HomeMy WebLinkAboutLV24-00208 - APPROVED-18346 Kingsway Path Solar Permit PlansPV- 0COVER PAGEAUTHORITIES HAVING JURISDICTIONBUILDING: CITY OF LAKEVILLEZONING: CITY OF LAKEVILLENEW PHOTOVOLTAIC SYSTEM 11.890 KW DC18346 KINGSWAY PATH, LAKEVILLE, MN 55044GENERAL NOTESVICINITY MAPSATELLITE VIEW1.1.1 PROJECT NOTES:1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONALELECTRICAL CODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING ANDINSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BYTHE AUTHORITY HAVING JURISDICTION’S (AHJ) APPLICABLE CODES.1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED ANDPV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION.1.1.4 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE ISINTEGRATED WITH THE MICROINVERTER IN ACCORDANCE WITH NEC 690.41(B)1.1.5 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVEINVERTERS AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED ANDLISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4: PVMODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIREINVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(ES): UL1703 OR UL 1741 ACCESSORY1.1.6 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDEDTEMP COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGECALCULATED ACCORDING TO NEC 690.7.1.1.7 ALL INVERTERS, PHOTOVOLTAIC MODULES,PHOTOVOLTAIC PANELS,AND SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAICPOWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATIONPER690.4 (D). SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONS FROMLISTING OR LABELING [NEC 110.3].1.1.8 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDINGCODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUESAND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.1.2.1 SCOPE OF WORK:1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN ANDSPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT.PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTINGONSITE REQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THE EXTERIORROOF-MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMS DETAILED INTHIS DOCUMENT1.3.1 WORK INCLUDES:1.3.2 PV RACKING SYSTEM INSTALLATION - IRONRIDGE XR RAILS1.3.3 PV MODULE AND INVERTER INSTALLATION - REC410AA Pure-R (410W)SOLAR MODULES / ENPHASE IQ8X-80-M-US MICROINVERTERS1.3.4 PV EQUIPMENT ROOF MOUNT1.3.5 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX1.3.6 PV LOAD CENTERS (IF INCLUDED)1.3.7 PV METERING/MONITORING (IF INCLUDED)1.3.8 PV DISCONNECTS1.3.9 PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.3.10 PV FINAL COMMISSIONING1.3.11 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV1.3.12 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODESCOPE OF WORKSYSTEM SIZE: AC SIZE :29 X 380W= 11.020 kW AC (29)REC410AA PURE-R (410W) SOLAR MODULES ATTACHMENT TYPE: ROOF MOUNTOWNERNAME:REV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY -CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comSTEVEN SWANSONDC SIZE :29 X 410W= 11.890 kW DC (29)ENPHASE