (psf)1600000 Purlin C/C Spacing (in)12 Rafter C/C. Spacing (in.)24 Purlin Section Thickness, b (in.)2 Section Depth, d (in.)4 Rafter Section Thickness, b (in.)2 Section Depth, d (in.)4 Maximum Rafter Span (ft)7 Factors Cd(wind)1.60 Cd(Snow)1.60 CLS 1.15 CM 1 Ct 1 CL 0.75 CF 1.5 Cfu 1 Cv 1 Cr 1 M allowable_wind 413.44 M allowable_snow 297.16 303 N. Glenoaks Blvd Suite #200 Burbank, CA 91502 | (310) 928-0938 | new@engineerinc.io Dead Load(psf) Comp Shingles 3.00 psf 1/2" OSB Board 2.00 psf Insulation 2.00 psf Total Roof 1DL 7 psf No. 2, Douglas Fir-Larch 31.00 lb/ft3 Solar Panel DL 3.00 psf Roof 1 Roof_Dist_DL 7.00 psf M_Roof_Dist_DL 1673.11 Def_Roof_Dist_DL 1.00 PV_uni_Dist_DL 3.00 psf M_PV_uni_Dist_DL 10.54 Def_PV_uni_Dist_DL 0.01 Total_Uni_DL 11.00 psf M_Total_DL 1683.65 Def_Total_DL 1.00 Snow Load(psf) Ground Snow Load, pg 50 Importance Factor, Ic 1 Thermal Factor, Ct 1 Exposure Factor, Ce 1 Flat roof snow, pF 50 Slope Factor, Cs 1 303 N. Glenoaks Blvd Suite #200 Burbank, CA 91502 | (310) 928-0938 | new@engineerinc.io Sloped Row Snow, ps 50 Uni_Dist_S 50.00 M_uni_Dist_s 306.25 Def_uni_Dist_S 0.18 Wind Load Ultimate Wind Speed 125 Directionality Factor,kd 0.85 Topographic factor 1.00 Velocity pressure exposure factor,kz 0.88 Ground Elevation Factor,ke -0.42 Side Wall Width 55 Median Roof Height -16.79 Velocity pressure,qz 29.92 External Pressure Up,GCp_1 -0.04 External Pressure Up,GCp_2 -0.6 External Pressure Up,GCp_3 -0.9 External Pressure Down,GCp 0.38 Design Pressure Up,p_1 -1.00 Design Pressure Up,p_2 -15.01 Design Pressure Up,p_3 -22.51 Design Pressure Up,p 9.50 Uni_Dist_W_up -22.51 M_uni_Dist_W_up -137.87 Def_uni_Dist_W_up -0.08 Uni_Dist_W_down 9.50 303 N. Glenoaks Blvd Suite #200 Burbank, CA 91502 | (310) 928-0938 | new@engineerinc.io M_uni_Dist_W_down 58.19 Def_uni_Dist_W_down 0.03 Lag Screw Uplift Check (ASD) 5/16" Lag Screw Withdrawl value 205.00 lb/in Lag Screw Penetration 2.50 in Roof1 0.6D+0.6W(up z1)1146.672 > 512.5 Roof1 0.6D+0.6W(up z2)1138.266 > 512.5 Framing Check (ASD): Roof1 uni 1.0D+0.6W 1718.56 > 413.44 Lag Screw Penetration 1939.52 > 413.44 Roof1 0.6D+0.6W(up z1)1989.90 > 297.16 Roof1 0.6D+0.6W(up z2)927.47 > 413.44 Seismic Check: Wood 5.00 psf 2x4 Studs @ 16"2.00 psf Gypsum 3.00 psf Misc(insulatioon,etc)2.00 psf Total wall DL 12.00 psf Total Wall Area (Approx)2765.00 ft2 Total Wall W 33180 lbs Total Roof DL 7.50 psf Total Roof Area (Approx)1591.88 ft2 Total Roof W 11939.1 lbs 303 N. Glenoaks Blvd Suite #200 Burbank, CA 91502 | (310) 928-0938 | new@engineerinc.io OK PV Panel W 3.00 psf Area of panel 480.00 ft2 Total Roof W 948.92 lbs % increase=(Wadditional)/Wexisting 2.26% The increase in weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. Limits of Scope of Work and Liability Existing structure is assumed to have been designed and constructed following appropriate codes at time of erection, and assumed to have appropriate permits. The calculations produced are only for the roof framing supporting the proposed PV installation referenced in the stamped planset and were completed according to generally recognized structural analysis standards and procedures, professional engineering and design experience, opinions and judgements. Existing deficiencies which are unknown or were not observable during time of inspection are not included in this scope of work. All PV modules, racking, and mounting equipment shall be designed and installed per manufacturer's approved installation specifications. The Engineer of Record and Engineerinc assume no responsibility for misuse or improper installation. This analysis is not stamped for water leakage. Framing was determined based on information in provided plans and/or photos, along with engineering judgement. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and spans noted in the stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any discrepancies prior to starting construction. Contractor shall also verify that there is no damaged framing that was not addressed in stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any concerns prior to starting construction. Prior to the commencement of work, the contractor shall verify the existing roof and framing conditions. Notify Engineerinc and the engineer of record of any Discrepancies prior to starting construction. Prior to the commencement of work, the contractor shall inspect framing for any damage such as water damage, cracked framing, etc. and notify the E.O.R. if any issues are found.These plans/calculations are stamped for structural code compliance of the roof framing supporting the proposed PV installation reference only. These plans/calculations are not stamped for water leakage. PV modules, racking, and attachment components must follow manufacturer guidelines and requirements. 303 N. Glenoaks Blvd Suite #200 Burbank, CA 91502 | (310) 928-0938 | new@engineerinc.io