IQ8X-80-M-US MICROINVERTERSDESIGN SPECIFICATIONOCCUPANCY: IICONSTRUCTION: SFRZONING:RESIDENTIALGROUND SNOW LOAD: 58 psfWIND EXPOSURE: BWIND SPEED: 115 mphPROJECT INFORMATION(1)ENPHASE IQ COMBINER PANEL MSP UPGRADE : NO(1)60A FUSED AC DISCONNECTAPPLICABLE CODES & STANDARDSBUILDING: MBC 2020 MRC 2020ELECTRICAL: NEC 2023FIRE: MFC 2020SHEET INDEXCOVER PAGEPV- 0SITE PLANATTACHMENT PLANELECTRICAL PLANTHREE LINE DIAGRAMWARNING LABELSSTANDOFF DETAILSELECTRICAL CALCULATIONSPV - 1PV - 2PV - 3PV - 4PV - 5PV - 6PV - 7PV - 8ONE LINE DIAGRAMPV - 9PV - 10PV - 11PV - 12MODULES DATASHEETINVERTER DATASHEETATTACHMENT DATASHEETRACKING DATASHEETUTILITY: DAKOTA ELECTRICCONTRACTOR INFONAME: JAMES RAYMONDCELL: +1 (763) 229 -9046EMAIL: J.raymond@solarbycentauri.comCOORDINATES. : 44.683873, -93.298511 9/27/2024Concept Approval ONLYSubject to Field InspectionInspectorDate2015MN BldgCode09/30/2024jnuetzman
KINGSWAY PATHROOF MOUNTED PHOTOVOLTAICARRAY29 REC410AA PURE-R (410W) SOLARMODULES=11890 DC WATTS109'-10"12
8
'
-
1
1
"
85'-5"43'-6"45'-6"29'-7"18
0
'
-
1
0
"43'-1"92'-9
"31'-6"56'-1
1
"DRIVEWAYUM
MSP
PM
CP
ACDROOF ACCESSPOINTROOF 1(N) AC CONDUIT RAN THROUGHTHE ATTIC IN INTERIOROF HOME 3/4" EMT(E) UTILITY METER(OUTSIDE HOUSE)(N) COMBINER PANEL(OUTSIDE HOUSE)(E) MAIN SERVICE PANEL(INSIDE HOUSE)(N) VISIBLE-OPEN TYPE, LOCKABLE,AND READILY ACCESSIBLE ACDISCONNECT (FUSIBLE)(OUTSIDE HOUSE)(N) PRODUCTION METER(OUTSIDE HOUSE)(N) JUNCTION BOXNEMA-3R OR EQUIVALENTROOF ACCESSPOINT18" FIRE SETBACK36" FI
R
E
S
E
T
B
A
C
K
PV - 1REV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY -CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comSITE PLANNOTES:1. ALL CONSTRUCTION / INSTALLATIONIS TO COMPLY WITH THE FOLLOWING:ALL DIMENSIONS ARE APPROXIMATE.2. ROOF VENTS, SKYLIGHTS,WILL NOT BE COVEREDUPON PV INSTALLATION.NNOTES:1. LOCATION OF JUNCTION BOX(ES), ACDISCONNECTS(S), AC COMBINER PANEL(S),AND OTHER ELECTRICAL EQUIPMENT(S)RELEVANT TO PV INSTALLATION SUBJECT TOCHANGE BASED ON SITE CONDITIONS.2. SETBACKS AT RIDGES CAN BE REDUCED TO18 INCHES IN COMPLIANCE WITH MBC 2020:TOTAL PLAN VIEW AREA = 2746 SQFTTOTAL PV AREA = 29(68.1 IN)(44 IN)/(144IN^2) = 603.44 SQFT(603.44 SQFT/2746 SQFT)100 = 21.98 %TOTAL PV AREA POPULATES 21.98 % OF TOTALPLAN VIEW AREA AND IS WITHIN THE 33%REQUIREMENT. INVERTER SPECIFICATIONSMANUFACTURER / MODEL ENPHASE IQ8X-80-M-US MICROINVERTERSMAXIMUM OUPUT POWERNOMINAL VOLTAGENOMINAL OUTPUT CURRENT380 VA240 V1.58 AINVERTER QUANTITY29 NOS.LEGENDSUMACDPMMSP- UTILITY METERJB- AC DISCONNECT- PRODUCTION METER- MAIN SERVICE PANEL- VENT, ATTIC FAN(ROOF OBSTRUCTION)- JUNCTION BOXCP- COMBINER PANEL- CONDUIT- FIRE SETBACKNOTE: 24/7 UNESCORTED KEYLESS ACCESS SHALL BEPROVIDED TO ALL XCEL ENERGY EQUIPMENTALL PV EQUIPMENT INSTALLEDWITHIN 10' OF UTILITY METER3. NO CLEARANCE ISSUESAROUND HOME OR SOLARARRAYELECTRIC SERVICE LINES AREUNDERGROUND NOTOVERHEADPHASES OF INVERTERS : SINGLE PHASEPHASES OF DER SYSTEM : SINGLE PHASE11.020 AGGREGATE kW AC11.890 kW DC ARRAY(29)REC410AA PURE-R (410W) SOLAR MODULESNEAREST INTERSECTION:75FT SE, AT KINGSWAY PATH AND KERRVILLE TRIAL9/27/2024
UM
MSP
PM
CP
ACDROOF 1(N) AC CONDUIT RANTHROUGHTHE ATTIC IN INTERIOROF HOME 3/4" EMTSEE EQUIPMENTLOCATION ELEVATIONROOF MOUNTED PHOTOVOLTAICARRAY29 REC410AA PURE-R (410W) SOLARMODULES=11890 DC WATTS1111111111222222222233333333318" FIRE SETBACK36" F
I
R
E
S
E
T
B
A
C
K
ROOF SECTION(S)TILT - 27°AZIMUTH - 205°MODULE - 29ROOF 1SCALE:3/32" = 1'-0"PV-2REV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY -CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comELECTRICAL PLANVARIESEQUIPMENT ELEVATION STRING OF 10 MODULES1 STRING OF 10 MODULES2 STRING OF 09 MODULES310'M(E) UTILITY METER(OUTSIDE HOUSE)(E) 200A MAINSERVICE PANEL(INSIDE HOUSE)(N) COMBINER PANEL(OUTSIDE HOUSE)(N) JUNCTION BOX(ON THE ROOF)(N) AC-DISCONNECTVISIBLE-OPEN TYPE,LOCKABLE, READILYACCESSIBLE, LABELED,EATON DG222NRB 60AFUSIBLE WITH 60A/2PFUSES, 240VM(N) UTILITYPRODUCTIONUTILITY METER(OUTSIDE HOUSE)(OUTSIDE HOUSE)
IRONRIDGE RAIL(TYP TYPE RACKING)2"X4" PRE-FAB TRUSSES @ 24"O.C., VERIFY LOCATIONSMOUNTING POINTS, REFER TODETAIL(TYP TYPE RACKING)4'-2"44'-11"7"1'-6"
17'-2"
2'-7"4'-0"PV - 3ATTACHMENT PLAN 1ATTACHMENT PLANSCALE:3/16" = 1'-0"MEETS OR EXCEEDS IBC IRC CONSTRUCTION STANDARDS LOAD CALCULATIONSMODULE TYPE, DIMENSIONS & WEIGHT:NUMBER OF PANELS IN ARRAY = 29 MODULESMODULE TYPE = REC410AA PURE-R (410W) SOLAR MODULESNUMBER OF CONNECTIONS TO ROOF =64WEIGHT OF INDIVIDUAL PANEL = 47.4 LBS / 21.5 KG.MOUNTING SYSTEM WEIGHT : 1.5 LBS. PER MODULETOTAL WEIGHT OF ARRAY: 1374.6 LBS.WEIGHT AT EACH CONNECTION : 1374.6 LBS / 64 = 21.48 LBSSOLAR PANEL AREA = 68.1"X 44" =20.78 SFTOTAL ARRAY AREA = 29 X 20.78 = 602.62SF DISTRIBUTED LOAD = 1374.6/602.62 = 2.28 PSFREV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY -CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.com5'-8"
12"3'-9"ROOF 1: ARRAY DETAILSTILT- 27 DEGAZIMUTH - 205 DEGMATERIAL- ASPHALT SHINGLES9/27/2024
STANDOFF PV-4DETAILS1STAND OFF DETAILSSCALE:3/8" = 1'-0"REV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY -CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comLAG BOLT/SCREWS OF A RELATIVELY SMALL,5/16 INCH DIAMETER BY 3 INCHES LONG CANBE EMBEDDED IN THE TOP, 2"X4" CHORD OFA SIMPLE SPAN MEMBER TRUSS A MINIMUMPENETRATION OF 2-1/2" INCHES IS REQUIRED(TYP TYPE RACKING)STRUCTURAL DETAILS#14 RD STRUCTURAL SCREWIRONRIDGE (AIRE) RAILSIRONRIDGE(QUICK MOUNTHALO ULTRAGRIP)IRONRIDGE (QUICKMOUNT HALO ULTRAGRIP)IRONRIDGE (AIRE) RAILSSOLAR MODULEWOOD SHEATHINGWOOD ROOFTRUSS TYP.WOOD ROOFTRUSS TYP.WOOD SHEATHINGRELEASE LINERRELEASE LINERRAFTER MOUNT9/27/2024
10 MICROINVERTERS IN BRANCH CIRCUIT 209 MICROINVERTERS IN BRANCH CIRCUIT 310 MICROINVERTERS IN BRANCH CIRCUIT 1L129 -REC410AA PURE-R (410W) SOLAR MODULES ENPHASE Q CABLES29 - ENPHASE IQ8X-80-M-USMICROINVERTERS (240V) - MOUNTED UNDEREACH PANEL (690.14(D))INTEGRATED GROUNDING WIRE(N) DEDICATEDPHOTOVOLTAIC SYSTEMENPHASE COMBINER PANELWITH ENVOY-IQ METER 125A120 / 240 VACENVOY IQ(REVENUE GRADE METER)L1L1INTERCONNECT CABLERED-L1BLACK-L2GREEN- GROUNDROOF MOUNTEDWATERPROOF1(N) JUNCTION BOXROOFTOP600 V, NEMA 3-RUL LISTED20A/2P15A/2P20A/2P20A/2PGECGML1(E) 200A/2P(E) UTILITY METERTO UTILITY GRID(E) BI-DIRECTIONAL UTILITYMETER 1-PHASE, 3-W,120V/240VEXISTING GROUNDINGELECTRODE SYSTEMTO EARTHREF.NEC 250.52,250.53(A)(E) MAIN SERVICE PANEL200A RATED, 240V(E) MAIN BREAKER TOHOUSE 240 V, 200A/2PMETER TAP WITH MILBANKCONNECTOR KIT #K4977E32L1PMUTILITY PRODUCTIONMETER1-PH, 3-WIRE,120/240V, 200LOAD SIDE2REFERENCE POINT OFAPPLICABILITYL1L1VISIBLE-OPEN TYPE,LOCKABLE, READILYACCESSIBLE, LABELED,EATON DG222NRB 60AFUSIBLE WITH 60A/2PFUSES, 240VUTILITY AC DISCONNECTLINE SIDEDITEKDTK-120/240CM+SURGEPROTECTIONDEVICEREV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY-CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comONE LINE DIAGRAMPV-5PHASES OF INVERTERS : SINGLE PHASEPHASES OF DER SYSTEM : SINGLE PHASEALL PV EQUIPMENT INSTALLEDWITHIN 10' OF UTILITY METER INVERTER SPECIFICATIONSMANUFACTURER / MODEL ENPHASE IQ8X-80-M-US MICROINVERTERSMAXIMUM OUPUT POWERNOMINAL OUTPUT VOLTAGEMAXIMUM OUTPUT CURRENT380VA240 V1.58 AINVERTER QUANTITY29 NOS.1-PHASE, 60 HZ, UL 1741 LISTEDCOMBINER PANEL COMPLIANTWITH IEE 1547-2018 SURGE PROTECTION DEVICEDITEK DTK-120/240CM+ MEETS2023 NEC REQUIREMENTSPHOTOVOLTAIC INSTALLATION ELECTRICAL DIAGRAMPV MODULES AND MICROINVERTER :(29) REC410AA PURE-R (410W) SOLAR MODULES (29) ENPHASE IQ8X-80-M-US MICROINVERTERSDC SIZE : 11.890 kW DC AC SIZE : 11.020 AGGREGATE kW ACDESIGN SHALL MEET NEC REQUIREMENTS(2) BRANCHED CIRCUITS OF 10 MODULESWIRE /CONDUIT SCHEDULETAG DESCRIPTION12 (3)#6 THWN-2 CU & (1)#10 THWN-2 CU GROUND / 3/4" EMT CONDUIT(6)#10 THWN-2 CU & (1)#10 THWN-2 CU GROUND / 3/4" EMT CONDUIT3 (3)#6 THWN-2 CU & (1)#10 THWN-2 CU GROUND / 3/4" EMT CONDUIT(1) BRANCHED CIRCUIT OF 09 MODULES
10 MICROINVERTERS IN BRANCH CIRCUIT 209 MICROINVERTERS IN BRANCH CIRCUIT 3G10 MICROINVERTERS IN BRANCH CIRCUIT 1L2L129 -REC410AA PURE-R (410W) SOLAR MODULES ENPHASE Q CABLES29 - ENPHASE IQ8X-80-M-USMICROINVERTERS (240V) - MOUNTED UNDEREACH PANEL (690.14(D))INTEGRATED GROUNDING WIRENG(N) DEDICATEDPHOTOVOLTAIC SYSTEMENPHASE COMBINER PANELWITH ENVOY-IQ METER 125A120 / 240 VACENVOY IQ(REVENUE GRADE METER)L2L1L2L1INTERCONNECT CABLERED-L1BLACK-L2GREEN- GROUNDROOF MOUNTEDWATERPROOF1(N) JUNCTION BOXROOFTOP600 V, NEMA 3-RUL LISTED20A/2P15A/2P20A/2P20A/2PNGECGML2L1N(E) 200A/2P(E) UTILITY METERTO UTILITY GRID(E) BI-DIRECTIONAL UTILITYMETER 1-PHASE, 3-W,120V/240VEXISTING GROUNDINGELECTRODE SYSTEMTO EARTHREF.NEC 250.52,250.53(A)(E) MAIN SERVICE PANEL200A RATED, 240V(E) MAIN BREAKER TOHOUSE 240 V, 200A/2PMETER TAP WITH MILBANKCONNECTOR KIT #K4977E32L1L2NGPMUTILITY PRODUCTIONMETER1-PH, 3-WIRE,120/240V, 200LOAD SIDE2REFERENCE POINT OFAPPLICABILITYL1L2NGL1L2NGVISIBLE-OPEN TYPE,LOCKABLE, READILYACCESSIBLE, LABELED,EATON DG222NRB 60AFUSIBLE WITH 60A/2PFUSES, 240VUTILITY AC DISCONNECTLINE SIDEDITEKDTK-120/240CM+SURGEPROTECTIONDEVICEREV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY-CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comTHREE LINE DIAGRAMPV-6 INVERTER SPECIFICATIONSMANUFACTURER / MODEL ENPHASE IQ8X-80-M-US MICROINVERTERSMAXIMUM OUPUT POWERNOMINAL OUTPUT VOLTAGEMAXIMUM OUTPUT CURRENT380 VA240 V1.58 AINVERTER QUANTITY29 NOS.1-PHASE, 60 HZ, UL 1741 LISTEDALL PV EQUIPMENT INSTALLEDWITHIN 10' OF UTILITY METERCOMBINER PANEL COMPLIANTWITH IEE 1547-2018 SURGE PROTECTION DEVICEDITEK DTK-120/240CM+ MEETS2023 NEC REQUIREMENTSPHASES OF INVERTERS : SINGLE PHASEPHASES OF DER SYSTEM : SINGLE PHASEPHOTOVOLTAIC INSTALLATION ELECTRICAL DIAGRAMPV MODULES AND MICROINVERTER :(29) REC410AA PURE-R (410W) SOLAR MODULES (29) ENPHASE IQ8X-80-M-US MICROINVERTERSDC SIZE : 11.890 kW DC AC SIZE : 11.020 AGGREGATE kW ACDESIGN SHALL MEET NEC REQUIREMENTS(2) BRANCHED CIRCUITS OF 10 MODULESWIRE /CONDUIT SCHEDULETAG DESCRIPTION12 (3)#6 THWN-2 CU & (1)#10 THWN-2 CU GROUND / 3/4" EMT CONDUIT(6)#10 THWN-2 CU & (1)#10 THWN-2 CU GROUND / 3/4" EMT CONDUIT3 (3)#6 THWN-2 CU & (1)#10 THWN-2 CU GROUND / 3/4" EMT CONDUIT(1) BRANCHED CIRCUIT OF 09 MODULES
ELECTRICAL CALCULATIONSREV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY-CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comPV-7MICRO INVERTER CALCULATIONS:1.CURRENT CARRYING CONDUCTOR(A)BEFORE IQ COMBINER PANEL AMBIENT TEMPERATURE - (32)°C ...NEC 310.15(B)(3)(c) TEMPERATURE DERATE FACTOR - 0.96 ...NEC 310.15(B)(2)(a) GROUPING FACTOR - 0.8..NEC 310.15(B)(3)(a) CONDUCTOR AMPACITY = (INVERTER O/P CURRENT ) x 1.25 / A.T.F / G.F ...NEC 690.8(B) = [(10 x 1.58) x 1.25] / [0.96 / 0.8] = 25.72 A SELECTED CONDUCTOR - #10 THWN-2 ...NEC 310.15(B)(16)2.PV OVER CURRENT PROTECTION ...NEC 690.9(B) = TOTAL INVERTER O/P CURRENT x 1.25 = (29 x 1.58) x 1.25 = 57.28 A SELECTED OCPD = 60 A ...NEC 240.6 (B) AFTER IQ COMBINER PANEL TEMPERATURE DERATE FACTOR - 0.96 GROUPING FACTOR - 1 CONDUCTOR AMPACITY = (TOTAL INV O/P CURRENT) x 1.25 / 0.96 / 1 ...NEC 690.8(B) = [(29 x 1.58) x 1.25] / 0.96 = 59.66 A SELECTED CONDUCTOR - #6 THWN-2 ...NEC 310.15(B)(16)PERCENT OFVALUESNUMBER OF CURRENTCARRYING CONDUCTORS INEMT.804-6.707-9.5010-20AMBIENT TEMPERATURE SPECS RECORD LOW TEMP-27° AMBIENT TEMP (HIGH TEMP 2%)32° CONDUIT HEIGHT0.5" CONDUCTOR TEMPERATURE RATE90° INVERTER SPECIFICATIONSMANUFACTURER / MODEL ENPHASE IQ8X-80-M-US MICROINVERTERSMAXIMUM OUPUT POWERNOMINAL VOLTAGENOMINAL OUTPUT CURRENT380 VA240 V1.58 ASOLAR MODULE SPECIFICATIONSVMPIMPVOCISCDIMENSIONMANUFACTURER / MODEL REC410AA PURE-R (410W)49.4 V8.30 A59.2 V8.84 A68.1"L X 44"WX1.18"D IN INCH
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY-CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comPV-8WARNING LABELSLABEL 3AT POINT OF INTERCONNECTION,MARKED AT AC DISCONNECTINGMEANS.[NEC 690.54, NEC 690.13 (B)]LABEL 4AT POINT OF INTERCONNECTION FOREQUIPMENT CONTAINING OVERCURRENTDEVICES IN CIRCUTS SUPPLYING POWER TOA BUSBAR OR CONDUCTOR SUPPLIED FORMMULTIPLE SOURCES, EACH SERVICEEQUIPMENT AND ALL ELECTRIC POWERPRODUCTION SOURCE LOCATIONS.[NEC 705.12(B)(3)]LABEL 5PLACED ADJACENT TO THEBACK-FED BREAKER FROM THEINVERTER IF TIE IN CONSISTS OFLOAD SIDE CONNECTION TOBUSBAR.[NEC 705.12(B)(2)(3)(b)]LABEL 6AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND ENCLOSURES OF JUNCTIONBOXES, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10FT SECTION OR WHERESEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS.[NEC 690.31(G)(3&4)]LABEL 9(ONLY IF 3 OR MORE SUPPLY SOURCES TO ABUSBAR)SIGN LOCATED AT LOAD CENTER IF ITCONTAINS 3 OR MORE POWER SOURCES.[NEC 705.12(B)(2)(3)(c)]LABEL 8SIGN LOCATED AT RAPID SHUT DOWNDISCONNECT SWITCH [NEC 690.56(C)(3)].LABEL 7FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY ANDCONDUCTORS LEAVING THE ARRAY:SIGN TO BE LOCATED ON OR NO MORE THAN 3 FTAWAY FROM SERVICE DISCONNECTING MEANS TOWHICH THE PV SYSTEMS ARE CONNECTED AND SHALLINDICATE THE LOCATION OF ALL IDENTIFIED RAPIDSHUTDOWN SWITCHES IF NOT AT THE SAMELOCATION.[NEC 690.56(C)(1)(a)]LABEL 10PLACARD TO BE PLACED AT THE MAINBILLING METER PER XCEL ENERGY.LABEL 11PLACARD TO BE PLACED AT AC DISCONNECTPER XCEL ENERGY.LABEL 1FOR PV DISCONNECTING MEANSWHERE ALL TERMINALS OF THEDISCONNECTING MEANS MAY BEENERGIZED IN THE OPENPOSITION.[NEC 690.13(B)]LABEL 2AT EACH DC DISCONNECTINGMEANS, INCLUDING THE DCDISCONNECT AT THE INVERTER.[NEC 690.53]LABEL 12SIGN LOCATED AT MAIN SERVICEDISCONNECTING MEANS IF ALL ELECTRICALPOWER SOURCE DISCONNECTING MEANSARE GROUPED WITHIN 10' AND LINE OF SITEOF MAIN SERVICE DISCONNECT[NEC 705.10].LABEL 13SIGN LOCATED AT AC COMBINER BOX FORALL MICRO-INVERTER / AC MODULE INSTALLS(IF APPLICABLE).! WARNINGTERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONELECTRIC SHOCK HAZARDRATED AC OUTPUT CURRENT ANOMINAL OPERATING AC VOLTAGEVPHOTOVOLTAIC SYSTEMAC DISCONNECT!! WARNINGWARNING: PHOTOVOLTAICPOWER SOURCETURN RAPID SHUTDOWNSWICH TO THE "OFF"POSITION TO SHUT DOWNPV SYSTEM AND REDUCESHOCK HAZARD IN ARRAYSOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNSOLAR ELECTRICPV PANELSRAPID SHUTDOWNSWITCH FORSOLAR PV SYSTEM! WARNINGTHIS EQUIPMENT IS FED BY MULTIPLESOURCES. TOTAL RATING OF ALLOVERCURRENT DEVICES, EXCLUDINGMAIN SUPPLY OVERCURRENTDEVICE, SHALL NOT EXCEEDAMPACITY OF BUSBAR.PHOTOVOLTAICSYSTEM CONNECTEDUTILITY AC DISCONNECTRAPID SHUTDOWN TESTNOT REQUIRED!CAUTION!ALL ELECTRIC POWER SOURCEDISCONNECTING MEANS GROUPEDAND LABELED WITHIN 10 FT ANDLINE OF SIGHT OF THIS LOCATIONDIRECT CURRENTPHOTOVOLTAIC POWER SOURCEMAXIMUM VOLTAGE:VDCMAX CIRCUIT CURRENT:AMPSNO DC WIRES PRESENT! WARNINGINVERTER OUTPUT CONNECTIONDO NOT RELOCATETHIS OVERCURRENTDEVICEDUAL POWER SUPPLYSOURCES: UTILITY GRID AND PVSOLAR ELECTRIC SYSTEM0045.82240PRODUCTION METERLABEL 15PLACARD TO BE PLACED ATBI-DIRECTIONAL METER PER XCELENERGY.LABELING NOTES:1.LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINEEXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATEADJUSTMENTS.2.LABELING REQUIREMENTS BASED ON THE 2023 NATIONAL ELECTRIC CODE, OSHA STANDARD 19010.145,ANSI Z535.3.MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.4.LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC 110.21]5.LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, ANDPERMANENTLY AFFIXED [NEC 690.31(G)]!!
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY-CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comPV-9MODULES DATASHEET
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY-CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comPV-10INVERTER DATASHEET
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY-CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comPV-11ATTACHMENT DATASHEET
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY09/09/2024HDSHEET NUMBERREVIEWED BY-CENTAURI SYSTEMS3922 VAN BUREN ST NE,MINNEAPOLIS, MN 55421License #EA765306AHJ STAMPSTEVEN SWANSON
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044 CONTRACTOR INFO:NAME: JAMES RAYMONDCELL: +1 (763) 229-9046J.raymond@solarbycentauri.comPV-12RACKING DATASHEET
MSP
ACD18346 KINGSWAY PATH, LAKEVILLE, MN 55044(E) SERVICEDISCONNECT 1 OF 2(INSIDE HOUSE)(N) SERVICEDISCONNECT 2 OF 2(OUTSIDE HOUSE)POWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:CAUTIONN
18346 KINGSWAY PATH,
LAKEVILLE, MN 55044
Design Criteria:
9/27/2024
CENTAURI SYSTEMS
Attn.: To Whom It May Concern re
job: STEVEN SWANSON
The following calculations are for the structural engineering design of the photovoltaic panels and are valid
only for the structural info referenced in the stamped plan set. The verification of such info is the
responsibility of others.
After review, I certify that the roof structure has sufficient structural capacity for the applied PV loads.
All mounting equipment shall be designed and installed per manufacturer's approved installation
specifications.
Code 2020 International Residential Code(MBC) (ASCE 7-16)
Risk category II Wind Load (component and Cladding)
Dr 10 psf V 115 mph
DPV Exposure B
Lr
Roof Dead Load
PV Dead Load
Roof Live Load
Ground Snow S
2.28 psf
20 psf
58 psf
9/27/2024
2 of 5
Roof Properties:
Roof Type =
Roof Pitch (deg) =
Mean Roof Height (ft) =
Attachment Trib Width (ft) =
Attachment Spacing (ft) =
Framing Type =
Framing Size =
Framing OC Spacing (in.) =
Section Thickness, b (in.) =
Section Depth, d (in.) =
Section Modulus, Sx (in.^3) =
Moment of Inertia, Ix (in.^4) =
Framing Span (ft) =
Deflection Limit D+L (in.) =
Deflection Limit S or W (in.) =
Framing Upgrade =
Sister Size =
Wood Species =
Wood Fb (psi) =
Wood Fv (psi) =
Wood E (psi) =
CD (Wind) =
CD (Snow) =
CM = Ct = CL = Ci =
CF =
Cfu =
Cr =
F'b_wind (psi) =
F'b_snow (psi) =
F'v_wind (psi) =
F'v_snow (psi) =
M_allowable_wind (lb-ft) =
M_allowable_snow (lb-ft) =
V_allowable_wind (lbs) =
V_allowable_snow (lbs) =
E' (psi) =
12
2.4
1.60
Adequate
NA
DF #2
900
180
1600000
1.6
1.15
1.0
1.3
1.00
1.15
2153
1547
288
207
1357
975
1584
1139
1600000
2x4
24
1.5
3.4
5.8
20.6
4
Truss
15
3.25
Comp Shingle
27
Roof
9/27/2024
3 of 5
Wind Load Cont.
115 mph
B
1.0
0.96
0.83
0.87
ASCE 7-16 Figure 26.5-1B
ASCE 7-16 Sec 26.8.2
ASCE 7-16 Table 26.10-1
ASCE 7-16 Table 26.6-1
ASCE 7-16 Table 26.9-1
25.60 psf
27.0 Degrees
1.5 Conservatively assuming all exposed
0.8 conservatively assuming 10 ft2 effective area
Uplift (W)Zone(1) Zone(2r) Zone(2e)Zone(3)
Fig. 30-3-2 -2.1 -2.6 -2.7 -2.7
Eq. 29.4-7 -62.51 -53.56 -65.41 -57.37
0.3 Figure 30.3-2
GCp=
P=qh(GCp)(γE)(γa)=
GCp=
P=qh(GCp)(γE)(γa)=6.56 Equation 29.4-7
Truss Attachments: 0.6D+0.6W (CD=1.6)
Connection Check
Attachment max. spacing=4 ft
#14 RD STRUCTURAL SCREW Withdrawal Value=266 lbs/in
2.5 in
Table 12.2A - NDS
DFL Assumed
Prying Coefficient
Allowable Capacity=
Zone Trib Width Area (ft)
1.4
740 lbs Uplift
(lbs)Down (lbs)
Zone(1)4 11.0 85.6
Zone(2r)4 11.0
Zone(2e)4 11.0
Zone(3)4 11.0
85.6
85.6
85.6
Conservative Max=
174.5
224.2
178.5
221.2 <740
CONNECTION IS OK
Risk Category =
V=
Exposure =
KZt =
KZ =
1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift
governs
2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw.
Embedment in sheading or other material does not count.
II
Kd =
Ke =
qh= 0.00256KzKztKdKeV2=
Pitch =
γE=
γa=
Lag Screw Penetration
185.5
4 of 5
Vertical Load Resisting System Design
Roof Framing Truss
Snow Load Fully Exposed
pg=58 psf Ct =1.1
Ce =0.9 Is =1.0
pf = 3 psf
pfmin. = 3.2 psf
ps = 1 psf Conservatively (Cs=1)59.3 plf
Max Length, L = 8.0 ft (Truss maximum Allowable Horizontal Span)
24 in
10 psf 20 plf
Tributary Width, WT =
Dr =
PvDL =3 psf 12 plf
Load Case: DL+0.75(0.6W+S)
0.75(Pnet+Ps)+ Ppvcos(θ)+PDL=41 plf
Mdown=328 lb-ft
975 lb-ft >168 lb-ft OKMallowable = Sx x Fb' (wind)=
Load Case: DL+S
Ps+ Ppvcos(θ)+PDL=38 plf
Mdown=306 lb-ft
975 lb-ft >172 lb-ft OKMallowable = Sx x Fb' (wind)=
Load Case: DL+0.6W
Pnet+ Ppvcos(θ)+PDL=37.7 plf
Max Moment, Mu=302 lb-ft
Mallowable = Sx x Fb' (wind)=1357 lb-ft >275 lb-ft OK
Pv max Shear=85.6 lbs
244 lbsShear, Vu=wL/2+Pv Point Load =
Max Shear, Vu=wL/2+Pv Point Load = 214 lb
Member Capacity
DF-L No.2
2X4 CL CF Ci Cr KF φ λFb =900 psi 1.0 1.3 1.0 1.15 2.54 0.85 0.8 1346 psi
Fv =180 psi N/A N/A 1.0 N/A 2.88 0.75 0.8 180 psi
E =1600000 psi N/A N/A 1.0 N/A N/A N/A N/A 1600000 psiEmin =580000 psi N/A N/A 1.0 N/A 1.76 0.85 N/A 580000 psi
3.5 in
1.5 in
Depth, d =
Width, b =
Cross-Sectonal Area, A =5.25 in2
Moment of Inertia, Ixx =Section Modulus, Sxx =7.5425 in20.7469 in4
3
848.5 lb-ft SatisfactoryAllowable Moment, Mall = Fb'Sxx =
Allowable Shear, Vall = 2/3Fv'A =990.1 lb
DCR=Mu/Mall =0.34 < 1
DCR=Vu/Vall =0.22 < 1 Satisfactory
Design Value Adjusted Value
5 of 5
Existing structure is assumed to have been designed and constructed following appropriate codes at
time of erection, and assumed to have appropriate permits. The calculations produced are only for the
roof framing supporting the proposed PV installation referenced in the stamped planset and were
completed according to generally recognized structural analysis standards and procedures, professional
engineering and design experience, opinions and judgements. Existing deficiencies which are unknown or
were not observable during time of inspection are not included in this scope of work. All PV modules,
racking, and mounting equipment shall be designed and installed per manufacturer's approved
installation specifications. The Engineer of Record and the engineering consulting firm assume no
responsibility for misuse or improper installation. This analysis is not stamped for water leakage.
Framing was determined based on information in provided plans and/or photos, along with engineering
judgement. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and
spans noted in the stamped plans, calculations, and cert letter (where applicable) and notify the
Engineer of Record of any discrepancies prior to starting construction. Contractor shall also verify that
there is no damaged framing that was not addressed in stamped plans, calculations, and cert letter
(where applicable) and notify the Engineer of Record of any concerns prior to starting construction.
Siesmic Loads Check
Roof Dead Load 10 psf
21.98%2.28 psf
7.3 psf
% or Roof with Pv
Dpv and Racking
Average Total Dead Load
Increase in Dead Load 3.4% OK